Energy Perf of Boilers

208
ENERGY PERFORMANCE ASSESSMENT OF BOILERS

Transcript of Energy Perf of Boilers

Page 1: Energy Perf of Boilers

ENERGY PERFORMANCE ASSESSMENT OF BOILERS

Page 2: Energy Perf of Boilers

Performance Terms and Definitions

Heat outputHeat Input

Boiler Efficiency, η =

Heat in steam output (kCals)Heat in Fuel Input (kCals)

Quantity of Steam GenerationQuantity of fuel Consumption

Evaporation Ratio =

The efficiency of a boiler is expressed as the % of useful heat available from the total energy available by burning the fuel. This is expressed on the basis of gross calorific value (GCV) .

Page 3: Energy Perf of Boilers

StandardsBritish standards, BS845: 1987 This describes the methods and conditions under which a boiler should

be tested.Boiler should be operated under steady load conditions(generally full load) for a period of one hour before taking reading

ASME Standard: PTC-4-1 Power Test Code for Steam Generating Units

Part One: Direct method (also called as Input -output method)Part Two: Indirect method (also called as Heat loss method)

IS 8753: Indian Standard for Boiler Efficiency Testing

All standards do not include blow down as a loss in the efficiency determination process.

Page 4: Energy Perf of Boilers

Direct Method Testing

BoilerFuel Input 100%+ Air

Stea

m O

utpu

t

Efficiency = Heat addition to Steam x 100Gross Heat in Fuel

Flue Gas

Wat

er

100 valuecalorific Gross x rate firing Fuel

enthalpy) water feed enthalpy (steam x rate flow Steam xEfficiencyBoiler −=

Page 5: Energy Perf of Boilers

Indirect Method Testing

Boiler Flue gas sample

Steam Output

Efficiency = 100 – (1+2+3+4+5+6+7+8) (by Indirect Method)

Air

Fuel Input, 100%

1. Dry Flue gas loss2. H2 loss3. Moisture in fuel4. Moisture in air5. CO loss

7. Fly ash loss

6. Surface loss

8. Bottom ash loss

Wat

er

Blow down

Page 6: Energy Perf of Boilers

Instruments used for Boiler Performance Assessment.

Instrument Type Measurements

Flue gas analyzer

Portable or fixed % CO2 , O2 and CO

Temperature indicator

Thermocouple, liquid in glass

Fuel temperature, flue gas temperature, combustion air temperature, boiler surface temperature, steam temperature

Draft gauge Manometer, differential pressure

Amount of draft used or available

TDS meter Conductivity Boiler water TDS, feed water TDS, make-up water TDS.

Flow meter As applicable Steam flow, water flow, fuel flow, air flow

Page 7: Energy Perf of Boilers

1.Technical specification of boiler

1 Boiler ID code and Make

2 Year of Make

3 Boiler capacity rating

4 Type of Boiler

5 Type of fuel used

6 Maximum fuel flow rate

7 Efficiency by GCV

8 Steam generation pressure &superheat temperature

9 Heat transfer area in m2

10 Is there any waste heat recovery device installed

11 Type of draft

12 Chimney height in metre

Page 8: Energy Perf of Boilers

2 - Fuel analysis details

Fuel Fired

GCV of fuel

Specific gravity of fuel (Liquid)

Bulk density of fuel (Solid)

Proximate Analysis Date of Test:

1 Fixed carbon %

2 Volatile matter %

3 Ash %

4 Moisture %

Page 9: Energy Perf of Boilers

Ultimate Analysis Date of Test:Carbon %

Hydrogen %

Sulphur %

Nitrogen %

Ash %

Moisture %

Oxygen %

Water Analysis Date of Test:

Feed water TDS ppm

Blow down TDS ppm

PH of feed water

PH of blow down

Flue gas Analysis Date of Test:

CO2 %

O2 %

CO %

Flue gas temperature OC

Page 10: Energy Perf of Boilers

4. Format sheet for boiler efficiency testing

Date: ………………… Boiler Code No. …………………

S.No

Time

Ambient air Fuel Feed water Steam Flue gas analysis

Surface Temp of boiler, oC

Dry bulb

Temp, oC

Wet Bulb

Temp, oC

Flow Rate, kg/hr

Tempo

C

Flow rate,

m3/hr

Tempo

C

Flow rate,m3

/hr

Pressure

kg/cm2

g

Tempo

C

O

2%

CO

2%

CO

%

Temp0

C

1.

2.

3.

4.

5.

6.

7.

8.

Boiler Supervisor Energy Manager Energy Auditor

Page 11: Energy Perf of Boilers

Fuel firing rate = 5599.17 kg/hr

Steam generation rate = 21937.5 kg/hr

Steam pressure = 43 kg/cm2(g)

Steam temperature = 377 oC

Feed water temperature = 96 oC

%CO2 in Flue gas = 14

%CO in flue gas = 0.55

Average flue gas temperature = 190 oC

Ambient temperature = 31 oC

Humidity in ambient air = 0.0204 kg / kg dry air

Surface temperature of boiler = 70 oC

Wind velocity around the boiler = 3.5 m/s

Total surface area of boiler = 90 m2

GCV of Bottom ash = 800 kCal/kg

GCV of fly ash = 452.5 kCal/kg

Ratio of bottom ash to fly ash = 90:10

Fuel Analysis (in %)

Ash content in fuel = 8.63

Moisture in coal = 31.6

Carbon content = 41.65

Hydrogen content = 2.0413

Nitrogen content = 1.6

Oxygen content = 14.48

GCV of Coal = 3501 kCal/kg

The data collected are for a boiler using coal as the fuel.

Find out the boiler efficiency by indirect method.

Page 12: Energy Perf of Boilers

Boiler efficiency by indirect method

Step – 1 Find theoretical air requirement

Theoretical air required for complete combustion

=

[(11.43 x C) + {34.5 x (H2 – O2/8)} + (4.32 x S)] / 100 kg/kg of coal

= [(11.43 x 41.65) + {34.5 x (2.0413 – 14.48/8)} + (4.32 x 0)] / 100

= 4.84 kg / kg of coal

Page 13: Energy Perf of Boilers

Step – 2 Find theoretical CO2 %

% CO2 at theoretical condition ( CO2 )t

=

Moles of C Moles of N2 + Moles of C

Where,

Moles of N2

=

4.84 x 77/100 0.016 + = 0.1332 28 28

Where moles of C = 0.4165/12 = 0.0347

( CO2 )t

=

0.0347 0.1332 + 0.0347

=

20.67

Page 14: Energy Perf of Boilers

Step – 3 To find Excess air supplied

Actual CO2 measured in flue gas

=

14.0%

% Excess air supplied (EA) =

7900 x [ ( CO2)t – (CO2)a] (CO2)a x [100 – (CO2)t ]

=

7900 x [20.67 – 14 ] 14a x [100 – 20.67]

=

47.44 %

Page 15: Energy Perf of Boilers

Step – 4 to find actual mass of air supplied

Actual mass of air supplied =

{1 + EA/100} x theoretical air

= {1 + 47.44/100} x 4.84

= 7.13 kg/kg of coal

Step –5 to find actual mass of dry flue gas Mass of dry flue gas consists of Mass of CO2 +Mass of N2 content in the fuel+ Mass

of N2 in the combustion air supplied + Mass of oxygen in combustion air supplied

Mass of dry flue gas

=

0.4165 x 44 7.13 x 77 (7.13-4.84) x 23 + 0.016 + + 12 100 100

=

7.562 kg / kg of coal

Page 16: Energy Perf of Boilers

Step – 6 to find all losses 1. % Heat loss in dry flue gas (L1)

=

m x cp x (Tf – Ta ) x 100 GCV of fuel

=

7.562 x 0.23 x (190 – 31) x 100 3501

L1 = 7.89 %

Page 17: Energy Perf of Boilers

2. % Heat loss due to formation of water from H2 in fuel (L2)

=

9 x H2 x {584 + Cp (Tf – Ta )} x 100 GCV of fuel

=

9 x .02041 x {584 + 0.45(190-31)} x 100 3501

L2

= 3.44 %

3. % Heat loss due to moisture in fuel (L3)

=

M x {584 + Cp ( Tf – Ta )} X 100 GCV of fuel

=

0.316 x {584 + 0.45 ( 190 – 31) } x 100 3501

L3

=

5.91 %

Page 18: Energy Perf of Boilers

4. % Heat loss due to moisture in air (L4)

=

AAS x humidity x Cp x (Tf – Ta ) x 100 GCV of fuel

=

7.13 x 0.0204 x 0.45 x (190 – 31) x 100 3501

L4

= 0.29 %

5. % Heat loss due to partial conversion of C to CO (L5)

=

%CO x %C 5744 x x 100 % CO + (% CO2)a GCV of fuel

=

0.55 x 0.4165 5744 x x 100 0.55 + 14 3501

L5

= 2.58 %

Page 19: Energy Perf of Boilers

6. Heat loss due to radiation and convection (L6)

= 0.548 x [ (343/55.55)4 – (304/55.55)4] + 1.957 x

(343 - 304)1.25 x sq.rt of [(196.85 x 3.5 + 68.9) /

68.9]

= 633.3 w/m2 = 633.3 x 0.86 = 544.64 kCal / m2

Total radiation and convection loss per hour

= 544.64 x 90

= 49017.6 kCal % radiation and convection loss = 49017.6 x 100

3501 x 5591.17

L6 = 0.25 %

Page 20: Energy Perf of Boilers

7. % Heat loss due to unburnt in fly ash

% Ash in coal = 8.63 Ratio of bottom ash to fly ash = 90:10 GCV of fly ash = 452.5 kCal/kg Amount of fly ash in 1 kg of coal = 0.1 x 0.0863

= 0.00863 kg Heat loss in fly ash = 0.00863 x 452.5

= 3.905 kCal / kg of coal % heat loss in fly ash = 3.905 x 100 / 3501 L7 = 0.11 %

8. % Heat loss due to unburnt in fly ash GCV of bottom ash = 800 kCal/kg Amount of bottom ash in 1 kg of coal

= 0.9 x 0.0863

= 0.077 kg Heat loss in bottom ash = 0.077 x 800

= 62.136 kCal/kg of coal % Heat loss in bottom ash = 62.136 x 100 / 3501 L8 = 1.77 %

Page 21: Energy Perf of Boilers

Boiler efficiency by indirect method

= 100 – (L1+ L2+ L3+ L4+ L5+ L6+ L7+ L8)

= 100-(7.89 + 3.44+ 5.91+ 0.29+ 2.58+ 0.25+

0.11+1.77)

= 100-22.24 = 77.76 %

Summary of Heat Balance for Coal Fired Boiler

Input/Output Parameter

kCal / kg of coal

% loss

Heat Input = 3501 100 Losses in boiler 1. Dry flue gas, L1 = 276.23 7.89 2. Loss due to hydrogen in fuel, L2 = 120.43 3.44 3. Loss due to moisture in fuel, L3 = 206.91 5.91 4. Loss due to moisture in air, L4 = 10.15 0.29 5. Partial combustion of C to CO, L5 = 90.32 2.58 6. Surface heat losses, L6 = 8.75 0.25 7. Loss due to Unburnt in fly ash, L7 = 3.85 0.11 8. Loss due to Unburnt in bottom ash, L8

= 61.97 1.77

Boiler Efficiency = 100 – (L1 + L2+ L3+ L4+ L5+ L6+ L7+ L8) = 77.76 %

Page 22: Energy Perf of Boilers

Factors Affecting Boiler Performance

• Periodical cleaning of boilers • Periodical soot blowing • Proper water treatment programme and blow down

control• Draft control• Excess air control• Percentage loading of boiler• Steam generation pressure and temperature • Boiler insulation• Quality of fuel

Page 23: Energy Perf of Boilers

ENERGY PERFORMANCE ASSESSMENT OF

FURNACES

Page 24: Energy Perf of Boilers

Pusher-Type 3-Zone Reheating Furnace

Page 25: Energy Perf of Boilers

Performance Terms and Definitions

Furnace Efficiency, η = Heat in stock (material) (kCals)Heat in Fuel /electricity (kCals)

Specific Energy Consumption = Quantity of fuel or energy consumedQuantity of material processed.

