NERC PRC-026 Evaluation Dr. Juergen Holbach Quanta...
Transcript of NERC PRC-026 Evaluation Dr. Juergen Holbach Quanta...
NERC PRC-026 Evaluation
Dr. Juergen Holbach Quanta Technology
Raleigh, NC
Overview
Ø Basics of Power Swing Ø Impact on Distance Protection Relays Ø NERC PRC026
Simple two machine model
Vs Va Vb Vr
I*Xs1 I*Xs2I*Xl
ϑIa
Real power in relation to voltage angle
ϑ
P
Ps=Pr
Pmax
90 180
stableworkingarea
)sin(21
ϑSlS
RS
XXXVVP++
⋅=
Impedances in relation to the voltage angle
I*Zs2
Vs
Va Vb
Vr
I*Zs1 I*Zl
ϑ=60
Ia
Z loadϑ=60
R
X
Impedance seen by the relay inthe electr. center
Impedanceseen by the relay on Bus Blooking into the motor
Impedances in relation to the voltage angle
ϑ=120
VaIa
VrVs Vb
I*Zs2I*Zs1 I*Zl
Z loadϑ=60
R
X
Z loadϑ=120
Impedances in relation to the voltage angle
I*Zs2
VsVb
Vr
I*Zs1 I*Zl
ϑ=180
Ia
Va=0
Z loadϑ=60
R
X
Z loadϑ=120
Z loadϑ=180
Impedances trajectory for a system with losses
X
Impedancetrajectoryseenbytherelayintheelectr.center
R
Z loadϑ=60
Z loadϑ=120
Z loadϑ=180
ImpedancetrajectoryseenbytherelayonBusBlook ingintothemotor
Impedances trajectory with unequal machine voltages
VsVa
Vr
ϑ=0Ia
X
RZ loadϑ=60
Z loadϑ=120
Z loadϑ=180
ϕ
Z loadϑ=0
Power Swing Trajectories fro different conditions
B
A
0.2
0.3
0.4
0.5
0.6 0.65 0.7 0.75 0.8
0.85
0.9
0.95
1.05
1.1
1.15
1.21.251.31.41.51.61.7
∅=20°
∅=25°30°40° 35°45°50°
1.71.61.5
1.41.31.251.2
∅=340°
1.15
1.1
1.05
∅=335°
0.95
0.9
0.85
0.80.75
0.7 0.65 0.6
∅=0°
1.81.92.0
2.5
5.060°
75°90°120°150°180°21
0°240°270°285°∅= 300°
B
A
E
E
B
A
E
E
B
A
E
E
NERC PRC 026 requirement
Ø Criterion A: Ø An impedance-based relay used for tripping is expected to not trip for a stable power swing
when the relay characteristic is completely contained within the unstable power swing region. The unstable power swing region is formed by the union of three shapes in the impedance (RX) plane (see Figure 3‑10); (1) a lower loss-of-synchronism circle based on a ratio of the sending-end to receiving-end voltages of 0.7; (2) an upper loss-of-synchronism circle based on a ratio of the sending-end to receiving-end voltages of 1.43; (3) a lens that connects the endpoints of the total system impedance (with the parallel transfer impedance removed) bound by varying the sending-end and receiving-end voltages from 0.0 to 1.0 per unit, while maintaining a constant system separation angle across the total system impedance where:
Ø 1. The system separation angle is at least 120 degrees or an angle less than 120 degrees where a documented transient stability analysis demonstrates that the expected maximum stable separation angle is less than 120 degrees.
Ø 2. All generation is in service and all transmission BES elements are in their normal operating state when calculating the system impedance.
Ø 3. Saturated (transient or sub-transient) reactance is used for all machines.
Impedances trajectories
B
A
0.2
0.3
0.4
0.5
0.6 0.65 0.7 0.75 0.8
0.85
0.9
0.95
1.05
1.1
1.15
1.21.251.31.41.51.61.7
∅=20°
∅=25°30°40° 35°45°50°
1.71.61.5
1.41.31.251.2
∅=340°
1.15
1.1
1.05
∅=335°
0.95
0.9
0.85
0.80.75
0.7 0.65 0.6
∅=0°
1.81.92.0
2.5
5.060°
75°90°120°150°180°21
0°240°270°285°∅= 300°
B
A
E
E
B
A
E
E
B
A
E
E
PRC-026-1 Attachment B- Criterion A
PRC-026: Power System Model Simplification
PRC-026: Lens Point 1
Evaluating Limitation
PRC026 Limit
PRC026 Limit-Transformed
Summary
Ø With NERC PRC026, Protection engineers are required to check that stable Power Swings impedances will not enter any fast tripping Distance Protection Zone
Ø Evaluation process requires l Building Equivalent Network Model around the line
under investigation l Calculation of limiting Stable Power Swing impedances l Check if impedance enter fast tripping Distance Zone