7/21/2019 012873.01_EN-en_2004 http://slidepdf.com/reader/full/01287301en-en2004 1/33 2004-12-20 ICS:13.060.20:67.250  ΕΛΟΤ EN 12873.01  ΕΛΛΗΝΙΚΟ ΠΡΟΤΥΠΟ HELLENIC STANDARD Επίδραση των υλικών στο πόσιµο νερό - Επίδραση λόγω µετανάστευσης - Μέρος 1: Μέθοδος δοκιµής για µη µεταλλικά και µη τσι µεντοειδή βιοµηχανικά προϊόντα Influence of materials on water intended for human consumption - Influence due to migration - Part 1: Test method for non-metallic and non-cementitious factory made products Κλάση Τιµολόγησης : 13 © ΕΛΟΤ ΕΛΛΗΝΙΚΟΣ ΟΡΓΑΝΙΣΜΟΣ ΤΥΠΟΠΟΙΗΣHΣ  Α.Ε.  Αχαρνών 313 11145  Αθήνα 

description

012873.01_EN-en_2004

Transcript of 012873.01_EN-en_2004

Page 1: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 1/33

2004-12-20 ICS:13.060.20:67.250

  ΕΛΟΤ EN 12873.01 

ΕΛΛΗΝΙΚΟ ΠΡΟΤΥΠΟ 

HELLENIC STANDARD

Επίδραση  των υλικών στο πόσιµο  νερό  - Επίδραση  λόγω  µετανάστευσης  - Μέρος  1:Μέθοδος δοκιµής για µη µεταλλικά και µη τσιµεντοειδή βιοµηχανικά προϊόντα 

Influence of materials on water intended for human consumption - Influence due to migration -Part 1: Test method for non-metallic and non-cementitious factory made products

Κλάση Τιµολόγησης: 13

© ΕΛΟΤ  ΕΛΛΗΝΙΚΟΣ ΟΡΓΑΝΙΣΜΟΣ ΤΥΠΟΠΟΙΗΣHΣ  Α.Ε.   Αχαρνών 313 •11145  Αθήνα 

Page 2: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 2/33

ΕΛΟΤ EN 12873.01

Εθνικός Πρόλογος 

Αυτό είναι το Φύλλο Επικύρωσης 

του εγκεκριµένου Ευρωπαϊκού 

Προτύπου 

EN 12873-1 : 2003

ως Ελληνικού Προτύπου.

Το πρότυπο αυτό διατίθεται στην 

Αγγλική, ή Γαλλική ή Γερµανική 

γλώσσα από τον Ελληνικό 

Oργανισµό Τυποποίησης Α.Ε.

National Foreword

This Endorsement Sheet ratifies

the approval of European

Standard

EN 12873-1 : 2003

as a Hellenic Standard.

This standard is available in

English, French or German from

the Hellenic Organization for

Standardization S.A.

Page 3: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 3/33

EUROPEAN STANDARD

NORME EUROPÉENNE

EUROPÄISCHE NORM

EN 12873-1

November 2003

ICS 13.060.20; 67.250

English version

Influence of materials on water intended for human consumption- Influence due to migration - Part 1: Test method for non-

metallic and non-cementitious factory made products

Influence sur l'eau des matériaux en contact avec l'eaudestinée à la consommation humaine - Influence de la

migration - Partie 1: Méthode d'essai des matériaux defabrication industrielle, excepté les matériaux métalliques etceux à base de ciment

Einfluss von Bedarfsgegenständen auf Trinkwasser -Einfluss infolge der Migration - Teil 1: Prüfverfahren für

nichtmetallische und nicht zementgebundene fabrikmäßighergestellte Produkte

This European Standard was approved by CEN on 1 September 2003.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Management Centre or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the officialversions.

CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and UnitedKingdom.

EUROPEAN COMMITTEE FOR STANDARDIZATION

COMIT É E UROPÉ E N DE NORMAL ISAT ION

EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: rue de Stassart, 36 B-1050 Brussels

 © 2003 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.

Ref. No. EN 12873-1:2003 E

Page 4: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 4/33

EN 12873-1:2003 (E)

2

Contents page

Foreword............................................................................................................................................................. 3

Introduction ........................................................................................................................................................ 4

1 Scope ..................................................................................................................................................... 5

2 Normative references ........................................................................................................................... 5

3 Terms and definitions........................................................................................................................... 5

4 Principle................................................................................................................................................. 7

5 Reagents................................................................................................................................................ 75.1 Waters to be used for testing .............................................................................................................. 75.2 Cleaning liquids for glassware............................................................................................................ 75.3 Other reagents....................................................................................................................................... 8

6 Apparatus .............................................................................................................................................. 8

7 Test samples and test pieces .............................................................................................................. 97.1 Sampling, transport and storage of test samples ............................................................................. 97.2 Test piece preparation.......................................................................................................................... 97.3 Surface area-to-volume ratio (S/V).................................................................................................... 10

8 Pretreatment of test pieces................................................................................................................ 118.1 General................................................................................................................................................. 11

8.2 Test pieces to be tested at (23 ± 2) C .............................................................................................. 11

8.3 Test pieces to be tested at elevated temperature (60 C to 85 C).................................................. 118.4 Prewashing.......................................................................................................................................... 12