Page 26: Energy Perf of Boilers

Direct Method TestingMeasurement Parameters

The following measurements are to be made for doing the energy balance in oil fired reheating furnaces (e.g. Heating Furnace)

i) Weight of stock / Number of billets heatedii) Temperature of furnace walls, roof etciii) Flue gas temperatureiv) Flue gas analysisv) Fuel Oil consumption

Page 27: Energy Perf of Boilers

Example: Energy Efficiency by Indirect MethodAn oil-fired reheating furnace has an operating temperature of around 1340oC. Average fuel consumption is 400 litres/hour. The flue gas exit temperature is 750 oC. Air is preheated from ambient temperature of 40oC to 190 oC through an air pre-heater. The furnace has 460 mm thick wall (x) on the billet extraction outlet side, which is 1 m high (D) and 1 m wide. The other data are as given below. Find out the efficiency of the furnace by both indirect and direct method.

flue gas temperature before air preheater = 750oCAmbient temperature = 40oCPreheated air temperature = 190oCSpecific gravity of oil = 0.92Average fuel oil consumption = 400 Litres / hr

= 400 x 0.92 =368 kg/hrCalorific value of oil = 10000 kCal/kgAverage O2 percentage in flue gas = 12%Weight of stock = 6000 kg/hrSpecific heat of Billet = 0.12 kCal/kg/0C

Page 28: Energy Perf of Boilers

Furnace Efficiency (Direct Method)

Heat input = 400 litres / hr= 368 kg/hr

Heat output = m x Cp x ∆T= 6000 kg x 0.12 x (1340 – 40)= 936000 kCal

Efficiency = 936000 x 100 / (368 x 10000)= 25.43 %= 25% (app)

Total Losses = 75% (app)

Page 29: Energy Perf of Boilers

1. Sensible Heat Loss in Flue Gas:Corresponding excess air

(Where O2 is the % of oxygen in flue gas = 12% )= 12 x 100 / (21 – 12)= 133% excess air

2

2

% 10021 %

O xO

=−

Theoretical air required to burn 1 kg of oil=14 kg (Typical value for all fuel oil)Total air supplied = Theoretical air x (1 + excess air/100)Total air supplied = 14 x 2.33 kg / kg of oil

= 32.62 kg / kg of oilSensible heat loss = m x Cp x ∆T

m = Weight of flue gas= Actual mass of air supplied / kg of fuel + mass of fuel (1kg)

= 32.62 + 1.0 = 33.62 kg / kg of oil.Cp = Specific heat of flue gas

= 0.24 kCal/kg/oC∆T = Temperature difference

Heat loss = 33.62 x 0.24 x (750– 40)= 5729 kCal / kg of oil

% Loss = 5729 = 57.29%10000

% Heat gain by combustion air = 32.62 x 0.24 x (190 – 40)----------------------------------- x 100

10000= 11.74 %

Net % sensible heat loss in flue gas = (57.29 – 11.74) % = 45.55%

Page 30: Energy Perf of Boilers

2. Loss Due to Evaporation of Moisture Present in Fuel

% Loss M {584 + 0.45 (Tfg-Tamb)} 100GCV of Fuel

x=

Where, M - % Moisture of in 1 kg of fuel oil (0.15 kg/kg of fuel oil) Tfg - Flue Gas Temperature Tamb - Ambient temperature GCV - Gross Calorific Value of Fuel 0.15 {584 +0.45 (750-40)} % Loss = ------------------------------ x 100 10000 = 1.36 % 3. Loss Due to Evaporation of Water Formed due to Hydrogen in Fuel % Loss = 9 x H2 {584 + 0.45 (Tfg-Tamb)} ---------------------------------------- x 100 GCV of Fuel Where, H2 – % of H2 in 1 kg of fuel oil (0.1123 kg/kg of fuel oil) = 9 x 0.1123 {584 + 0.45 (750-40)} ------------------------------------- x 100

10000 = 9.13 %

Page 31: Energy Perf of Boilers

Graph for Determining Black Body Radiation at a Particular Temperature

Page 32: Energy Perf of Boilers

Factor for Determining the Equivalent of Heat Release from Openings to the Quality of Heat Release from Perfect

Black Body

Page 33: Energy Perf of Boilers

The reheating furnace in example has 460mm thick wall (X) on the billet extraction outletside, which is 1m high (D) and 1m wide. With furnace temperature of 1340 0C, the quantity (Q) of radiation heat loss from the opening is calculated as follows: The shape of the opening is square and D/X = 1/0.46 = 2.17 The factor of radiation (Refer Figure 2.5) = 0.71 Black body radiation corresponding to 1340oC = 36.00 kCal/cm2/hr (Refer Figure 2.4 On black body radiation) Area of opening = 100 cm x 100 cm = 10000 cm2 Emissivity = 0.8 Total heat loss = Black body radiation x area of opening x factor of radiation x emissivity

=36 x 10000 x 0.71 x 0.8 = 204480 kCal/hr Equivalent Oil loss = 204480/10,000

= 20.45 kg/hr

% of heat loss = 20.45 /368 x 100 = 5.56 %

Page 34: Energy Perf of Boilers

Quantity of Heat Release at Various Temperatures

Page 35: Energy Perf of Boilers

5a). Heat loss through roof and sidewalls: Total average surface temperature = 122oC Heat loss at 122 oC = 1252 kCal / m2 / hr Total area of heating + soaking zone = 70.18 m2

Heat loss = 1252 kCal / m2 / hr x 70.18 m2

= 87865 kCal/hr Equivalent oil loss (a) = 8.78 kg / hr

6. Unaccounted Loss These losses comprises of heat storage loss, loss of furnace gases around charging doorand opening, heat loss by incomplete combustion, loss of heat by conduction throughhearth, loss due to formation of scales.

Page 36: Energy Perf of Boilers

Furnace Efficiency (Indirect Method) 1. Sensible heat loss in flue gas = 45.55%

2. Loss due to evaporation of moisture in fuel = 1.36 %

3. Loss due to evaporation of water formed from H2 in fuel = 9.13 % 4. Heat loss due to openings = 5.56 %

5. Heat loss through skin = 2.64%

6. Unaccounted losses = 10.76%

(Assessed by subtracting summation of losses 1 to 5 from the losses worked out by direct method i.e. [75 – (45.55+1.36+9.13+5.56+2.64) ] ) Total losses = 75% Furnace Efficiency = 100 – 75

= 25 % Specific Energy Consumption = 400 litre /hour (fuel consumption)

6Tonnes/hour (Wt of stock)

= 66.6 Litre of fuel /tonne of Material (stock)

Page 37: Energy Perf of Boilers

Theoretical Heat Example of melting one tonne of steel from an ambient temperature of 20oC . Specific heat of steel = 0.186 Wh/kg/0C, latent heat for melting of steel = 40 Wh/kg/0C. Melting point of steel = 1600 oC. Theoretical Total heat = Sensible heat + Latent heat

Sensible Heat = 1000 kg x 0.186 Wh /kg oC x (1600-20)oC = 294 kWh Latent heat = 40 Wh/ kg x 1000 kg = 40 kWh Total Heat = 294 + 40 = 334 kWh.

So the theoretical energy needed to melt one tonne of steel from 20o C = 334 kWh. Actual Energy used to melt to 1600o C is 700 kWh Efficiency = 334 kWh x 100 = 48% 700 kwh

Page 38: Energy Perf of Boilers

Factors Affecting Furnace Performance

• The important factors, which affect the efficiency, are listed below for critical analysis.

• Under loading due to poor hearth loading and improper production scheduling Improper Design

• Use of inefficient burner• Insufficient draft/chimney• Absence of Waste heat recovery• Absence of Instruments/Controls• Improper operation/Maintenance• High stack loss, waste heat recovery device • Improper insulation /Refractories

Page 39: Energy Perf of Boilers

Steam turbine analysis

Figure 3.1 Process Flow Diagram for Cogeneration Plant

S

1st Extraction

Extraction cum condensingTurbine

Boiler

h1

Power output kW

Boiler

2st Extraction

Condenser

h2

h3 h4

h11

h11

H1

H2 H3

Page 40: Energy Perf of Boilers

Actual heat extraction

Calculate the actual heat extraction in turbine at each stage,

Steam Enthalpy at turbine inlet : h1 kCal / kg Steam Enthalpy at 1st extraction : h2 kCal / kgSteam Enthalpy at 2nd extraction : h3 kCal / kg Steam Enthalpy at Condenser : h4* kCal / kg

* Due to wetness of steam in the condensing stage, the enthalpy of steam cannot be considered as equivalent to saturated steam. Typical dryness value is 0.88 – 0.92. This dryness value can be used as first approximation to estimate heat drop in the last stage. However it is suggested to calculate the last stage efficiency from the overall turbine efficiency and other stage efficiencies.

Page 41: Energy Perf of Boilers

Calculate enthalpy drop

Heat extraction from inlet : h1 – h2 kCal / kgto stage –1 extraction (h5)

Heat extraction from : h2-h3 kCal / kg1st –2nd extraction (h6)

Heat extraction from 2nd : h3-h4 kCal / kg Extraction – condenser (h7)

Page 42: Energy Perf of Boilers

Calculate theoretical enthalpy dropsFrom Mollier diagram (H-φ Diagram) estimate the theoretical heat extraction for the conditions mentioned in Step 1. Towards this:

a) Plot the turbine inlet condition point in the Mollier chart – corresponding to steam pressure and temperature

b) Since expansion in turbine is an adiabatic process, the entropy is constant. Hence draw a vertical line from inlet point (parallel to y-axis) upto the condensing conditions.

c) Read the enthalpy at points where the extraction and condensing pressure lines meet the vertical line drawn.

d) Compute the theoretical heat drop for different stages of expansion

Page 43: Energy Perf of Boilers

Theoretical enthalpy drop

Theoretical Enthalpy after 1st extraction : H1 Theoretical Enthalpy after 2nd extraction : H2Theoretical Enthalpy at condenser conditions : H3

Theoretical heat extraction from inlet to : h1 – H1stage 1 extraction, h8

Theoretical heat extraction from : H1-H21st – 2nd extraction, h9

Theoretical heat extraction from : H2-H32nd extraction – condensation, h10

Page 44: Energy Perf of Boilers

Compute turbine cylinder efficiency

Efficiency of 1st stage : h5 Heat extraction-actual h1- h2h8 Heat extraction theoretical h1 – H1

Efficiency of 2nd stage : h6 Heat extraction-actual h2- h3h9 Heat extraction theoretical H1 – H2

Efficiency of condensing stage : h7h10

Page 45: Energy Perf of Boilers

Calculate plant heat rate

M x (h1 – h11) Heat rate, kCal / kWh = P M – Mass flow rate of steam in kg/hr h1 - Enthalpy of inlet steam in kCal/kg h11 - Enthalpy of feed water in kCal/kg P - Average Power generated in kW *Alternatively the following guiding parameter can be utilised Plant heat consumption = fuel consumed for power generation, kg/hr Power generated, kW

Page 46: Energy Perf of Boilers

Example: Small Cogeneration Plant A distillery plant having an average production of 40 kilolitres of ethanol is having a cogeneration system with a backpressure turbine. The plant steam and electrical demand are 5.1 Tons/hr and 100 kW. The process flow diagram is shown in figure 3.2.Gross calorific value of Indian coal is 4000kCal/kg

Figure 3.2 Process Flow Diagram for Small Cogeneration Plant

S

Process Steam

BackPressureTurbineBoiler

Coal1550 kg/hr

Steam to turbineQ – 5100 kg/hrP – 15 kg/cm2gT – 250oC

Q – 5100 kg/hrP – 2 kg/cm2gT – 130oC

Power output 100kW

Page 47: Energy Perf of Boilers

Calculation stepsStep 1 :

Total heat of steam at turbine inlet conditions at 15kg / cm2 and 250oC, h1 =698kCal/kg

Step 2 :

Total heat of steam at turbine outlet conditions at 2 kg/cm2 and 130oC, h2 = 648 kCal/kg

Step 3 :

Heat energy input to turbine per kg of inlet steam (h1- h2) = (698-648) = 50 kCal/kg

Step 4 :

Total steam flow rate, Q1 = 5100 kg/hrPower generation = 100 kWEquivalent thermal energy = 100 x 860 = 86,000 kCal /hr

Step 5 :

Energy input to the turbine = 5100 x 50 = 2,55,000 kCal/hr.

Page 48: Energy Perf of Boilers

Step 6 :

Energy outputPower generation efficiency of the turbo alternator = --------------------- x 100

Energy Input

86,000= ------------- x 100 = 34%

2,55,000Step 7 :Efficiency of the turbo alternator = 34% Efficiency of Alternator = 92 %Efficiency of gear transmission = 98 %

AlternatorofEfficiencyontransmissigearofEfficiencyalternatorturboofefficiencygenerationPowerofTurbineEfficiency

*= 38.0

92.0*98.034.0

==

Page 49: Energy Perf of Boilers

Step 8 :

Quantity of steam bypassing the turbine = Nil

Step 9 :

Coal consumption of the boiler = 1550 kg/hr.