9 Test procedure.................................................................................................................................... 129.1 Migration of substances..................................................................................................................... 129.2 Procedural blank tests ....................................................................................................................... 139.3 Analysis ............................................................................................................................................... 13

10 Calculation of test results.................................................................................................................. 1310.1 Calculation of the concentration of the substances in the migration water ................................ 1310.2 Calculation of the migration rate of the measured substances..................................................... 1410.3 Calculation of the mean migration rate ............................................................................................ 14

11 Test report ........................................................................................................................................... 1411.1 General information............................................................................................................................ 1411.2 Information on the test procedure .................................................................................................... 1511.3 Test results .......................................................................................................................................... 15

Annex A (informative) Arrangement for flushing pipes with nominal size greater than DN 80 ............... 17

Annex B (informative) Additional procedures for testing non-homogeneous products and pipeswith nominal size greater than DN 80 ................................................................................................ 20B.1 Arrangements for testing................................................................................................................... 20B.2 Flushing of the test piece................................................................................................................... 20B.3 Blank test............................................................................................................................................. 20B.4 Sealing ................................................................................................................................................. 20B.5 Calculation of the surface area-to-volume ratio (S/V) value for test arrangement 1 (see

Figure B.1) ........................................................................................................................................... 23

Annex C (informative) Examples of extended collection and analysis of migration waters ...................... 25

Annex D (informative) Procedural tests using standard additions (positive controls)............................... 26

Annex E (informative) Flow diagrams for migration test procedure for cold water temperature andelevated temperature.......................................................................................................................... 27

Bibliography ..................................................................................................................................................... 31

Page 5: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 5/33

EN 12873-1:2003 (E)

3

Foreword

This document (EN 12873-1:2003) has been prepared by Technical Committee CEN/TC 164 “Water supply”,the secretariat of which is held by AFNOR.

This European Standard shall be given the status of a national standard, either by publication of an identicaltext or by endorsement, at the latest by May 2004, and conflicting national standards shall be withdrawn at thelatest by May 2004.

It has been drawn up with the objective to describe a test method to determine the migration of substances fromnon-metallic and non-cementitious products for use in contact with water intended for human consumption.

Annex A, which is informative, describes an alternative arrangement for flushing pipes having a nominal sizegreater than DN 80.

Annex B, which is informative, describes additional procedures for testing non-homogeneous products and pipeshaving a nominal size greater than DN 80.

Annex C, which is informative, describes a schedule for the preparation of migration waters.

Annex D, which is informative, describes procedural tests using standard additions (positive controls).

Annex E, which is informative, describes the migration test procedure in a schematic manner.

This European Standard will be one of a series of standards on test methods which supports the appropriatestandards.

This standard, part 1, is the first in a series of standards for dealing with the influence of migration from materialson water intended for human consumption, including:

    Part 1 : Test method for non-metallic and non-cementitious factory made products;

    Part 2 : Test method for non-metallic and non-cementitious site-applied materials;

    Part 3 : Test method for ion exchange and absorbent resins;

    Part 4 : Test method for membrane water treatment systems.

According to the CEN/CENELEC Internal Regulations, the national standards organizations of the followingcountries are bound to implement this European Standard: Austria, Belgium, Czech Republic, Denmark,Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands,Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and the United Kingdom.

Page 6: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 6/33

EN 12873-1:2003 (E)

4

Introduction

In respect of potential adverse effects on the quality of water intended for human consumption caused by thematerials, it is called to mind that, while awaiting the adoption of verifiable European acceptance criteria, therelevant national regulations remain in force.

Page 7: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 7/33

EN 12873-1:2003 (E)

5

1 Scope

This European Standard specifies a procedure to determine the migration of substances from non-metallicand non-cementitious factory made or factory applied products for use in contact with water intended for

human consumption.

This standard is applicable to products intended to be used under various conditions for the transport andstorage of water intended for human consumption, including raw water used for the production of waterintended for human consumption. It covers the extraction by water of substances from the finished products.

2 Normative references

This European Standard incorporates by dated or undated reference, provisions from other publications.These normative references are cited at the appropriate places in the text, and the publications are listedhereafter. For dated references, subsequent amendments to or revisions of any of these publications apply to

this European Standard only when incorporated in it by amendment or revision. For undated references thelatest edition of the publication referred to applies (including amendments).

EN ISO 7393-2, Water quality – Determination of free chlorine and total chlorine – Part 2: Colorimetric method using N, N-diethyl-1, 4-phenylenediamine for routine control purposes (ISO 7393-2:1985).

3 Terms and definitions

For the purposes of this European Standard, the following terms and definitions apply.

3.1test

technical operation that consists of the determination of one or more characteristics of a given product

3.2test procedurespecified technical method for performing a test

3.3test reportdocument that presents test results and other information relevant to a test

3.4test laboratorylaboratory that performs tests

3.5productmanufactured item, in its finished form, that comes into contact with water intended for human consumption,or a component part of a manufactured item

3.6homogeneous productproduct where the water contact surface is made from the same material as the remainder of the product

3.7non-homogeneous product

product where the water contact surface is made from a material that differs from those comprising theremainder of the product

Page 8: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 8/33

EN 12873-1:2003 (E)

6

3.8fitting, ancillarycomplete functional unit made up of one or more components or materials, parts of which are in contact withwater, e.g. taps, valves, water meters, water filters, pipe connectors and flexible hose assemblies

3.9test samplesample of a product submitted for testing

3.10test piecetest sample, or a part of it, that is tested

3.11tap waterwater intended for human consumption

(See also 5.1.1).

3.12test waterwater used for migration testing

(5.1.2 and 5.1.3).

3.13disinfection treatment waterwater used for preliminary chlorination (5.1.4)

3.14prewashing water

water used for prewashing (5.1.5)

3.15blank watertest water (5.1.2 and 5.1.3) which has been kept at the same specified conditions as migration water (3.18)but without contact with test pieces

3.16migration periodperiod of time (24 h or 72h, see clause 4) in which the migration is carried out under specified conditions

3.17migrationmovement of a substance or substances from test pieces into test water

3.18migration watertest water after exposure to a test piece under specified conditions

3.19migration ratemass of a measured substance or substances (in mg) migrating from one square decimetre of a test piece

into the test water in one day at a specified temperature (°C)

3.20

lininglayer of material applied to a product and intended to come into contact with water intended for humanconsumption, e.g. the inside surfaces of pipes, fittings or storage vessels. Excluded are layers, such as

Page 9: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 9/33

EN 12873-1:2003 (E)

7

coatings, not intended for contact with water intended for human consumption, e.g. as applied to the outsidesurfaces of pipes and fittings for corrosion protection

3.21geomembranes

flexible water impermeable membranes normally used to avoid draining of stored water into surrounding soiland sub-soil strata

4 Principle

Each test piece is subjected to a specified pretreatment procedure of stagnation and prewashing. The surface ofthe test piece, that is exposed in practice to water intended for human consumption, is brought into contact withtest water during at least three sequential migration periods. A migration period is either;

    72 h at 23 °C for products intended to come into contact with cold water,

    24 h at a specified temperature in the range 60 °C to 85 °C for products intended to come into contactwith warm or hot water.

Migration rates for the first three migration periods are determined by analysis of the required substances in thecorresponding migration waters.

NOTE 1 The test is carried out under conditions to ensure that calculation of a reliable migration rate is facilitated.These conditions are not meant to simulate "real use conditions". Relating the results obtained from this standard to "realuse conditions" is carried out using a conversion procedure. This procedure will be specified in regulations.

NOTE 2 The choice of the type of test water (chlorinated and/or chlorine-free), the temperature of the test water, thenumber of additional migration periods and the necessity for a preliminary chlorination (see clause 8) will be specified byproduct/system standards or national regulations.

5 Reagents

For the purposes of this European Standard, the following reagents apply:

5.1 Waters to be used for testing

5.1.1 tap water, water intended for human consumption with a free chlorine content less than 0,2 mg/las Cl2.

5.1.2 test water, chlorine free water with a conductivity of < 2 mS/m and a total organic content (TOC) of< 0,2 mg/l C, e.g. prepared by reverse osmosis, deionization or distillation, followed by activated carbonfiltration.

5.1.3 chlorinated test water, test water according to 5.1.2 having an active chlorine content of(1 ± 0,2) mg/l as Cl2 (5.3.1).

5.1.4 disinfection treatment water, test water according to 5.1.2 having an active chlorine content of(50 ± 5) mg/l as Cl2 (5.3.1).

5.1.5 prewashing water, tap water (5.1.1).

5.2 Cleaning liquids for glassware

5.2.1 hydrochloric acid, concentrated (30% mass per volume) analytical reagent grade.

Page 10: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 10/33

EN 12873-1:2003 (E)

8

5.2.2 hydrochloric acid solution, prepared by slowly adding (0,5 ± 0,01) l of concentrated hydrochloricacid (5.2.1) to (0,5 ± 0,01) l of test water (5.1.2).

NOTE Care is needed because the solution may generate heat.

5.2.3 nitric acid, concentrated (65% mass per volume) analytical reagent grade.

5.2.4 nitric acid solution, prepared by slowly adding (0,5 ± 0,01) l of concentrated nitric acid (5.2.3) to(0,5 ± 0,01) l of test water (5.1.2).

NOTE Care is needed because the solution may generate heat.

5.2.5 sulphuric acid, concentrated (density 1,84 g/ml) analytical reagent grade.

5.2.6 chromic acid, analytical reagent grade (5% mass per volume) or prepared by dissolving (50 ± 1) g ofchromium (VI) oxide in (1 ± 0,02) l of sulphuric acid (5.2.5).

NOTE Chromic acid is a storage hazard; it can burst a sealed container due to carbon dioxide release. It is a

powerful oxidizer and can give potentially explosive reactions with oxidizable materials. It can ignite on contact withacetone or alcohols. When heated to decomposition it emits acrid smoke and irritating fumes.

5.3 Other reagents

5.3.1 sodium hypochlorite solution, prepared from a technical or general purpose reagent grade ofsodium hypochlorite (NaOCl), using test water (5.1.2) and having a known concentration of about 0,1 % bymass of free chlorine determined in accordance with EN ISO 7393-2.