Step 10:

Overall plant heat rate, kCal/kWh

= Mass flow rate of steam x ((Enthalpy of steam, kCal/kg – Enthalpy of feed water,kCal/kg)Power output, kW

= 5100 x (698 – 30)100

= 34068 kCal/kWh*

*Note: The plant heat rate is in the order of 34000 kCal/kWh because of the use of backpressure turbine. This value will be around 3000 kcal/kWh while operating on fully condensing mode. However with backpressure turbine, the energy in the steam is not wasted, as it is utilised in the process.

Overall plant fuel rate including boiler = 1550/100 = 15.5 kg coal / kW

Page 50: Energy Perf of Boilers

Gas turbine and Waste heat recovery steam generator

o

o

T h eo re tica l tem p era tu re rise acro ss th e co m p resso r, C A ir C o m p resso r effic ien cy, % = A ctu al tem p era tu re rise , C

Power output, kW x 860 Overall Gas turbine efficiency (Compressor + Gas turbine), % = Fuel input for Gas turbine, kg/hr x GCV of fuel, kCal/kg

Heat Recovery Steam Generator (HRSG) PerformanceHeat Recovery Steam Generator efficiency, %

where, hs = Enthalpy of steamhw = Enthalpy of feed watertin = inlet temperature of flue gastout = outlet temperature of flue gas

s

in

w

out

steam generated, kg/hr x (h , kCal/kg - h ,kCal/kg)[Mass flow of flue gas, kg/hr x Cp x ( t - t )] + [ auxiliary fuel consumption, kg/hr x GCV of fuel, kCal/hr ]

=

Page 51: Energy Perf of Boilers

Energy Performance Assessment of Heat Exchangers

Page 52: Energy Perf of Boilers

Purpose of the Performance Test

To determine the overall heat transfer coefficient for assessing the performance of the heat exchanger. Any deviation from the design heat transfer coefficient will indicate occurrence of fouling.

Page 53: Energy Perf of Boilers

Overall heat transfer coefficient, U

Heat exchanger performance is normally evaluated by the overall heat transfer coefficient U that is defined by the equation

WhereQ = Heat transferred in kCal/hrA = Heat transfer surface area in m2

LMTD = Log Mean Temperature Difference in 0CU = Overall heat transfer Coefficient kCal/hr/m2/0C

Q=UxAx LMTD

Page 54: Energy Perf of Boilers

NomenclatureCold fluid in w, ti Hot fluid out W, ToShell

Cold fluid out w, to

Hot fluid in W, TiBaffles

Page 55: Energy Perf of Boilers

Heat Duty

Heat duty of the exchanger can be calculated either on the hot side fluid or cold side fluid as given below.

Heat Duty for Hot fluid, Qh = Wx Cph x (Ti-To) ………..Eqn-1,

Heat Duty for Cold fluid, Qc = Wx Cpc x ( to-ti) ………...Eqn-2

If the operating heat duty is less than design heat duty, it may be due to heat losses, fouling in tubes, reduced flow rate (hot or cold) etc. Hence, for simple performance monitoring of exchanger, efficiency may be considered as factor of performance irrespective of other parameter. However, in industrial practice, fouling factor method is more predominantly used.

Page 56: Energy Perf of Boilers

Methodology of Heat Exchanger Performance Assessment

Procedure for determination of Overall heat transfer Coefficient, U at field

This is a fairly rigorous method of monitoring the heat exchanger performance by calculating the overall heat transfer coefficientperiodically. Technical records are to be maintained for all theexchangers, so that problems associated with reduced efficiency and heat transfer can be identified easily. The record should basically contain historical heat transfer coefficient data versus time / date of observation. A plot of heat transfer coefficient versus time permits rational planning of an exchanger-cleaning program.

Page 57: Energy Perf of Boilers

Step – A

Monitoring and reading of steady state parameters of the heat exchanger under evaluation are tabulated as below:

Parameters Units Inlet Outlet Hot fluid flow,W kg/h Cold fluid flow,w kg/h Hot fluid Temp, T OC Cold fluid Temp,t OC Hot fluid Pressure,P bar g Cold fluid Pressure, p bar g

Page 58: Energy Perf of Boilers

Step – B

With the monitored test data, the physical properties of the stream can be tabulated as required for the evaluation of the thermal data

Parameters Units Inlet Outlet Hot fluid density, ρh kg/m3 Cold fluid density, ρc kg/m3 Hot fluid Viscosity, µh MpaS* Cold fluid Viscosity, µc MPaS Hot fluid Thermal Conductivity, kh

kW/(m. K)

Cold fluid Thermal Conductivity, kc

kW/(m. K)

Hot fluid specific heat Capacity, Cph

kJ/(kg. K)

Cold fluid specific heat Capacity, Cpc

kJ/(kg. K)

* MpaS – Mega Pascal Second

Density and viscosity can be determined by analysis of the samples taken from the flow stream at the recorded temperature in the plant laboratory. Thermal conductivity and specific heat capacity if not determined from the samples can be collected from handbooks.

Page 59: Energy Perf of Boilers

Step – C

Calculate the thermal parameters of heat exchanger and compare with the design data

Parameters Units Test Data Design Data Heat Duty, Q kW Hot fluid side pressure drop, ∆Ph bar * Cold fluid side pressure drop, ∆Pc bar * Temperature Range hot fluid , ∆T OC Temperature Range cold fluid , ∆t OC Capacity ratio, R ----- Effectiveness, S ----- Corrected LMTD, MTD OC Heat Transfer Coefficient, U kW/(m2. K) * - The pressure drop for the design flow can be rated with the relation , Pressure drop is proportional to (Flow)1.75

Page 60: Energy Perf of Boilers

ExamplesLiquid – Liquid Exchanger

A shell and tube exchanger of following configuration is considered being used for oil cooler with oil at the shell side and cooling water at the tube side.

Tube Side 460 Nos x 25.4mmOD x 2.11mm thick x 7211mm longPitch – 31.75mm 30o triangular2 Pass

Shell Side787 mm ID Baffle space – 787 mm1 Pass

The monitored parameters are as below:

Parameters Units Inlet Outlet Hot fluid flow, W kg/h 719800 719800 Cold fluid flow, w kg/h 881150 881150 Hot fluid Temp, T OC 145 102 Cold fluid Temp, t OC 25.5 49 Hot fluid Pressure, P bar g 4.1 2.8 Cold fluid Pressure, p bar g 6.2 5.1

Page 61: Energy Perf of Boilers

Calculation of Thermal dataHeat Transfer Area = 264.55 m2

1.Heat Duty: Q = qs = ql Hot fluid, Q = 719800 x 2.847 x (145 –102) = 24477.4 kW Cold Fluid, Q = 881150 x 4.187 x (49 – 25.5) = 24083.4 kW

2. Hot Fluid Pressure Drop Pressure Drop = Pi – Po = 4.1 – 2.8 = 1.3 bar g.

3. Cold Fluid Pressure Drop Pressure Drop = pi – po = 6.2 – 5.1 = 1.1 bar g.

4. Temperature range hot fluid Temperature Range ∆T = Ti – To = 145 – 102 = 43 o C.

5. Temperature Range Cold Fluid Temperature Range ∆t = ti – to = 49 – 25.5 = 23.5 0C.

Page 62: Energy Perf of Boilers

6. Capacity Ratio

Capacity ratio, R = 23.5/43 = 0.547.

7. Effectiveness

Effectiveness, S = (to – ti) / (Ti – ti) =(49 – 25.5)/(145-25.5) =23.5/119.5 = 0.20.

8. LMTD

a). LMTD, Counter Flow = (96 – 76.5)/ ln (96/76.5) = 85.9 0C.

b). Correction Factor to account for Cross flow

(R + 1)1/2 x ln ((1- SR)/ (1- S )

F = (R + 1)1/2 x ln ((1- SR)/ (1- S )

( 1 – R) x ln 2- S ( R + 1 – (R2 +1)1/2)

2- S ( R + 1 + (R2 +1)1/2)

F = 0.977.

9. Corrected LMTD

= F x LMTD = 0.977 x 85.9 = 83.9 oC.

10. Overall Heat Transfer Co-efficient

U = Q/ A ∆T = 24477.4/ (264.55 x 83.9) = 1.104 kW/m2. K

Page 63: Energy Perf of Boilers

Comparison of Calculated data with Design Data

Parameters Units Test Data Design Data Duty, Q kW 24477.4 25623

Hot fluid side pressure drop, ∆Ph Bar 1.3 1.34

Cold fluid side pressure drop, ∆Pc Bar 1.1

0.95

Temperature Range hot fluid, ∆T OC 43 45

Temperature Range cold fluid, ∆t OC 23.5 25 Capacity ratio, R ----- 0.547 0.556 Effectiveness, S ----- 0.20 0.375 Corrected LMTD, MTD OC 83.8 82.2 Heat Transfer Coefficient, U kW/(m2. K) 1.104 1.178

Page 64: Energy Perf of Boilers

Inferences• Heat Duty: Actual duty differences will be practically negligible as these duty

differences could be because of the specific heat capacity deviation with the temperature. Also, there could be some heat loss due to radiation from the hot shell side.

• Pressure drop: Also, the pressure drop in the shell side of the hot fluid is reported normal (only slightly less than the design figure). This is attributed with the increased average bulk temperature of the hot side due to decreased performance of the exchanger.

• Temperature range: As seen from the data the deviation in the temperature ranges could be due to the increased fouling in the tubes (cold stream), since a higher pressure drop is noticed.

• Heat Transfer coefficient: The estimated value has decreased to increased fouling that has resulted in minimized active area of heat transfer.

• Physical properties: If available from the data or Lab analysis can be used for verification with the design data sheet as a cross check towards design considerations.

• Troubleshooting: Fouled exchanger needs cleaning.

Page 65: Energy Perf of Boilers

ENERGY PERFORMANCE ASSESSMENT OF MOTORS / VARIABLE SPEED DRIVES

Page 66: Energy Perf of Boilers

Motor efficiency vs loading

Page 67: Energy Perf of Boilers

Performance Terms and Definitions

Efficiency :The efficiency of the motor is given by

in

loss

inout

PP

1P

P −==η

Where Pout – Output power of the motorPin – Input power of the motorPLoss – Losses occurring in motor

Motor Loading :

Motor Loading % = Actual operating load of the motorRated capacity of the motor

Page 68: Energy Perf of Boilers

Field Tests for Determining Efficiency

Page 69: Energy Perf of Boilers

No Load Test

The motor is run at rated voltage and frequency without any shaft load. Input power, current, frequency and voltage are noted. The no load P.F. is quite low and hence low PF watt meters are required. From the input power, stator I2R losses under no load are subtracted to give the sum of Friction and Windage (F&W) and core losses. To separate core and F & W losses, test is repeated at variable voltages. It is worthwhile plotting no-load input kW versus Voltage; the intercept is F & W kW loss component.

F&W and core losses = No load power (watts) – (No load current)2 × Stator resistance

Page 70: Energy Perf of Boilers

Stator and Rotor I2R Losses :

The stator winding resistance is directly measured by a bridge or volt amp method. The resistance must be corrected to the operating temperature. For modern motors, the operating temperature is likely to be in the range of 1000C to 1200C and necessary correction should be made. Correction to 750C may be inaccurate. The correction factor is given as follows :

where, t1 = ambient temperature, oC & t2 =- operating temperature, oC.The rotor resistance can be determined from locked rotor test at reduced frequency, but rotor I2R losses are measured from measurement of rotor slip.Rotor I2R losses = Slip × (Stator Input – Stator I2R Losses – Core Loss)Accurate measurement of slip is possible by stroboscope or non-contact type tachometer. Slip also must be corrected to operating temperature.

1

2

1

2

t 235 t 235

RR

++

=

Page 71: Energy Perf of Boilers

Stray Load Losses

These losses are difficult to measure with any accuracy. IEEE Standard 112 gives a complicated method, which is rarely used on shop floor. IS and IEC standards take a fixed value as 0.5 % of output. It must be remarked that actual value of stray losses is likely to be more. IEEE –112 specifies values from 0.9 % to 1.8 %.