NOTE Unless tests have proved otherwise the sodium hypochlorite solution should be considered unstable andprepared on the day of use.

6 Apparatus

6.1 Vessels, containers, stoppers and connectors  shall consist of a material, such as glass, PTFE orstainless steel, that is inert under the specified test conditions (clause 9).

NOTE The material PTFE should only be used when there is a small contact area with the test water. Thus PTFE isunsuitable for containers.

6.2 Plates stainless steel, mild steel, (sand-blasted) glass or concrete/cement-mortar plates, for testinglinings or the material itself. The plates shall be covered completely.

6.3 Equipment, capable of maintaining the appropriate migration temperature, e.g. (23 ± 2) °C, or

(60 ± 2) °C to (85 ± 2) °C.

6.4 Cleaning

Laboratory glassware, stainless steel plates and sand blasted glass plates shall be cleaned by washing with abiodegradable laboratory detergent, followed by rinsing with either hydrochloric acid solution (5.2.2) (exceptfor stainless steel), nitric acid solution (5.2.4) or chromic acid (5.2.6) and finally by thoroughly rinsing with testwater (5.1.2). Drain the plates and dry them in a hot air cabinet.

Page 11: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 11/33

EN 12873-1:2003 (E)

9

7 Test samples and test pieces

7.1 Sampling, transport and storage of test samples

Sample products in accordance with the relevant product/system standard or with the relevant nationalregulations when applicable.

Ensure that the surface of test pieces intended to come into contact with test water shall be free fromadhesive tape, labels, ink or pencil marks. Care shall be taken to ensure that the transport and storageconditions shall not influence the test results.

NOTE 1 If the test samples have to be stored, then this should be done in the absence of light at (23 ± 5) °C, instainless steel containers, tissue-paper, glassware or other materials, which do not influence the results of the migrationtest, except where the supplier of the test samples provides alternative written storage instructions which are those thatthe products are subject to in practice.

NOTE 2 Storage envelopes or pockets should not be sealed, dusting powder should not be used and cleaning shouldnot be carried out unless any of these procedures form part of the usual production procedures. Where appropriate,

storage containers should be cleaned using the same procedures as are used for the test containers.

7.2 Test piece preparation

7.2.1 General

Prepare test pieces in such a way that only the surface intended to come into contact with water intended forhuman consumption is exposed to the test water (5.1.2 and/or 5.1.3).

For homogeneous materials it is acceptable to expose the whole test piece to the test water, includingsurfaces not intended to come into contact with water intended for human consumption. Calculate the totalsurface area of the test piece. The calculation of the surface-area-to-volume (S/V) ratio (7.3) shall include the

total surface area of the test piece.

NOTE If a homogeneous product has to be cut to obtain the required test piece size, this should be done in a mannerthat ensures the area of the cut edges is as small as possible.

7.2.2 Pipes and hoses

7.2.2.1 Use the internal diameter for the S/V ratio calculation.

7.2.2.2 Assess migration from pipes with an internal diameter ≤ DN 80 by using pipes as test vessels witha length that provides sufficient migration water for analysis.

7.2.2.3 Migration from pipes with an internal diameter > DN 80, where the internal and external surfaceshave the same properties, can be assessed by either immersing pipe segments in test water (5.1.2 and/or5.1.3) in glass containers or using one of the test arrangements detailed in annex B.

7.2.2.4 Test pieces from composite pipes, i.e. pipes whose internal and external surfaces have differentproperties, with an internal diameter > DN 80, shall be tested in such a way that only the surface areaintended to come into contact with water intended for human consumption is exposed to the test water (5.1.2and/or 5.1.3). Suitable arrangements are given in annex B.

7.2.3 Fittings and ancillaries

7.2.3.1 The number of fittings or ancillaries to be tested has to be chosen in such a way that therequirements described in 7.2.1 are satisfied.

7.2.3.2 Assess migration from fittings and ancillaries by immersion according to the requirementsdescribed in 7.2.1.

Page 12: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 12/33

EN 12873-1:2003 (E)

10

7.2.4 Factory applied linings

7.2.4.1 Test pieces with factory applied linings shall be prepared as described in 7.2.1, 7.2.2 and 7.2.3.

7.2.4.2 If it is not possible to test the original final product then test pieces shall be prepared by the

manufacturer or a contractor in accordance with the manufacturer's written instructions under supervision ofthe responsible body. Test panels/plates shall be fully coated in accordance with the standard factoryprocedure. If this is impractical, then a method giving an equivalent product surface to that produced by thestandard factory procedure shall be used.

7.2.4.3 Assess migration from other linings applied to other products by immersing plates (e.g. stainlesssteel or (sand blasted) glass plates), completely coated with the product, in the test water (5.1.2 and/or 5.1.3).

7.2.4.4 The number of coated plates has to be chosen in such a way that they meet the requirements of7.3.1 when tested in containers (6.1) that are completely filled with test water (5.1.2 and/or 5.1.3) and closedwith a lid.

7.2.5 Geomembranes

7.2.5.1 Geomembranes (3.21) may be homogeneous (composed of one material only) or non-homogeneous (comprising a complex laminate system of several materials).

7.2.5.2 Assess migration from geomembranes, if homogeneous, by immersing test pieces in the testwater (5.1.2 and/or 5.1.3). If non-homogeneous go to 7.2.7.

7.2.6 Other homogeneous products

7.2.6.1 Migration from these products shall be assessed using test pieces immersed in the test water(5.1.2 and/or 5.1.3).

7.2.7 Other non-homogeneous products

7.2.7.1 Test pieces derived from non-homogeneous products shall have the same composition andstructure as the finished products.

7.2.7.2 Test the test pieces in such a way that only the surface intended to come into contact with waterintended for human consumption is exposed to the test water (5.1.2 and/or 5.1.3). (See also annex B).

7.3 Surface area-to-volume ratio (S/V).

7.3.1 The ratio of the surface area (S ) of the test piece intended to come into contact with test water to

the volume (V ) of the test water shall be expressed per decimeter, i.e dm-1 (which is dm2 /dm3 or dm2 /l). Use a

surface area-to-volume ratio in the range of 5 dm-1 – 40 dm-1.

NOTE The S/V ratio can be specified by product or system standards or national regulations.

7.3.2 If the test piece has an irregular or textured surface then, for calculations, the surface isconsidered to be smooth. If the shape of the test piece is such that accurate calculation of the surface isimpracticable then use an estimated surface area of the test piece. In this case the length and width shall berecorded together with a sufficiently detailed description of the product(s) to enable further test pieces to beprepared that will be within ± 10% of the surface area of the original test piece.

NOTE The supplier of the test samples should be instructed to ensure that they represent the product as it is used incontact with water intended for human consumption.

Page 13: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 13/33

EN 12873-1:2003 (E)

11

8 Pretreatment of test pieces

8.1 General

8.1.1 Test pieces are pretreated prior to migration testing by procedures involving flushing, stagnation andprewashing.

8.1.2 If required a disinfection treatment (stagnation) at (23 ± 2) °C is carried out.

NOTE The disinfection treatment is optional. The requirement to carry out this stage will be specified in the relevant

product/system standard or by national regulations.

8.1.3 If it is not possible, because of laboratory time constraints, to carry out the pretreatment and testprocedure without a break, the break shall be during the pretreatment procedure. The migration periods shallbe consecutive and without a break.

8.2 Test pieces to be tested at (23 ± 2) C

8.2.1 Flushing

8.2.1.1 If possible, flush test pieces with flowing tap water (5.1.1) for (60 ± 5) min with a speed of 1 m/minto 3 m/min.

NOTE In order to avoid the use of large quantities of water the arrangement described in annex A can be used toflush large diameter products.

8.2.1.2 Test pieces which cannot be flushed shall be placed in an appropriate vessel, e.g. a bucket,having a flow of water from the bottom upwards such that the calculated speed with regard to the upper opensurface of the vessel is 1 m/min to 3 m/min for (60 ± 5) min.

8.2.2 Stagnation with test water

8.2.2.1 Test pieces shall be immersed in, or filled with, test water (5.1.2 and/or 5.1.3) for a period of

(24 ± 1) h at (23 ± 2) °C.

8.2.2.2 Remove the water.

8.2.2.3 Prewash the test pieces according to 8.4.

8.2.3 Stagnation with disinfection treatment water

8.2.3.1 Test pieces shall be immersed in, or filled with, disinfection treatment water (5.1.4) for a period of

(24 ± 1) h at (23 ± 2) °C.

8.2.3.2 Remove the water.

8.2.3.3 Prewash the test pieces according to 8.4.

8.3 Test pieces to be tested at elevated temperature (60 C to 85 C)

8.3.1 Flushing

Flush test pieces according to 8.2.1

Page 14: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 14/33

EN 12873-1:2003 (E)

12

8.3.2 Stagnation with disinfection treatment water at (23 ± 2) C

If stagnation with disinfection treatment water prior to stagnation with test water (8.3.2) is required thenstagnation shall be carried out according to 8.2.3.

8.3.3 Stagnation with test water at elevated temperature

8.3.3.1 Test pieces shall be immersed in, or filled with, test water (5.1.2 and/or 5.1.3) for a period of(24 ± 1) h at the elevated temperature.

8.3.3.2 Remove the water.

8.3.3.3 Prewash the test pieces according to 8.4.

8.4 Prewashing

8.4.1 Flush test pieces according to 8.2.1

8.4.2 Rinse the test pieces with test water (5.1.2 and/or 5.1.3) for 2 min.

NOTE In order to avoid the use of large quantities of water the arrangement described in annex A can be used toflush large diameter products.

9 Test procedure

9.1 Migration of substances

9.1.1 Carry out each the test for each test water type (5.1.2 and/or 5.1.3).

NOTE 1 The number of tests to be carried out, e.g. single tests or duplicates for each water type, will be specified innational regulations. As guidance the method assumes duplicate testing.

NOTE 2 The choice of the type of test water (chlorinated and/or chlorine-free) will be specified by Product /systemstandards or national regulations. The method assumes testing with chlorinated and unchlorinated test water.

The first migration shall be started immediately after the pretreatment.

Immerse or fill the test pieces (according to 7.2) in or with test water (5.1.2 and/or 5.1.3). Ensure that the testpieces or vessels/containers are completely immersed or filled and free of headspace in order to retain volatilesubstances.