Motor Rating Stray Losses

1 – 125 HP 1.8 %

125 – 500 HP 1.5 %

501 – 2499 HP 1.2 %

2500 and above 0.9 %

Page 72: Energy Perf of Boilers

Points for Users

It must be clear that accurate determination of efficiency is very difficult. The same motor tested by different methods and by same methods by different manufacturers can give a difference of 2 %. Estimation of efficiency in the field can be summarized as follows:

1. Measure stator resistance and correct to operating temperature. From rated current value, I2R losses are calculated.

2. From rated speed and output, rotor I2R losses are calculated3. From no load test, core and F & W losses are determined for stray loss

Page 73: Energy Perf of Boilers

ExampleMotor Specifications

Rated power = 34 kW/45 HP

Voltage = 415 Volt

Current = 57 Amps

Speed = 1475 rpm

Insulation class = F

Frame = LD 200 L

Connection = Delta

Page 74: Energy Perf of Boilers

No load test Data

Voltage, V = 415 Volts

Current, I = 16.1 Amps

Frequency, F = 50 Hz

Stator phase resistance at 300C

= 0.264 Ohms

No load power, Pnl = 1063.74 Watts

Page 75: Energy Perf of Boilers

Try to calculate the following

Calculate iron plus friction and windage losses

Calculate stator resistance at 1200C

R2 = R1 × 1

2

t235 t235

++

Calculate stator copper losses at operating temperature of resistance at 1200C

Calculate full load slip(s) and rotor input assuming rotor losses are slip timesrotor input.

Determine the motor input assuming that stray losses are 0.5 % of the motorrated power

Calculate motor full load efficiency and full load power factor

Page 76: Energy Perf of Boilers

Solution

Let Iron plus friction and windage loss, Pi + fw No load power, Pnl = 1063.74 Watts

Stator Copper loss, P st-300C (Pst.cu) = 3 × (16.1 / √3)2 × 0.264 = 68.43 Watts Pi + fw = Pnl – Pst.cu = 1063.74 – 68.43 = 995.3 W

Page 77: Energy Perf of Boilers

Stator Resistance at 1200C,

R1200

C = 0.264 × 235 30235 201

++

= 0.354 ohms per phase

Stator copper losses at full load, Pst.cu 1200C

= 3 × (57 / √3)2 × 0.354

= 1150.1 Watts

Page 78: Energy Perf of Boilers

Full load slip

S = (1500 – 1475) / 1500

= 0.0167

Rotor input, Pr = Poutput/ (1-S)

= 34000 / (1-0.0167) = 34577.4 Watts

Motor full load input power, P input

= Pr + Pst.cu 1200C + (Pi + fw) + Pstray

= 34577.4 + 1150.1 + 995.3 + (0.005* × 34000)

= 36892.8 Watts

*where, stray losses = 0.5% of rated output (assumed)

Page 79: Energy Perf of Boilers

Motor efficiency at full load

Efficiency = 100 P

P

input

output ×

= 100 36892.8

34000×

= 92.2 %

Full Load PF = I V 3

P

fl

input

××

= 57 415 3

36892.8××

= 0.90

Page 80: Energy Perf of Boilers

Comments

• The measurement of stray load losses is very difficult and not practical even on test beds.

• The actual value of stray loss of motors up to 200 HP is likely to be 1 % to 3 % compared to 0.5 % assumed by standards.

• The value of full load slip taken from the nameplate data is notaccurate. Actual measurement under full load conditions will give better results.

• The friction and windage losses really are part of the shaft output; however, in the above calculation, it is not added to the rated shaft output, before calculating the rotor input power. The error however is minor.

• When a motor is rewound, there is a fair chance that the resistance per phase would increase due to winding material quality and the losses would be higher. It would be interesting to assess the effect of a nominal 10 % increase in resistance per phase.

Page 81: Energy Perf of Boilers

Determining Motor Loading

By Input Power Measurements

First measure input power Pi with a hand held or in-line power meter Pi = Three-phase power in kW

Note the rated kW and efficiency from the motor name plate

The figures of kW mentioned in the name plate is for output conditions.

So corresponding input power at full-rated load

ηfl = Efficiency at full-rated load Pir = Input power at full-rated power in kW

The percentage loading can now be calculated as follows

Page 82: Energy Perf of Boilers

Example The nameplate details of a motor are given as power = 15 kW, efficiency η = 0.9. Using a power meter the actual three phase power drawn is found to be 8 kW. Find out the loading ofthe motor. Input power at full-rated power in kW, Pir = 15 /0.9 = 16.7 kW Percentage loading = 8/16.7 = 48 %

Page 83: Energy Perf of Boilers

By Line Current Measurements

The line current load estimation method is used when input power cannot be measured andonly amperage measurements are possible. The amperage draw of a motor variesapproximately linearly with respect to load, down to about 75% of full load. Below the 75%load point, power factor degrades and the amperage curve becomes increasingly non-linear. In the low load region, current measurements are not a useful indicator of load. However, this method may be used only as a preliminary method just for the purpose ofidentification of oversized motors.

100*%currentratedInputcurrentloadInputLoad = (Valid up to 75% loading)

Page 84: Energy Perf of Boilers

Slip MethodIn the absence of a power meter, the slip method can be used which requires a tachometer. This method also does not give the exact loading on the motors.

*100%s r

SlipLoadS S

=−

Where: Load = Output power as a % of rated power Slip = Synchronous speed - Measured speed in rpm Ss = Synchronous speed in rpm at the operating frequency Sr = Nameplate full-load speed

Example: Slip Load Calculation Given: Synchronous speed in rpm = 1500 at 50 HZ operating frequency.

( Synchronous speed = 120f/P) f: frequency, P: Number of poles Nameplate full load speed = 1450 Measured speed in rpm = 1480 Nameplate rated power = 7.5 kW Determine actual output power.

%40%100*1450150014801500

=−−

=Load

From the above equation, actual output power would be 40% x 7.5 kW = 3 kW

The speed/slip method of determining motor part-load is often favored due to its simplicityand safety advantages. Most motors are constructed such that the shaft is accessible to atachometer or a strobe light.

Page 85: Energy Perf of Boilers

The accuracy of the slip method, however, is limited

The largest uncertainty relates to the accuracy with which manufacturers report the nameplatefull-load speed. Manufacturers generally round their reported full-load speed values to some multiple of 5 rpm. While 5 rpm is but a small percent of the full-load speed and may be considered as insignificant, the slip method relies on the difference between full-load nameplate and synchronous speeds. Given a 40 rpm “correct” slip, a seemingly minor 5 rpmdisparity causes a 12% change in calculated load. Slip also varies inversely with respect to the motor terminal voltage squared. A voltagecorrection factor can, also, be inserted into the slip load equation. The voltage compensatedload can be calculated as shown Where: Load = Output power as a % of rated power Slip = Synchronous speed - Measured speed in rpm Ss = Synchronous speed in rpm Sr = Nameplate full-load speed V = RMS voltage, mean line to line of 3 phases Vr = Nameplate rated voltage

Page 86: Energy Perf of Boilers

Performance Evaluation of Rewound Motors

Ideally, a comparison should be made of the efficiency before and after a rewinding. Arelatively simple procedure for evaluating rewind quality is to keep a log of no-load input current for each motor in the population. This figure increases with poor quality rewinds. Areview of the rewind shop’s procedure should also provide some indication of the quality ofwork. When rewinding a motor, if smaller diameter wire is used, the resistance and the I2R losses will increase.

Page 87: Energy Perf of Boilers

Application of Variable Speed Drives (VSD)

Concept of Variable Frequency Drive The speed of an induction motor is proportional to the frequency of the AC voltage applied toit, as well as the number of poles in the motor stator. This is expressed by the equation:

RPM = (f x 120) / p

Where f is the frequency in Hz, and p is the number of poles in any multiple of 2. Therefore, if the frequency applied to the motor is changed, the motor speed changes in directproportion to the frequency change. The control of frequency applied to the motor is the jobgiven to the VSD. The VSD's basic principle of operation is to convert the electrical system frequency and voltage to the frequency and voltage required to drive a motor at a speed other than its rated speed. The two most basic functions of a VSD are to provide power conversion from one frequency to another, and to enable control of the output frequency

Page 88: Energy Perf of Boilers

VSD Power Conversion

There are two basic components, a rectifier and an inverter, to accomplish power conversion. The rectifier receives the 50-Hz AC voltage and converts it to direct current (DC) voltage. ADC bus inside the VSD functions as a "parking lot" for the DC voltage. The DC busenergizes the inverter, which converts it back to AC voltage again. The inverter can becontrolled to produce an output frequency of the proper value for the desired motor shaftspeed.

Page 89: Energy Perf of Boilers

Factors for Successful Implementation of Variable Speed Drives

Load Type for Variable Frequency Drives The main consideration is whether the variable frequency drive application require a variable torque or constant torque drive. If the equipment being driven is centrifugal, such as a fanor pump, then a variable torque drive will be more appropriate. Energy savings are usually the primary motivation for installing variable torque drives for centrifugal applications. Forexample, a fan needs less torque when running at 50% speed than it does when running at fullspeed. Variable torque operation allows the motor to apply only the torque needed, whichresults in reduced energy consumption. Conveyors, positive displacement pumps, punch presses, extruders, and other similar typeapplications require constant level of torque at all speeds. In which case, constant torque variable frequency drives would be more appropriate for the job. A constant torque driveshould have an overload current capacity of 150% or more for one minute. Variable torquevariable frequency drives need only an overload current capacity of 120% for one minute since centrifugal applications rarely exceed the rated current. If tight process control is needed, then you may need to utilize a sensor less vector, or flux vector variable frequency drive, which allow a high level of accuracy in controlling speed, torque, and positioning.

Page 90: Energy Perf of Boilers

Motor Information

• Full Load Amperage Rating. Using a motor's horsepower is an inaccurate way to size variable frequency drives.

• Speed Range. Generally, a motor should not be run at any speed less than 20% of its specified maximum speed allowed. If it is run at a speed less than this without auxiliary motor cooling, the motor will overheat. Auxiliary motor cooling should be used if the motor must be operated at very slow speeds.

• Multiple Motors. To size a variable frequency drive that will control more than one motor, add together the full-load amp ratings of each of the motors. All motors controlled by a single drive must have an equal voltage rating.

Page 91: Energy Perf of Boilers

Efficiency and Power Factor

• The variable frequency drive should have an efficiency rating of 95% or better at full load.

• Variable frequency drives should also offer a true system power factor of 0.95 or better across the operational speed range, to save on demand charges, and to protect the equipment (especially motors).

Page 92: Energy Perf of Boilers

Protection and Power Quality

• Motor overload Protection for instantaneous trip and motor over current.

• Additional Protection: Over and under voltage, over temperature, ground fault, control or microprocessor fault. These protective circuits should provide an orderly shutdown of the VFD, provide indication of the fault condition, and require a manual reset (except under voltage) before restart. Under voltage from a power loss shall be set to automatically restart after return to normal. The history of the previous three faults shall remain in memory for future review.

• If a built-up system is required, there should also be externally-operated short circuit protection, door-interlocked fused disconnect and circuit breaker or motor circuit protector (MCP)

Page 93: Energy Perf of Boilers

To determine if the equipment under consideration is the right choice for a variable

speed drive

The load patterns should be thoroughly studied before exercising the option of VSD. In effect the load should be of a varying nature to demand a VSD

Figure 5.3 Example of an excellent variable speed drive candidate

Figure 5.4 Example of a poor variable speed drive candidate

Page 94: Energy Perf of Boilers

Information needed to Evaluate Energy Savings for Variable Speed Application

Method of flow control to which adjustable speed is compared: o output throttling (pump) or dampers (fan) o recirculation (pump) or unrestrained flow (fan) o adjustable-speed coupling (eddy current coupling) o inlet guide vanes or inlet dampers (fan only) o two-speed motor.

Pump or fan data: o head v's flow curve for every different type of liquid (pump) or gas

(fan) that is handled o Pump efficiency curves.

Process information: o specific gravity (for pumps) or specific density of products (for fans) o system resistance head/flow curve o equipment duty cycle, i.e. flow levels and time duration.

Efficiency information on all relevant electrical system apparatus: o motors, constant and variable speed o variable speed drives o gears o transformers.

If we do not have precise information for all of the above, we can make reasonable assumptions for points 2 and 4.

Page 95: Energy Perf of Boilers

ENERGY PERFORMANCE ASSESSMENT OF FANS AND

BLOWERS

Page 96: Energy Perf of Boilers

Purpose of the Performance Test

The purposes of such a test are to determine, under actual operating conditions, the volumeflow rate, the power input and the total pressure rise across the fan. These test results will provide actual value for the flow resistance of the air duct system, which can be compared with the value specified by supplier.

Page 97: Energy Perf of Boilers

Performance Terms and Definitions

Static Pressure: The absolute pressure at a point minus the reference atmospheric pressure. Dynamic Pressure: The rise in static pressure which occurs when air moving with specified velocity at a point isbought to rest without loss of mechanical energy. It is also known as velocity pressure. Total Pressure: The sum of static pressures and dynamic pressures at a point. Fan Shaft Power: The mechanical power supplied to the fan shaft Motor Input Power: The electrical power supplied to the terminals of an electric motor drive.

Fan Efficiency: The air power static divided by impeller power

Static Fan Efficiency % = Volume in m3 / Sec x total pressure in mmwc102 x Power input to the shaft in (kW)

Page 98: Energy Perf of Boilers

Pressures in a duct

Page 99: Energy Perf of Boilers

Pitot tube

Page 100: Energy Perf of Boilers

Traverse readings

Page 101: Energy Perf of Boilers

Example

The following is a typical report on measurements taken and calculations made for adouble inlet fan in a palletizing plant.

(a) Design Parameters:

Volume = 292 m3/sec. Static Pressure = 609.6 mmwc

(b) Measurements:

Temperature = 32oC Speed = 740 RPM

Page 102: Energy Perf of Boilers

Inlet Damper Position

%

Suction Pressure (-) mmwc

Outlet Pressure

(+) mmwc

Measured Velocity

Pressure ( p), mmwc

Volume M3/Sec.

Amps(I)

Power Consumption

(kW)

ONE SIDE 25, 22, 20 Average=22.33

455, 462, 480,478 Avg.=468.75

Average = 70

80%

ANOTHER SIDE 15, 18, 23, 21 Average=19.25

459, 464, 473 479, 480, 470 Avg.=470.83

Average = 70

166.6

220

2127 KW

Instruments used a) Suction pressure, outlet pressure = ‘U’ tube manometer b) For differential pressure = Inclined tube manometer c) For temperature = Mercury in glass thermometer d) Fan speed = Tachometer e) Line current = Tong tester

Page 103: Energy Perf of Boilers

c) (P1) = Power input to the motor (kW) = √ 3 x V x I x Cos ∅ 1000

= √ 3 x 6600 x 220 x 0.9 1000 = 2263 kW d) P = Power input to the fan shaft

= Power input to the motor (kW) x Efficiency of motor (%) at the operating load x transmission efficiency

Motor efficiency = 0.94

P = 2263 x 0.94 x 1 (as motor was direct coupled) = 2127 kW

Page 104: Energy Perf of Boilers

e) Fan Efficiency % = Volume in m3 / Sec x total pressure in mmwc (a) x Power input to the shaft in (kW)

Where 102 is a conversion constant

For double inlet fan,

The total Volume of air,m3 / Sec = 166.6 x 2 = 333.2

Total static pressure, mmwc = 468.75- (-22.33) = 491 ( p Static ,across the fan)

Fan Efficiency = 333.2 x 491 x 100

102 x 2127

Static Fan Efficiency = 75%

Page 105: Energy Perf of Boilers

Performance calculationsa) Gas Density = 273 x 1.293 (Corrected to NTP) 273 + ToC (at site condition) = 273 x 1.293 273 + 32oC (at site condition) = 1.15 kg/m3

b) Volume = Cp x A √ 2 x 9.81 x p x γ

1.15 Cp = Pitot tube constant, 0.85 A = Area of rectangular duct in m2, 1.029 x 5.502

p = Average velocity pressure measured by pitot tube by taking measurement at number of points over the entire cross section of the duct.(see Table)

γ = Density at test condition, 1.15 kg/m3 Flow (v) = 0.85 x 1.029 x 5.502 √ 2 x 9.81 x 70 x 1.15

1.15 v = 166.6 m3 / Sec

Page 106: Energy Perf of Boilers

ENERGY PERFORMANCE ASSESSMENT OF WATER

PUMPS

Page 107: Energy Perf of Boilers

Purpose of the Performance Test

• Determination of the pump efficiency during the operating condition

• Determination of system resistance and the operating duty point of the pump and compare the same with design.

Page 108: Energy Perf of Boilers

Performance Terms and Definitions

Pump Capacity, Q = Volume of liquid delivered by pump per unit time,m3/hr or m3/sec Q is proportional to N, where N- rotational speed of the pump

Total developed head, H= The sum of suction and discharge pressures

The pump head represents the net work done on unit weights of a liquid in passing from

inlet of the pump to the discharge of the pump.

There are three heads in common use in pumps namely 1.0. Static head

2.0. Velocity head 3.0. Friction head.

The frictional head in a system of pipes, valves and fittings varies as a function (roughly

as the square) of the capacity flow through the system.

System resistance: The sum of frictional head in resistance & total static head. .

Page 109: Energy Perf of Boilers

Pump Efficiency

Pump efficiency = Hydraulic power, Ph x 100 Power input to the pump shaft

Where, Hydraulic power Ph(kW)

= Q (m3/s) x Total head,(hd - hs) (m) x r (kg/m3) x g (m/s2) / 1000 Q = Volume flow rate, r = density of the fluid, g = acceleration due to gravity

Page 110: Energy Perf of Boilers

Field Testing for Determination of Pump Efficiency

To determine the pump efficiency, three key parameters are required: Flow, Head and Power.Of these, flow measurement is the most crucial parameter as normally online flow meters arehardly available, in a majority of pumping system. The following methods outlined below can be adopted to measure the flow depending on the availability and site conditions.

Page 111: Energy Perf of Boilers

Flow Measurement, Q

• Tracer method BS5857• Ultrasonic flow measurement• Tank filling method• Installation of an on-line flowmeter

Page 112: Energy Perf of Boilers

Tracer Method

The Tracer method is particularly suitable for cooling water flow measurement because of their sensitivity and accuracy.

This method is based on injecting a tracer into the cooling water for a few minutes at anaccurately measured constant rate. A series of samples is extracted from the system at a pointwhere the tracer has become completely mixed with the cooling water. The mass flow rate iscalculated from: qcw = q1 x C1/C2

where qcw = cooling water mass flow rate, kg/s q1 = mass flow rate of injected tracer, kg/s

C1 = concentration of injected tracer, kg/kg C2 = concentration of tracer at downstream position during the ‘plateau’ period of constant concentration, kg/kg The tracer normally used is sodium chloride.

Page 113: Energy Perf of Boilers

Ultrasonic Flow meterOperating under Doppler effect principle these meters are non-invasive, meaning measurements can be taken without disturbing the system. Scales and rust in the pipes arelikely to impact the accuracy.

Ensure measurements are taken in a sufficiently long length of pipe free from flow disturbance due to bends, tees and other fittings. The pipe section where measurement is to be taken should be hammered gently to enable scales and rusts to fall out. For better accuracy, a section of the pipe can be replaced with new pipe for flow measurements.

Page 114: Energy Perf of Boilers

Tank filing method

In open flow systems such as water getting pumped to an overhead tank or a sump, the flowcan be measured by noting the difference in tank levels for a specified period during whichthe outlet flow from the tank is stopped. The internal tank dimensions should be preferabletaken from the design drawings, in the absence of which direct measurements may beresorted to.

Page 115: Energy Perf of Boilers

Installation of an on-line flowmeter

If the application to be measured is going to be critical and periodic then the best optionwould be to install an on-line flowmeter which can rid of the major problems encounteredwith other types.

Page 116: Energy Perf of Boilers

Determination of total head, H

Suction head (hs)

This is taken from the pump inlet pressure gauge readings and the value to be converted in to meters (1kg/cm2 = 10. m). If not the level difference between sump water

level to the centerline of the pump is to be measured. This gives the suction head in meters.

Discharge head (hd) This is taken from the pump discharge side pressure gauge. Installation of the pressure gaugein the discharge side is a must, if not already available.

Page 117: Energy Perf of Boilers

Pump efficiency exampleExample of pump efficiency calculation

Illustration of calculation method outlined A chemical plant operates a cooling water pump for process cooling and refrigeration applications. During the performance testing the following operating parameters were measured; Measured Data Pump flow, Q 0.40 m3/ s Power absorbed, P 325 kW Suction head (Tower basin level), h1 +1 M Delivery head, h2 55 M Height of cooling tower 5 M Motor efficiency 88 % Type of drive Direct coupled Density of water 996 kg/ m3

Page 118: Energy Perf of Boilers

Pump efficiency

Flow delivered by the pump 0.40 m3/s Total head, h2 -(+h1) 54 M Hydraulic power 0.40 x 54 x 996 x 9.81/1000 = 211 kW Actual power consumption 325 kW

Overall system efficiency 211/325 = 65 % Pump efficiency 65/0.88 = 74 %

Page 119: Energy Perf of Boilers

ENERGY PERFORMANCE ASSESSMENT OF COMPRESSORS

Page 120: Energy Perf of Boilers

Purpose of the Performance Test

• Actual Free Air Delivery (FAD) of the compressor

• Isothermal power required • Volumetric efficiency • Specific power requirement

Page 121: Energy Perf of Boilers

Performance Terms and Definitions

Compression ratio : Absolute discharge pressure of last stage Absolute intake pressure

Isothermal Power : It is the least power required to compress the air assuming isothermal conditions.

Isothermal Efficiency : The ratio of Isothermal power to shaft power

Volumetric efficiency : The ratio of Free air delivered to compressor swept volume

Specific power requirement: The ratio of power consumption (in kW ) to the volume delivered at ambient conditions.

Page 122: Energy Perf of Boilers

Measurement of Free Air Delivery (FAD) by Nozzle method

Principle: If specially shaped nozzle discharge air to the atmosphere from a receivergetting its supply from a compressor, sonic flow conditions sets in at the nozzle throat for a particular ratio of upstream pressure (receiver) to the downstream pressure(atmospheric) i.e. Mach number equals one.

When the pressure in the receiver is kept constant for a reasonable intervals of time,the airflow output of the compressor is equal to that of the nozzle and can becalculated from the known characteristic of the nozzle.

Page 123: Energy Perf of Boilers

Arrangement of test equipment

Page 124: Energy Perf of Boilers

Test nozzle sizes

Nozzle size Capacity (m3/hr) 6 10 16 22 33 50 80

125 165

3 – 9 9 –30

27 –90 60 – 170

130 – 375 300 – 450

750 – 2000 1800 – 5500 3500 - 10000

Page 125: Energy Perf of Boilers

Measurements and duration of the test

The compressor is started with the air from the receiver discharging to the atmospherethrough the flow nozzle. It should be ensured that the pressure drop through the throttlevalve should be equal to or twice the pressure beyond the throttle. After the system is stabilized the following measurements are carried out:

Receiver pressure Pressure and temperature before the nozzle Pressure drop across the nozzle Speed of the compressor kW, kWh and amps drawn by the compressor

The above readings are taken for the 40%, 60%, 100% and 110% of discharge pressure

values.

Page 126: Energy Perf of Boilers

Calculation Procedure for Nozzle Method

I. Free Air delivered Qf = k x π x d2 x T1 x 2 (P3-P4) (P3 x Ra) in m3/sec 4 P1 T3

k : Flow coefficient – as per IS

d : Nozzle diameter M T1 : Absolute inlet temperature oK

P1 : Absolute inlet pressure kg/cm2 P3 : Absolute Pressure before nozzle kg/cm2 T3 : Absolute temperature before nozzle oK Ra : Gas constant for air 287.1 J/kg k P3-P4 : Differential pressure across the nozzle kg/cm2

II. Isothermal Efficiency = Isothermal power/Input power

Isothermal power(kW) = P1 x Qf x loger 36.7 P1 = Absolute intake pressure kg/ cm2 Qf = Free air delivered m3/hr. r = Pressure ratio P2/P1 III. Specific power consumption = Power consumption ,kW at rated discharge pressure Free Air Delivered, m3/hr

Page 127: Energy Perf of Boilers

Volumetric efficiency

IV. Volumetric efficiency = Free air delivered m3/min x 100 Compressor displacement, m3/min

Compressor Displacement = π x D2 x L x S x χ x n 4

D = Cylinder bore, metre L = Cylinder stroke, metre S = Compressor speed rpm χ = 1 for single acting and 2 for double acting cylinders n = No. of cylinders

Page 128: Energy Perf of Boilers

ExampleCalculation of Isothermal Efficiency for a Reciprocating Air Compressor. Step – 1 : Calculate Volumetric Flow Rate k : Flow coefficient (Assumed as 1) d : Nozzle diameter : 0.08 metre P2 : Receiver Pressure - 3.5 kg / cm2 (a) P1 : Inlet Pressure - 1.04 kg / cm2(a) T1

: Inlet air temperature 30oC or 303oK P3 : Pressure before nozzle – 1.08 kg / cm2

T3 : Temperature before the nozzle 40oC or 313oK P3 – P4 : Pressure drop across the nozzle = 0.036 kg / cm2

Ra : Gas constant : 287 Joules / kg K Free Air Delivered Qf = k x π x d2 x T1 x 2 (P3-P4) (P3 x Ra) 4 P1 T3 = 1 x π ?? x (0.08)2 x 303 x 2 x 0.036 x 1.08 x 287 4 1.04 313 = 0.391 m3/sec = 1407.6 m3 / h.