NOTE 3 Thin layer chromatography tanks (volume 3.5 - 4 l) with lids made from glass can be used as containers tocarry out the tests.

9.1.2 In the case of products intended for use with cold water, each migration period shall be (72 ± 1) h at

(23 ± 2) °C.

9.1.3 In the case of products intended for use with warm (60 ± 2 °C) to hot water (85 ± 2 °C), eachmigration period shall be (24 ± 1) h.

9.1.4 At the end of each migration period remove the migration water. Replace with fresh test water asnecessary. As a minimum, migration waters from the first, second and third migration period shall be

analyzed. For each analysis the concentration aTn

 (see clause 10) shall be determined.

Page 15: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 15/33

EN 12873-1:2003 (E)

13

Referring standards and/or national regulatory authorities may specify the number of sequential migrationperiods to be carried out and how to interpret the data. Annex C provides examples of the sequence andnumber of migration periods that can be undertaken in practice (see introduction).

9.2 Procedural blank tests

9.2.1 For each migration period carry out a blank test procedure using the same test conditions (test water,test temperature, migration periods, stoppers etc.) as described in 9.1, but omitting the test piece.

9.2.2 Where only glass or stainless steel plates and/or stoppers are used (e.g. pipes that are filled with testwater) to seal test pieces, use a glass container for the procedural blank. Where other stoppers, connectors orsealants are used (e.g. PTFE), include these in the procedural blank with the same contact condition.

9.2.3 Determine at the end of each migration period the concentration bTn

  (see clause 10) of each

measured substance of interest.

9.2.4 If any of the blank results are greater than the relevant lowest concentration of interest for the

substance determined (e.g. a value lying between the limit of detection and the concentration not to beexceeded in water intended for human consumption as specified in the referring standard or nationalregulations) then steps shall be taken to eliminate the source of contamination, after which the entire testprocedure shall be repeated (see introduction).

9.3 Analysis

Carry out the required analysis on the migration waters using the respective analytical methods. Determine atthe end of each migration period the concentration of the substance being measured. General guidance onanalytical performance requirements such as detection limit and accuracy is contained in ENV ISO 13530.

NOTE 1 If migration waters are not analyzed immediately then it should be ensured that the storage time andconditions do not adversely affect the analytical result.

NOTE 2 For some analytical methods and/or specific test procedures, recovery rates for the substances beingdetermined are to be established using positive controls. Annex D gives further guidance.

10 Calculation of test results

10.1 Calculation of the concentration of the substances in the migration water

NOTE The migration of substances from materials into water depends on the type of material and the migrationconditions: temperature, contact time, the S  / V  ratio and whether the water is static or flowing. For static test conditionsand constant temperature, the increase in the concentration of the substance in the test water is asymptotic. However, for

practical purposes the increase with time is assumed to be linear:

Calculate for each migration water the concentration of the measured substance as follows;

cTn

 = aTn

 – bTn

(1)

where

cTn

is the concentration of the measured substance in mg/l

aTn

is the concentration of the substance in mg/l measured in the migration water

bTn

is the concentration of the substance in mg/l measured in the blank water

Page 16: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 16/33

EN 12873-1:2003 (E)

14

For the conditions:

T  is the test temperature ((23 ± 2) °C or (60 ± 2) °C to (85 ± 2) °C)

n is the sequence number of the migration period (1, 2, 3, …10)

10.2 Calculation of the migration rate of the measured substances

Calculate for each migration water the migration rate M Tn

 for a migrated substance from the concentration cTn

as follows:

 M Tn

 = cTn /(S  / V  ⋅ t ) [mg dm-2d-1] (2)

where

 M Tn

is the migration rate for the nth migration period (3.16)

t  is the duration of the migration period in days, either one day (24 ± 1) h for elevated temperatures

or three days (72 ± 1) h for (23 ± 2) °C (9.1.2 and 9.1.3).

S  / V  is the surface area-to-volume ratio in dm-1 (7.3.1).

10.3 Calculation of the mean migration rate

Calculate the arithmetic mean migration rate Tn

 M    for the duplicate values of  M Tn

  for each test water

(5.1.2 and 5.1.3).

11 Test report

11.1 General information

The test report shall include the following information:

    name and address of test laboratory and location where the test was carried out when different from theaddress of the testing laboratory;

    unique identification of report (such as serial number) and of each page, and total number of pages of thereport;

    name and address of client;

    description and identification of the test item;

    proposed use of the product;

    signature and title or an equivalent marking of person (s) accepting technical responsibility for the testreport and date of issue;

    statement to the effect that the test results relate only to the items tested;

    statement that the report shall not be reproduced except in full without the written approval of the testinglaboratory.

Page 17: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 17/33

EN 12873-1:2003 (E)

15

The information on the product shall at least include:

    trade name or designation of manufactured product ;

    complete identification and date of receipt of test item and date of performance of test;

    names of the primers and undercoats used, together with the wet film thickness of each lining applied;

    details of the test piece preparation;

    name of the manufacturer of the product;

    production place and date;

    organization submitting the sample;

    organisation responsible for preparing the test pieces;

    description of sampling procedure.