Page 129: Energy Perf of Boilers

Step – 2 : Calculate Isothermal Power Requirement Isothermal Power (kW) = P1 x Qf x loger 36.7

P1 - Absolute intake pressure = 1.04 kg / cm2 (a) Qf -Free Air Delivered = 1407.6 m3 / h.

Compression ratio r = 3.5 = 3.36 1.04 ∴ Isothermal Power = 1.04 x 1407.6 x loge3.36 = 48.34 kW 36.7

Page 130: Energy Perf of Boilers

Step – 3 : Calculate Isothermal Efficiency Motor input power = 100 kW Motor and drive efficiency = 86 % Compressor input power = 86 kW Isothermal efficiency = Isothermal Power x 100 Compressor input Power = 48.34 x 100 = 56% 86.0

Page 131: Energy Perf of Boilers

Assessment of Specific Power requirement

Specific power consumption = Actual power consumed by the compressor Measured Free Air Delivery In the above example the measured flow is 1407.6 m3/hr and actual power consumption is 100 kW. Specific power requirement = 100 1407.6 = 0.071 kW/m3/hr

Page 132: Energy Perf of Boilers

Measurement of FAD by Pump Up Method:Example

An instrument air compressor capacity test gave the following results (assume the finalcompressed air temperature is same as the ambient temperature) – Comment?

Piston displacement : 16.88 m3/minute Theoretical compressor capacity : 14.75 m3/minute @ 7 kg/cm2 Compressor rated rpm 750 : Motor rated rpm : 1445 Receiver Volume : 7.79 m3 Additional hold up volume, i.e., pipe / water cooler, etc., is : 0.4974 m3 Total volume : 8.322 m3 Initial pressure P1 : 0.5 kg/cm2 Final pressure P2 : 7.03 kg/cm2 Atmospheric pressure P0 : 1.026 kg/cm2

,a

Compressor output m3/minute : ( )

timePumpup Pressure Atm.Volume Total PP 12

××−

: ( )

4.021 .02618.322 5.003.7

××−

= 13.17 m3/minute

Capacity shortfall with respect to 14.75 m3/minute rating is 1.577 m3/minute i.e., 10.69 %, which indicates compressor performance needs to be investigated further.

Page 133: Energy Perf of Boilers

ENERGY PERFORMANCE ASSESSMENT OF HVAC

SYSTEMS

Page 134: Energy Perf of Boilers

Purpose of the Performance Test

The purpose of performance assessment is to verify the performance of a refrigeration to verify the performance of a refrigeration system by using field measurements. system by using field measurements.

The test will measure net cooling capacity (tons of refrigeration) and energy requirements, at the actual operating conditions. The objective of the test is to estimate the energy consumption at actual load vis-à-vis design conditions

Page 135: Energy Perf of Boilers
Page 136: Energy Perf of Boilers

Performance Terms and Definition

Tons of refrigeration (TR): One ton of refrigeration is the amount of cooling obtainedby one ton of ice melting in one day: 3024 kCal/h, 12,000 Btu/h or 3.516 thermal kW.

Net Refrigerating Capacity. A quantity defined as the mass flow rate of the evaporator water multiplied by the difference in enthalpy of water entering and leaving the cooler,expressed in kCal/h, tons of Refrigeration.

kW/ton rating: Commonly referred to as efficiency, but actually power input tocompressor motor divided by tons of cooling produced, or kilowatts per ton (kW/ton).Lower kW/ton indicates higher efficiency.

Coefficient of Performance (COP): Chiller efficiency measured in Btu output (cooling)divided by Btu input (electric power).

Energy Efficiency Ratio (EER): Performance of smaller chillers and rooftop units is frequently measured in EER rather than kW/ton. EER is calculated by dividing a chiller's cooling capacity (in Btu/h) by its power input (in watts) at full-load conditions. The higher the EER, the more efficient the unit.

Page 137: Energy Perf of Boilers

To determine the net refrigeration capacity

The net refrigeration capacity in tons shall be obtained by the following equation:Net refrigeration Capacity (TR) = m x cp x (tin –tout)

3024Where m – mass flow rate of chilled water, m3/hr

cp - Specific heat, kcal/kg oCtin – Chilled water temperature at evaporator inlet oCtout- Chilled water temperature at evaporator outlet oC

a. Water flow rateb. Temperature difference between entering and leaving water

Page 138: Energy Perf of Boilers

Methods of measuring the flow

In the absence of an on-line flow meter the chilled water flow can be measured by the following methods

•In case where hot well and cold well are available, the flow can be measured from the tank level dip or rise by switching off the secondary pump.

•Non invasive method would require a well calibrated ultrasonic flow meter using which the flow can be measured without disturbing the system

•If the waterside pressure drops are close to the design values, it can be assumed that the water flow of pump is same as the designrated flow.

Page 139: Energy Perf of Boilers

Measurement of compressor power

The compressor power can be measured by a portable power analyserwhich would give reading directly in kW.

If not, the ampere has to be measured by the available on-line ammeter or by using a tong tester. The power can then be calculated by assuming a power factor of 0.9

kW = √3 x V x I ξ χοσφ

Page 140: Energy Perf of Boilers

The energy efficiency of a chiller is commonly expressed in one of the three following ratios:

1.Coefficient of performance COP = kW refrigeration effect

kW input2. Energy efficiency ratio EER = Btu/h refrigeration effect

Watt input3. Power per Ton

kW/Ton = kW inputTons refrigeration effect

Page 141: Energy Perf of Boilers

First calculate the kW/ton rating from the measured parameters.

a) kW/ton rating = Measured compressor power, kW Net refrigeration Capacity (TR)

Use this data to calculate other energy efficiency parameters with the following relations COP = 0.293 EER EER = 3.413 COP kW/Ton = 12 / EER EER = 12 / (kW/Ton) kW/Ton = 3.516 / COP COP = 3.516 / (kW/Ton) * Source : American Refrigeration Institute

b) Coefficient of performance (COP)

COP = 3.516

kW/ton rating

c) Energy Efficiency Ratio (EER) = 12 kW/ton rating

Page 142: Energy Perf of Boilers

Example

In a brewery chilling system, ethylene glycol is used a secondary refrigerant. The designed capacity is 40 TR. A test was conducted to find out the operating capacity and energy performance ratios. The flow was measured by switching off the secondary pump and measuring the tank level difference in hot well.measurements data:

Temperature of ethylene glycol entering evaporator = (-) 1oC Temperature of ethylene glycol leaving evaporator = (-) 4 oCEthylene glycol flow rates = 13200 kg/hrEvaporator ethylene glycol pressure drop (inlet to outlet) = 0.7 kg/cm2

Power input to compressor electrical power, kW = 39.5 kWSpecific heat capacity of ethylene glycol = 2.34 kCal/kgoC

Page 143: Energy Perf of Boilers

Calculations Net refrigeration Capacity (TR) = m x cp x (tin –tout)

3024 = 13200 x 2.34 x (-1 – (-4)) 3024 = 30.65 TR

kW/ton rating = Measured compressor power, kW Net refrigeration Capacity (TR)

= 39.5 kW

30.65 TR = 1.29 kW/TR

Coefficient of performance (COP) = 3.516 kW/ton rating = 3.516 1.29

= 2.73

Energy Efficiency Ratio (EER) = 12 kW/ton rating

= 12 1.29 = 9.3

Page 144: Energy Perf of Boilers

ENERGY PERFORMANCE ASSESSMENT OF LIGHTING

SYSTEMS

Page 145: Energy Perf of Boilers

Purpose of the Performance TestThe purpose of performance test is

• to calculate the installed efficacy in terms of lux/watt/m² (existing or design) for general lighting installation.

• The calculated value can be compared with the norms for specific types of interior installations for assessing improvement options.

• The installed load efficacy of an existing (or design) lighting installation can be assessed by carrying out a survey.

Page 146: Energy Perf of Boilers

Performance Terms and Definitions

Lumen is a unit of light flow or luminous flux. The lumen rating of a lamp is a measure of the total light output of the lamp. The most common measurement of light output (or luminous flux) is the lumen. Light sources are labeled with an output rating in lumens.

Lux is the metric unit of measure for illuminance of a surface. One luxis equal to one lumen per square meter.

Circuit Watts is the total power drawn by lamps and ballasts in a lighting circuit under assessment.

Page 147: Energy Perf of Boilers

Installed Load Efficacy is the average maintained illuminance provided on a horizontal working plane per circuit watt with general lighting of an interior. Unit: lux per watt per square metre (lux/W/m²)

Lamp Circuit Efficacy is the amount of light (lumens) emitted by a lamp for each watt of power consumed by the lamp circuit, i.e. including control gear losses. This is a more meaningful measure for those lamps that require control gear. Unit: lumens per circuit watt (lm/W)

Installed Power Density. The installed power density per 100 lux is the power needed per square metre of floor area to achieve 100 lux of average maintainedilluminance on a horizontal working plane with general lighting of an interior. Unit: watts per square metre per 100 lux (W/m²/100

Page 148: Energy Perf of Boilers

Installed load efficacy (lux/W/m²)

Installed Load Efficacy Ratio (ILER)

= Actual Lux/W/m² or Target W/m²/100luxTarget Lux/W/m² Actual W/m²/100lux

Average maintained illuminance is the average of lux levels measured at various points in a defined area.

Color Rendering Index (CRI) is a measure of the effect of light on the perceived color of objects. To determine the CRI of a lamp, the color appearances of a set of standard color chips are measured with special equipment under a reference light source with the same correlated color temperature as the lamp being evaluated. If the lamp renders the color of the chips identical to the reference light source, its CRI is 100. If the color rendering differs from the reference light source, the CRI is less than 100. A low CRI indicates that some colors may appear unnatural when illuminated by the lamp.

Installed power density (W/m²/100 lux) = 100

Page 149: Energy Perf of Boilers

Preparation (before Measurements)Before starting the measurements, the following care should be taken:

• All lamps should be operating and no luminaires should be dirty or stained.

There should be no significant obstructions to the flow of light throughout the interior, especially at the measuring points.

Accuracies of readings should be ensured by− Using accurate illuminance meters for measurements− Sufficient number and arrangement of measurement points

within the interior− Proper positioning of illuminance meterEnsuring that no obstructions /reflections from surfaces affect

measurement

Page 150: Energy Perf of Boilers

To Determine the Minimum Number and Positions of Measurement Points

Calculate the Room Index: RI = L x WHm(L + W)

Where L = length of interior; W = width of interior; Hm = the mounting height, which is the height of the lighting fittings above the horizontal working plane. The working plane is usually assumed to be 0.75m above the floor in offices and at 0.85m above floor level in manufacturing areas.

It does not matter whether these dimensions are in metres, yards or feet as long as the same unit is used throughout. Ascertain the minimum number of measurement points from Table

Page 151: Energy Perf of Boilers

For example, the dimensions of an interior are:

Length = 9m, Width = 5m, Height of luminaires above working plane (Hm) = 2m

Calculate RI = 9 x 5 = 1.932(9 + 5)

From Table 10.1 the minimum number of measurement points is 16

As it is not possible to approximate a “square array” of 16 points within such a rectangle it is necessary to increase the number of points to say 18, i.e. 6 x 3. These should be spaced as shown below:

Page 152: Energy Perf of Boilers

Therefore in this example the spacing between points along rows along the length of the interior = 9 ÷ 6 = 1.5m and the distance of the 'end' points from the wall = 1.5 ÷ 2 = 0.75m.

Similarly the distance between points across the width of the interior = 5 ÷ 3 = 1.67m with half this value, 0.83m, between the 'end' points and the walls.

If the grid of the measurement points coincides with that of thelighting fittings, large errors are possible and the number of measurement points should be increased to avoid such an occurrence.