11.2 Information on the test procedure

The information on the test procedure shall include:

    reference to this standard and (if applicable) to the referring standard or national regulation;

    number of test pieces used together in a migration;

    volume of the test water (V) in litres;

    surface area of test piece exposed to the test water (S) in square decimetres calculated from the actualdimensions of the test pieces;

    S/V ratio used;

    disinfection procedure ( if applicable);

    source of reference water and test water and (if applicable) details of preparation;

    test waters and test temperature;

    any deviation from the test procedure specified in this standard;

    any factors which may have affected the results, such as any incidents or any operating details notspecified in this standard;

    dates of start and completion of the test.

11.3 Test results

The test results shall, at least, include the duplicate and mean results and calculations shall be presented foreach test temperature and type of test water in tabular form, e.g.:

Page 18: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 18/33

EN 12873-1:2003 (E)

16

Table 1

Sequence number of migration period

1 2 3 n a

 a  Tn

 b T

n

 cT

n

 M  T

n

T

n M 

a n specifies additional migration periods.

Page 19: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 19/33

EN 12873-1:2003 (E)

17

Annex A(informative)

Arrangement for flushing pipes with nominal size greater than DN 80

An alternative arrangement for flushing large diameter products is shown in Figure A.1.a) and Figure A.1.b).

This arrangement is designed to avoid the use of large quantities of water to produce the required flow rateover the test piece surface.

The device is a cylinder made of inert material (6.1) with a diameter less than that of the internal diameter ofthe test piece.

The diameter of the cylinder should be at least 10 mm less than that of the internal diameter of the test piece.

This will leave a gap of at least 5 mm between the wall of the cylinder and the test piece. If the gap is anysmaller than this, there will be too much resistance to the waterflow.

The tap water is delivered via a valve and flow meter through a pipe to a space at the bottom of the cylinder.The cylinder is supported on the base plate by three or four short legs. The space into which the pipe deliversthe water is to allow for equal flow of water over the whole inside of the test piece. The space has an air ventwhich is opened at the start of the prewashing period in order to let out the air which would otherwise betrapped in the distribution space. Most of the volume of the cylinder is empty space which can be filled withe.g. water or sand in order to stabilize the set up.

Towards the top of the cylinder there is an adjustable ring with three or four screws to adjust the height of thering for different lengths of test pieces. There are also three or four screws which can be tightened into theoutside of the test piece in order to ensure that the cylinder is centred within the test piece, thus ensuring

equal flows of water over the whole inside surface of the test piece. The position of the ring is adjusted toallow a free flow of water over the top edge of the test piece. A vertical gap of about 10 mm should besufficient.

Page 20: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 20/33

EN 12873-1:2003 (E)

18

Key

1 Air vent 5 Flow meter 9 Test piece2 Gap > 5 mm 6 Main cylinder 10 Seal3 Valve 7 Height adjusting screw 11 Base plate4 Wash water 8 Centering screw

Figure A.1.a) – Example of an arrangement for flushing large diameter pipes

Page 21: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 21/33

EN 12873-1:2003 (E)

19

Key

1 Air vent 5 Wash water

2 Main cylinder 6 Test piece

3 Centering screw 7 Water inlet

4 Adjustable ring

Figure A.1.b) – Example of an arrangement for flushing large diameter pipes

Page 22: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 22/33

EN 12873-1:2003 (E)

20

Annex B(informative)

Additional procedures for testing non-homogeneous products and pipes

with nominal size greater than DN 80

B.1 Arrangements for testing

The test arrangements shown in Figure B.1 and Figure B.2 should be used.

Precautions should be taken to ensure that there is no loss of test water during the migration periods.

B.2 Flushing of the test piece

The test piece should be flushed in accordance with either clause 8 or, to avoid the use of large quantities ofwater, the procedure given in annex A.

In case of dispute, the procedure given in clause 8 should be used.

B.3 Blank test

The blank test should be carried out in accordance with 9.2.1, ensuring that all materials that will come intocontact with the test water will be included in the blank test and that they are present at the same surface-

area-to-volume ratio as in the actual test arrangement.

B.4 Sealing

The end pieces should be secured against the pipe segments to provide a seal, e.g. by means of clamps orbolts. If a seal cannot be achieved then it should be ensured that any material used will not affect the outcomeof the test, e.g. tape or film in the form of a gasket, with minimal surface in contact with test water (6.1).

Page 23: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 23/33

EN 12873-1:2003 (E)

21

Key

1 Cover of glass or stainless steel

2 Hole in top plate for filling with test water and release of air (sealed with stoppers)

3 End piece of stainless steel

4 Length of test piece

5 Test piece

6 Clamps or bolts

7 Test piece completely filled with test water

Figure B.1 – Test arrangement 1

Page 24: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 24/33

EN 12873-1:2003 (E)

22

Key1 Top plate of glass or stainless steel

2 Pipe wall

3 Cylinder of glass or stainless steel

4 Test water (test piece completely filled)

5 Seal between pipe section and plate, if necessary

6 Bottom plate of glass or stainless steel

7 Hole in top plate for filling with test water and release of air (sealed with stoppers)

Figure B.2 – Test arrangement 2

Page 25: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 25/33

EN 12873-1:2003 (E)

23

B.5 Calculation of the surface area-to-volume ratio (S/V) value for test arrangement 1(see Figure B.1)

The S/V value should be calculated for test arrangement 1 in Figure B.1 when S and V are calculated as follows.