Page 153: Energy Perf of Boilers

Calculation of the Installed Load Efficacy and Installed Load Efficacy Ratio of a General Lighting Installation in an Interior

STEP 1 Measure the floor area of the interior:

Area = -------------------- m²

STEP 2 Calculate the Room Index

RI = --------------------

STEP 3 Determine the total circuit watts of the installation by a power meter if a separate feeder for lighting is available. If the actual value is not known a reasonable approximation can be obtained by totaling up the lamp wattages including the ballasts:

Total circuit watts = -------------

STEP 4

Calculate Watts per square metre, Value of step 3 ÷ value of step 1

W/m² = ------------

STEP 5

Ascertain the average maintained illuminance by using lux meter, Eav. Maintained

Eav.maint. = ------------

STEP 6 Divide 5 by 4 to calculate lux per watt per square Metre

Lux/W/m² = ------------

STEP 7

Obtain target Lux/W/m² lux for type of the type of interior/application and RI (2):

Target Lux/W/m² =

STEP 8

Calculate Installed Load Efficacy Ratio ( 6 ÷ 7 ). ILER =

Page 154: Energy Perf of Boilers

Example of ILER Calculation STEP 1 Measure the floor area of the interior:

Area = 45 m² STEP 2 Calculate the Room Index

RI = 1.93

STEP 3 Determine the total circuit watts of the installation by a power meter if a separate feeder for lighting is available. If the actual value is not known a reasonable approximation can be obtained by totaling up the lamp wattages including the ballasts:

Total circuit watts = 990 W

STEP 4

Calculate Watts per square metre, 3 ÷1 : W/m² = 22

STEP 5

Ascertain the average maintained illuminance, Eav. Maintained (average lux levels measured at 18 points)

Eav.maint. = 700

STEP 6 Divide 5 by 4 to calculate the actual lux per watt per square Metre

Lux/W/m² = 31.8

STEP 7

Obtain target Lux/W/m² lux for type of the type of interior/application and RI (2):(Refer Table 10.2)

Target Lux/W/m² = 46

STEP 8

Calculate Installed Load Efficacy Ratio ( 6 ÷ 7 ).

ILER = 0.7

Referring to table 3, ILER of 0.7 means that there is scope for review of the lighting system. Annual energy wastage = (1 – ILER) x watts x no. of operating hours = (1 – 0.7) x 990 x 8 hrs/day x 300 days = 712 kWh/annum

Page 155: Energy Perf of Boilers

Table 10.4 IES Illuminance Categories and Values - For Generic Indoor Activities ACTIVITY CATEGORY LUX FOOTCANDLES Public spaces with dark surroundings A 20-30-50 2-3-5 Simple orientation for short temporary visits

B 50-75-100 5-7.5-10

Working spaces where visual tasks are only occasionally performed

C 100-150-200 10-15-20

Performance of visual tasks of high contrast or large size

D 200-300-500 20-30-50

Performance of visual tasks of medium contrast or small size

E 500-750-1000 50-75-100

Performance of visual tasks of low contrast or very small size

F 1000-1500-2000 100-150-200

Performance of visual tasks of low contrast or very small size over a prolonged period

G 2000-3000-5000 200-300-500

Performance of very prolonged and exacting visual tasks

H 5000-7500-10000 500-750-1000

Performance of very special visual tasks of extremely low contrast

I 10000-15000-20000

1000-1500-2000

A-C for illuminances over a large area (i.e. lobby space) D-F for localized tasks G-I for extremely difficult visual tasks

Page 156: Energy Perf of Boilers

Areas for Improvement

• Look for natural lighting opportunities through windows and other openings• In the case of industrial lighting, explore the scope for introducing translucent sheets• Assess scope for more energy efficient lamps and luminaries

• Assess the scope for rearrangement of lighting fixtures

Page 157: Energy Perf of Boilers

PERFORMING FINANCIAL ANALYSIS

IntroductionPlanning an energy efficiency or energy management projecEnergy auditor who advises the senior management of an organisation that capital should be invested in new PROJECTt.Inevitably, the management of the organisation would ask:

How much will the proposal cost?How much money will be saved by the proposal?

Page 158: Energy Perf of Boilers

What is Fixed and Variable Costs?

Item Type of cost Calculation Cost

Capital cost of generator Fixed - 9,00,000

Annual maintenance Fixed 30,000 x 5 (years)

1,50,000

Fuel cost Variable 219,000 x 3.50 7,66,500

Total cost 18,16,500

Example: The capital cost of the DG set is Rs.9,00,000, the annual output is 219 MWh, and the maintenance cost is Rs.30,000 per annum. The cost of producing each unit of electricity is 3.50 Rs./kWh. The total cost of a diesel generator operating over a 5-year period, taking into consideration both fixed and variable cost is

Page 159: Energy Perf of Boilers

Interest Charges

SSimple interest: If simple interest is applied, then charges are calculated as a fixed percentage of the capital that is borrowed. A fixed interest percentage is applied to each year of the loan and repayments are calculated using the equation

Compound interest: Compound interest is usually calculated annually (although this is not necessarily the case). The interest charged is calculated as a percentage of the outstanding loan at the end of each time period. It is termed 'compound' because the outstanding loan is the sum of the unpaid capital and the interest charges up to that point. The value of the total repayment can be calculated using the equation.

Page 160: Energy Perf of Boilers

Simple Payback PeriodExampleA new small cogeneration plant installation is

expected to reduce a company's annual energy bill byRs.4,86,000. If the capital cost of the new boiler installation is Rs.22,20,000 and the annual maintenance and operating costs are Rs. 42,000, the expected payback period for the project can be worked out as.

Solutionyears 5.0 42,000) -(4,86,00022,20,000/ PB ==

Page 161: Energy Perf of Boilers

Net Present Value Method,NPVThe net present value method considers the fact that a cash saving (often referred to as a 'cash flow') of Rs.1000 in year 10 of a project will be worth less than a cash flow of Rs.1000 in year 2. The net present value method achieves this by quantifying the impact of time on any particular future cash flow. This is done by equating each future cash flow to its current value today, in other words determining the present value of any future cash flow. The present value (PV) is determined by using an assumed interest rate, usually referred to as a discount rate. Discounting is the opposite process to compounding. Compounding determines the future value of present cash flows, where" discounting determines the present value of future cash flows.

Page 162: Energy Perf of Boilers

In order to understand the concept of present vale, consider the case described in Example 3.

If instead of installing a new cogeneration system, the company investedRs.22,20,000 in a bank at an annual interest rate of 8%, then:

08Rs.25,89,4 23,97,600) x (0.08 23,97,600 2year of end at the sum theof valueThe =+=

00Rs.23,97,6 22,20,000) x (0.08 22,20,000 1year of end at the sum theof valueThe =+=

The value of the investment would grow as compound interest is added, until after n years the value of the sum would be: nFV D x (1 IR/100)= +

Where FV is the future value of investment in Rs., and D is the value of initial deposit (or investment) in Rs., IR is Interest Rate and n is number of years.

The future value of the investment made at present, after 5 years will be:

5FV 22,20,000 x (1 8/100) Rs. 32,61,908.4= + =

Page 163: Energy Perf of Boilers

Present valueThe present value of an amount of money at any specified time in the future can be determined by the following equation.

Where PV is the present value of S in n years time (Rs.), and S is the value of cash flow in n years time (Rs.).

-nIR/100) (1 x S PV +=The net present value method calculates the present value of all the yearly cash flows (i.e. capital costs and net savings) incurred or accrued throughout the life of a project, and summates them. Costs are represented as a negative value and savings as a positive value. The sum of all the present values is known as the net present value (NPV). The higher the net present value, the more attractive the proposed project.

Page 164: Energy Perf of Boilers

Solution The annual cash flows should be multiplied by the annual discount factors for a rate of 8% to determine the annual present values, as shown in the Table below:

Project 1 Project 2 Year Discount Factor for 8%

(a) Net

savings (Rs.) (b)

Present value (Rs.)

(a x b)

Net savings (Rs.)

(c)

Present value (Rs.)

(a x c) 0 1.000 -30 000.00 -30 000.00 -30 000.00 -30 000.00 1 0.926 +6 000.00 +5 556.00 +6 600.00 +6 111.60 2 0.857 +6 000.00 +5 142.00 +6 600.00 +5 656.20 3 0.794 +6 000.00 +4 764.00 +6 300.00 +5 002.20 4 0.735 +6 000.00 +4 410.00 +6 300.00 +4 630.50 5 0.681 +6 000.00 +4 086.00 +6 000.00 +4 086.00 6 0.630 +6 000.00 +3 780.00 +6 000.00 +3 780.00 7 0.583 +6 000.00 +3 498.00 +5 700.00 +3323.10 8 0.540 +6 000.00 +3 240.00 +5 700.00 +3 078.00 9 0.500 +6 000.00 +3 000.00 +5 400.00 +2 700.00 10 0.463 +6 000.00 +2 778.00 +5 400.00 +2 500.20 NPV = +10 254.00 NPV = +10 867.80

It can be seen that over a 10 year life-span the net present value for Project 1 is Rs.10,254.00, while for Project 2 it is Rs.10,867.80. Therefore Project 2 is the preferential proposal.

Page 165: Energy Perf of Boilers

Internal rate of return methodIRR

• The discount rate which achieves a net present value of zero is known as the internal rate of return (IRR). The higher the internal rate of return, the more attractive the project.

Page 166: Energy Perf of Boilers

Internal rate of return analysis Example 6 A proposed project requires an initial capital investment of Rs.20 000. The cash flows generated by the project are shown in the table below:

Year Cash flow (Rs.) 0 -20,000.00 1 +6000.00 2 +5500.00 3 +5000.00 4 +4500.00 5 +4000.00 6 +4000.00

Given the above cash flow data, let us find out the internal rate of return for the project.

Page 167: Energy Perf of Boilers

Solution 8% discount rate 12% discount rate 16% discount rate Cash

flow (Rs.)

Discount factor

Present value (Rs.)

Discount factor

Present value (Rs.)

Discount factor

Present value (Rs.)

0 -20000 1.000 -20000 1.000 -20000 1.000 -20000 1 6000 0.926 5556 0.893 5358 0.862 5172 2 5500 0.857 4713.5 0.797 4383.5 0.743 4086.5 3 5000 0.794 3970 0.712 3560 0.641 3205 4 4500 0.735 3307.5 0.636 3862 0.552 2484 5 4000 0.681 2724 0.567 2268 0.476 1904 6 4000 0.630 2520 0.507 2028 0.410 1640 NPV = 2791 NPV = 459.5 NPV = -1508.5 It can clearly be seen that the discount rate which results in the net present value being zero lies somewhere between 12% and 16%. For12% discount rate, NPV is positive; for 16% discount rate, NPV is negative. Thus for some discount rate between 12 and 16 percent, present value benefits are equated to present value costs. To find the value exactly, one can interpolate between the two rates as follows:

(-1508.5))-(459.5459.5 x 0.12)-(0.16 0.12 return of rate Internal +=

%93.121508.5)(459.5

459.5 x 0.12)-(0.16 0.12 return of rate Internal =+

+=

Thus the internal rate of return for the project is 12.93 %.

Page 168: Energy Perf of Boilers

APPLICATION OF NON-CONVENTIONAL & RENEWABLE

ENERGY SOURCES

Page 169: Energy Perf of Boilers

Various forms of renewable energy

• Solar energy• Wind energy• Bio energy• Hydro energy• Geothermal energy• Wave and tidal energy

Page 170: Energy Perf of Boilers

Solar Energy

• Solar energy available is equivalent to 15000 times world’s commercial energy consumption

• 5-7 kWh/m2 for 300-330 days in a year• Applications are heating, lighting, cooking,

drying etc.• Solar thermal or solar electric (photo-

voltaic)

Page 171: Energy Perf of Boilers

Solar Thermal Energy Applications

• Low-Grade Heating Devices - up to the temperature of 100° C.

• Medium-Grade Heating Devices -up to the temperature of 100°-300°C

• High-Grade Heating Devices -above temperature of 300.° C

Page 172: Energy Perf of Boilers

Solar Collector

• Flat rectangular box with transparent cover

• Small tubes carrying water or fluid attached to black absorber plate

• Hot water transferred to storage tank Figure 12.1 Solar Flat plate collector

Page 173: Energy Perf of Boilers

Figure 12.2 Box Type solar collector

Solar Cooker

• FRP shell lined with SS reflector foil or aluminized polyester film

• Cooking vessel at focal point

• Can generate 500 kg of steam enough to cook for 500 people 2 twice a day

Page 174: Energy Perf of Boilers

Solar Photo-voltaic generation

• PV cells made of silicon which releases current when exposed to light

• Silicon cell covered with metal grid to direct current to a battery

• Group of cells connected together to from an array-1 cell can produce 1.5 W

• Modules are design to produce 12 V and rated by peak output at solar noon on a clear day

• Efficiency –upto 15%• Adds-on -Tracking system and

backup system

Page 175: Energy Perf of Boilers

Figure 12.6 Photovoltic water pumping

Page 176: Energy Perf of Boilers

Wind Energy

• Kinetic energy of wind to electrical energy• Annual Energy Output = Power x Time• Example: For a 100 kW turbine producing 20 kW at an

average wind speed of 15 mph, the calculation would be:• 100 kW x .20 (CF) = 20 kW x 8760 hours = 175,200 kWh• Capacity factor is wind turbine's actual energy output for

the year divided by the energy output if the machine operated at its rated power output for the entire year.