Keya Arc length of the pipe segment in millimetres

h Height of the pipe segment in millimetres

Figure B.3 - Cross section of pipe showing test piece

From the cross section of the pipe the arc length a and the surface area A of the hatched circle segment shouldbe calculated using the following equations:

a = ×

360(B.1)

where

d i is the internal diameter of the pipe from which the segment is taken, in millimetres

α  is the sector angle, in degrees i.e.

i

cosd 

hd ) =

(

2

2

−(B.2)

( )

   

  × 

 

 

 

 

 −−

× 

  

  

224360

22   α α 

tani

ih

d d 

  A = (B.3)

Page 26: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 26/33

EN 12873-1:2003 (E)

24

where

 A surface area of the hatched circle segment, in square millimetres

α  sector angle, in degrees

d i internal diameter of the pipe from which the segment is taken, in millimetres

S  = 10-4 × a ×  L (B.4)

where

S  inner surface area of the test piece (pipe segment), in square decimeters, exposed to the test water;

 L length of the pipe segment, in millimetres.

V  = 10-6 ×  A ×  L (B.5)

where

V  volume of the test water, in litres

Page 27: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 27/33

EN 12873-1:2003 (E)

25

Annex C(informative)

Examples of extended collection and analysis of migration waters

The number of migration waters to be collected and their analysis will be specified in either the referringstandard(s) or by national regulatory authorities. If more than the initial three migration periods are specifiedsome allowance for the timing of the intermediate migrations (between the third and the final migration) can beintroduced to assist the test laboratory. In every case, however, the migration water immediately before thefinal migration for analysis should be of the correct duration, either 72 h or 24 h.

In Table C.1 a practical sequence for obtaining migration waters is shown for 72 h periods (cold water). TableC.2 shows a sequence for 24 h periods (elevated temperatures).

Table C.1 –Sequence for obtaining migration water for 72 h migration periodsNumber migration periods/days Days Comment

1/3 Tuesday to Friday 72 h – analyzed

2/6 Friday to Monday 72 h – analyzed

3/9 Monday to Thursday 72 h – analyzed

4/13 Thursday to Monday 96 h

5/15 Monday to Wednesday 48 h

6/17 Wednesday to Friday 48 h

7/21 Friday to Tuesday 96 h

8/24 Tuesday to Friday 72 h

9/27 Friday to Monday 72 h – analyzed a

10/30 Monday to Thursday 72 h – analyzed a

A If required

Table C.2 - Sequence for obtaining migrations waters for 24 h migration periods

Number migration periods/days Days Comment

1/1 Tuesday to Wednesday 24 h – analyzed

2/2 Wednesday to Thursday 24 h – analyzed

3/3 Thursday to Friday 24 h – analyzed

4/6 Friday to Monday 72 h

5/7 Monday to Tuesday 24 h

6/8 Tuesday to Wednesday 24 h

7/9 Wednesday to Thursday 24 h

8/10 Tuesday to Friday 24 h

9/13 Friday to Monday 72 h

10/14 Monday to Tuesday 24 h – analyzed a

11/15 Tuesday to Wednesday 24 h – analysed a

A If required

Page 28: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 28/33

EN 12873-1:2003 (E)

26

Annex D(informative)

Procedural tests using standard additions (positive controls)

Periodically establishing recovery levels of substances determined from analytical methods and specific testprocedures is good laboratory practice. Any requirements for particular products will be specified in thereferring standards or by the appropriate national regulatory authorities.

a) A positive control should be included, where appropriate, in order to ensure that there are no significantlosses of the measured substance, migrating from the test piece, during the migration periods or duringsampling for analysis (e.g. by evaporation, adsorption on test vessels, etc.).

b) A solution of known concentration of the substance to be determined should be prepared using the test

water and further treated as described in 9.2 (Procedural blank tests).

c) If the recovery of the substances does not meet the requirement specified in either the referring standardor by the national regulatory authorities, then the whole test procedure should be checked, and ifnecessary repeated, until the required performance is obtained.

Page 29: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 29/33

EN 12873-1:2003 (E)

27

Annex E(informative)

Flow diagrams for migration test procedure for cold water temperature

and elevated temperature

Figure E.1 – Testing at 23 °C without high level disinfection

Page 30: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 30/33

EN 12873-1:2003 (E)

28

Figure E.2 – Testing at 23 °C with high level disinfection

Page 31: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 31/33

EN 12873-1:2003 (E)

29

Figure E.3 – Testing at elevated temperature without high level disinfection

Page 32: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 32/33

EN 12873-1:2003 (E)

30

Figure E.4 – Testing at elevated temperature with high level disinfection

Page 33: 012873.01_EN-en_2004

7/21/2019 012873.01_EN-en_2004

http://slidepdf.com/reader/full/01287301en-en2004 33/33

EN 12873-1:2003 (E)

Bibliography

ENV ISO 13530, Water quality - Guide to analytical quality control for water analysis (ISO/TR 13530:1997).