• Reasonable capacity factor would be 0.25 to 0.30. (0.40 will be good)

• Economic viability of wind power projects is extremely sensitive to the capacity factor and, there fore careful site selection is very important

Page 177: Energy Perf of Boilers

Wind speed vs. power generation potential

Average Wind Speed km/h (mph) Suitability

Up to 15 (9.5) No good 18 (11.25) Poor 22 (13.75) Moderate 25 (15.5) Good 29 (18) Excellent

Page 178: Energy Perf of Boilers

Biomass Energy

• Carbonaceous waste from human and natural activities

• Byproducts from wood industry, human and animal waste, agricultural crops, forest

• Main advantage is use of same equipment for combustion as fossil fuel

• Biomass use does not add to GHG emissions Carbon dioxide

Page 179: Energy Perf of Boilers

Direct Burning vs Biogas route

Biogas – 60% methane and 40% carbon dioxide

Safe for cooking and also produce high grade manure

Page 180: Energy Perf of Boilers

Biomass Briquetting

• Process of densifying loose agro-waste into a solidified biomass of high density for fuel

• Pollution free and eco-friendly• Some agricultural and forestry wastes can be briquetted

after suitable treatment• Can replace conventional fuels• JuteStick, Sawdust, Bagasse, CoffeeSpent, Tamarind,

CoffeeHusk, AlmondShell, Groundnutshells, CoirPith,BagaseePith, Barleystraw, Tobaccodust, RiceHusk,Deoiled Bran etc

Page 181: Energy Perf of Boilers

Biomass gasifers

• Conversion of solid Biomass (wood waste, agricultural residues etc) into a combustible gas mixture normally called producer gas.

• Producer gas is basically CO2, NH4,H2 and Nitrogen gas with calorific value of aroudn 1200 kCal/kg – Gasification Efficiency ~ 60%

• Suitable for IC engines for producing power• Use of gasification instead of direct burring leads

to 50% savings in fuel• Used along with diesel in dual firing mode in DG

set (70-80% substitution possible)

Page 182: Energy Perf of Boilers

Bipower

• Direct-fired• Cofiring• Gasification• Anaerobic digestion• Pyrolysis• Small modular.

Page 183: Energy Perf of Boilers

Energy potential by source

Solar Energy 20 MW / sq. kmWind Energy 20,000 MW Small Hydro 10,000 MW Ocean Thermal Power 50,000 MW Sea Wave Power 20,000 MW Tidal Power 10,000 MW Bio energy 17,000 MW Draught Animal Power 30,000 MW Energy from MSW 1,000 MW Biogas Plants 12 Million Plants Improved Wood Burning Stoves 120 Million Stoves Bagasse-based cogeneration 3500 MW

Page 184: Energy Perf of Boilers

Waste Waste MinimisationMinimisation &&Resource ConservationResource Conservation

Page 185: Energy Perf of Boilers

What is Waste ?Waste is a useful Material in wrong form in wrong place

Waste can be in form of:Defective productAir EmissionsWaste Water DischargesSolid WastesHazardous WastesProduction LossExcess EnergyExcess Water consumptionInefficient use of labourInefficient use of raw materialsUnusable/Discarded Chemical Residues

Page 186: Energy Perf of Boilers

Cost of Waste ?Cost is not only disposal cost, but includes;

• Disposal cost

• Inefficient energy use cost

• Purchase cost of wasted raw material

• Production cost for the waste material

• Management time spent on waste material

• Lost revenue for what could have been a product instead of waste

• Potential liabilities due to waste.

Page 187: Energy Perf of Boilers

What Is Waste Minimisation ?

“Systematically reducing waste at source “. This means

Prevention and/or reduction of waste generated

Efficient use of raw materials and packaging

Efficient use of fuel, electricity and water

Improving the quality of waste generated to facilitate

recycling and/or reduce hazard

Encouraging re-use, recycling and recovery.

Page 188: Energy Perf of Boilers

Waste Waste Minimiation Minimiation also means..also means..

Waste reductionPollution preventionSource reduction Cleaner technologySustainable Production

Page 189: Energy Perf of Boilers

Waste and Possible ResourcesWaste and Possible Resources

Wastes Resources

Fly ash from power plant Raw material for cement or brick manufacture

Bagasse wastes from sugarmanufature

Fuel for boiler

CO2 release from ammonia plant

Raw material for Urea manufacture

Page 190: Energy Perf of Boilers

WASTE MINIMISATION TECHNIQUES

SOURCE REDUCTIONRECYCLING

(ONSITE & OFFSITE)

PRODUCT CHANGES- PRODUCT SUBSTITUTION- PRODUCT CONSERVATION- CHANGE IN PRODUCT

COMPOSITION

SOURCE CONTROL

USE AND REUSE- RETURN TO ORIGINAL

PROCESS- RAW MATERIAL SUBSTITUTE

FOR ANOTHER PROCESS

RECLAMATION- PROCESSED FOR

RESOURCE RECOVERY- PROCESSED AS A

BY PRODUCT

INPUT MATERIAL CHANGES

- MATERIAL PURIFICATION- MATERIAL SUBSTITUTION

TECHNOLOGY CHANGES

- PROCESS CHANGES- EQUIPMENT, PIPING -OR LAYOUT CHANGES- ADDITIONAL AUTOMATION- CHANGES IN OPERATIONAL SETTINGS

GOOD OPERATING PRACTICE- PROCEDURAL MEASURES- LOSS PREVENTION- WASTE STREAM SEGREGATION- MANAGEMENT PRACTICES- MATERIAL HANDLING IMPROVEMENTS- PRODUCTION SCHEDULING

Page 191: Energy Perf of Boilers

Source Reduction

Good HousekeepingPreventing leakages and spillages through routine and preventive maintenanceGood working instructionsGood supervisionsEffective training of workforce

Regular cleaning of cartridge filters, inspection of tank linings & piping & periodic lubrication and greasing of pumps & blowers

Page 192: Energy Perf of Boilers

PROCESS CHANGES

Input Material ChangeSubstitution of input materials by eco-friendly (non-toxic or less toxic than existing and renewable) material preferably having longer service time.

Mercury and Cadmium free batteries

Page 193: Energy Perf of Boilers

PROCESS CHANGES

Better Process ControlModifications of the working procedures, machine-operating instructions and process record-keeping in order to run the processes at higher efficiency and with lower waste generation and emissions.

Excess control in boilers

Page 194: Energy Perf of Boilers

PROCESS CHANGES

Equipment ModificationsModification of existing production equipment and utilities, for instance by the addition of measuring and controlling devices, in order to run the processes at higher efficiency and lower waste and emission generation rates.

Conversion of existing boiler to FBC boiler

Page 195: Energy Perf of Boilers

PROCESS CHANGES

Technology ChangeReplacement of the technology, processing sequence and/or synthesis route in order tominimise waste and emission generation during production.

Replacement of mercury process to membrane process in caustic soda manufacture

Page 196: Energy Perf of Boilers

Recycling

On-site Recovery and ReuseReuse of wasted materials in the same process or for another useful application within the industry

Use of bagasse from crushed sugar cane as fuel in boiler

Page 197: Energy Perf of Boilers

Recycling

Production of Useful by-productModification of the waste generation process in

order to transform the wasted material into a material that can be reused or recycled for another application within or outside the company.

Page 198: Energy Perf of Boilers

ExamplesRecover Short fibre in pulp-making and use of etp sludge from paper board industry to make waste paper boards

Use of press mud from sugar mill and treated spent wash from distillery to manufacture bio-compost

Use of tanned leather pieces to make leather board or leather bags

Page 199: Energy Perf of Boilers

Product Modification

Characteristics of the product can be modified to minimize the environmental impacts of its production or those of the product itself during or after its use (disposal)

Jute bag instead of plastic bagElectricity or solar driven vehicles in place of petrol or diesel driven vehicles

Page 200: Energy Perf of Boilers

MATERIAL PURIFICATION

Use of purer anodes

Coal Beneficiation

De-sulfurisation of fuel

Un-leaded petrol

Use of lime with less inerts

Page 201: Energy Perf of Boilers

WASTE AUDIT

PHASE 1PREASSESSMENT

AUDIT PREPARATIONStep 1 Prepare and organise audit team and resourcesStep 2 Divide process into unit operationsStep 3 Construct process flow diagrams linking unit operation

PHASE 2MATERIALBALANCE

PROCESS INPUTSStep 4 Determine InputsStep 5 Record water usageStep 6 Measure current levels

of waste reuse/recycling

PROCESS OUTPUTSStep 7 Quantify products/by productsStep 8 Account for waste waterStep 9 Account for gaseous emissionsStep 10 Account for off-site wastes

DERIVE A MATERIAL BALANCEStep 11 Assemble input and output informationStep 12 Derive a preliminary material balanceStep 13 & 14 Evaluate and refine material balance

IDENTIFY WASTE REDUCTION OPTIONSStep 15 Identify obvious waste reduction measuresStep 16 Target and characterise problem wastesStep 17 Investigate the possibility of waste segregationStep 18 Identify long-term waste reduction measures

EVALUATE WASTE REDUCTION OPTIONSStep 19 Undertake environmental and economic evaluation

of waste reduction options List viable options

WASTE REDUCTION ACTION PLANStep 20 Design and implement a waste reduction action

action plan to achieve improved process efficiency

PHASE 3SYNTHESIS

Page 202: Energy Perf of Boilers

TYPICAL COMPONENTS OF A MATERIAL BALANCE

RAW MATERIALS GASEOUS EMISSIONS

CATALYST PRODUCTPLANT

PROCESSOR

UNIT OPERATIONS

WATER/AIR BY PRODUCTSINCLUDING WASTESFOR RECOVERYPOWER

WASTE WATER

LIQUID WASTES FORSTORAGE AND OROFF-SITE DISPOSAL

RECYCLE

REUSABLE WASTE IN

ANOTHER OPERATIONSOLID WASTES FORSTORAGE AND OROFF-SITE DISPOSAL

Page 203: Energy Perf of Boilers

TYPICAL COMPONENTS OF AN ENERGY BALANCE

COOLING WATER PRODUCTION LOSS

ENERGY IN VAPOURS

PROCESS OR UNIT OPERATIONS

STEAM

ENERGY IN RAW MATERIAL

ENERGY IN HOT PRODUCTELECTRICITY

ENERGY IN HOT RESIDUE

CONDENSATE

ENERGY IN COOLING WATER

Page 204: Energy Perf of Boilers

ASSIGN COST TO WASTE STREAMSTo Highlight the quantity of resources lost in waste streams along with their associated cost.

Cost of wastes include:↔ Cost of raw materials in waste↔ Cost of product in waste↔ Cost of waste treatment↔ Cost of waste disposal↔ Cost of waste transportation↔ Environmental liability costs (future)↔ Cost of maintaining required work

environment↔ Cost due to waste cess

Page 205: Energy Perf of Boilers

REVIEW OF PROCESS TO IDENTIFY REVIEW OF PROCESS TO IDENTIFY CAUSES FOR WASTE GENERATIONCAUSES FOR WASTE GENERATION

> Carry out a Cause Analysis to locate & pin -point the causes of waste generation

> It could be as simple as poor house keeping practice to complex technological problems

Page 206: Energy Perf of Boilers

TYPICAL CAUSES OF WASTETECHNICAL CAUSES

* Poor housekeeping

*Operational and maintenance negligence

*Poor raw material quality

*Poor Process / equipment design

*Poor Lay-out

•Bad TechnologyMANAGERIAL CAUSES

•Inadequately trained personnel

•Employee De-motivation

Page 207: Energy Perf of Boilers

BENEFITS OF WASTE MINIMISATIONDIRECT BENEFITS

REDUCTION INRaw Material UseEnergy UseWaste QuantityCapital Costs of new Pollution Control SystemsWaste Treatment CostClean-up costsRejects

IMPROVEMENTS INWorking Conditions

Safety Aspects

Environmental Performance

Page 208: Energy Perf of Boilers

INDIRECT BENEFITS

⇒ Better public image

⇒ Improved Staff Motivation

⇒ Improved Customer Loyalty

⇒ Improved Access to capital

⇒ Reduced Risk & Liability