ATeaching plan
A1
ACINV MAIN
M
DRIVEWAY
C S
TROOF MOUNTED CONDUIT (TYP.)
μ
RS
SHEET INDEX
PV0.0 COVER AND SITE PLAN
PV1.0 GENERAL NOTES
PV2.0 ARRAY LAYOUT
PV3.0 LINE DIAGRAM
PV4.0 LABELS
PHOTOVOLTAIC SYSTEM1 2 3 4 51
####
C
B
A
C
B
A
REV #:DESIGNED BY:
CUSTOMER INFORMATION:
DATE:
12/1/16
SYSTEM SIZE:
AC / DC kW STC: 2.687kW \ 3kW
EQUIPMENT:
PV MODULES: (10) LG LG300N1K-G4
INVERTER(S): (1) ABB PVI-3.0-OUTD-S-US-A
SCOPE OF WORK:
INSTALLATION OF A SAFE AND CODE-COMPLIANT GRID-TIED SOLAR PV SYSTEM ON AN EXISTING RESIDENTIAL ROOF TOP. APPLICABLE CODES:
CONTRACTOR INFORMATION:
JURISDICTIONAL INFORMATION:
NOTES TO INSTALLER:
2016 CEC (BASED ON 2014 NEC)2016 CBC2016 CRC2016 CPC2016 CMC2016 CFCLOCAL AMENDMENTS TO CA CODES
FOR INSTALLER USE ONLY
POST INSTALL SUNEYES REQUIRED?
I CERTIFY THAT NO CHANGES HAVEBEEN MADE TO THE ARRAY LAYOUT:
PV- 0.00
NO
N
STRUCTURAL UPGRADES
FENCE
SD
PV METERPVMROOF OBSTRUCTION
UTILITY METER
AC DISCONNECTAC
MONITORING UNIT
JUNCTION BOXMT
DRIVEWAY
RAPID SHUTDOWN ROOFBOX
RS
KEY:
CONDUIT RUNPROPERTY LINE
SUBPANEL
DC DISCONNECT
INVERTER
MAIN SERVICE PANELM
SUB
DC
INV
MAIN
SOLAR MODULE μ
FIRE CLEARANCE
JB
SCALE : SITE PLAN
N.T.S.
1. ALL WORK MUST COMPLY WITH THE REQUIREMENTSOF THE LATEST EDITION OF THE CALIFORNIA BUILDINGCODE AND THE CALIFORNIA ELECTRICAL CODE(ARTICLES 690 AND 705 FOR PV).2. ALL ROOF PENETRATIONS ARE REQUIRED TO BEFLASHED. ALL TILE ROOFS ARE REQUIRED TO BEDOUBLE-FLASHED.3. ROOF DECK FLASHING IS REQUIRED TO BEINSPECTED PRIOR TO PANEL INSTALLATION.4. CONTRACTOR IS REQUIRED TO HOLD A CURRENTAND VALID C-10 OR C-46 LICENSE.5. DESIGNED TO 110MPH 3-SECOND PEAK GUST.
ANYTOWN, CITY OF5555 C STREETANYTOWN, CA 99999
PV INSTALLER8888 B STREETANYTOWN, CA 99999
CUSTOMER NAME4444 C STREETANYTOWN, CA 99999
A2
GENERAL NOTES:1 2 3 4 51
####
C
B
A
C
B
A
REV #:DESIGNED BY:
CUSTOMER INFORMATION:
DATE:
12/1/161.0PV-
0
GENERAL NOTES:
N1. DRAWINGS ARE DIAGRAMMATIC ONLY. THE LOCATION AND ROUTING OF RACEWAYS SHALL BE DETERMINED BY THE CONTRACTOR UNLESS OTHERWISE NOTED OR STANDARDIZED.
N2. IF A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT DEVICES, OVERCURRENT PROTECTION, GROUNDING SYSTEMS, ETC. (ALL EQUIPMENT AND MATERIALS) THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIALS AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS IN THE SPECIFICATIONS OR NOTED ON THE PLANS TO ENSURE COMPLETE COMPLIANCE WITH ALL CODES AND TO ENSURE THE LONGEVITY AND SAFETY OF THE OPERABLE SYSTEM.
N3. ALL OUTDOOR EQUIPMENT SHALL BE MIN. NEMA 3R RATED.
N4. METAL CONDUIT AND ENCLOSURES SHALL BE USED WHERE PV SOURCE OR OUTPUT CIRCUITS ARE RUN INSIDE A BUILDING.
N5. MODULES SHALL NOT BE PLACED OVER ANY PLUMBING VENTS AND AT LEAST 6" ABOVE FLUSH VENTS.
N6. THE ELECTRICAL CONTRACTOR SHALL COMPLY WITH ANY AND ALL REQUIREMENTS GIVEN BY UTILITY COMPANIES.
N7. FOR ADDITIONAL EQUIPMENT SPECIFICATIONS, SEE PROVIDED CUT SHEETS.
N8. ALL NEC REFERENCES SHALL BE DIRECTLY INTERCHANGEABLE WITH CEC REFERENCES.
N9. IT IS ILLEGAL FOR ANYONE UNLESS ACTING UNDER THE DIRECTION OF A LICENSED PROFFESIONAL ENGINEER OR REGISTERED ARCHITECT TO ALTER ANY ITEMS ON THIS PLAN.
N10. THE ENGINEER HAS NOT BEEN RETAINED FOR JOB SUPERVISION.
N11. ALL OSHA REGULATIONS AND STANDARDS FOR SAFE AND HEALTHFUL WORKING CONDITIONS TO BE FOLLOWED.
N12. ALL CONTRACTORS WORKING ON ROOFS TO BE INSURED AS SUCH.
STRUCTURAL NOTES:
S1. MOUNTS ARE DIAGRAMMATIC AND EXACT LOCATION MAY CHANGE, BUT SHALL BE ACCURATELY SPACED.
S2. MOUNTS SHALL BE STAGGERED WHEN NECESSARY TO EVENLY DISTRIBUTE LOAD AMONGST RAFTERS.
S3. DO NOT SPLICE RAILS IN MIDDLE 50% OF SPAN BETWEEN TWO MOUNTS.
ELECTRICAL NOTES:
E1. MAXIMUM VOLTAGE DOES NOT EXCEED 600VDC, AND DC EQUIPMENT SHALL BE RATED FOR AT LEAST 600VDC.
E2. ANY EQUIPMENT OR ELECTRICAL MATERIALS USED FOR THIS INSTALLATION SHALL BE NEW AND LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY.
E3. AN INVERTER IN AN INTERACTIVE SOLAR PV SYSTEM SHALL AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE CONNECTED ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK UPON LOSS OF VOLTAGE IN THAT SYSTEM AND SHALL REMAIN IN THAT STATE UNTIL THE ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN RESTORED.
E4. ALL PV ARRAYS SHALL BE EQUIPPED WITH DC GROUND FAULT PROTECTION BY INVERTER)(S), AND ARC FAULT PROTECTION IS INVERTER-INTEGRATED.
E5. ANY AC COMPONENT SHALL MEET OR EXCEED THE AVAILABLE FAULT CURRENT CALCULATED AT THAT COMPONENT.
E6. ALL MODULES AND ANY RELATED ROOF MOUNTED METALLIC EQUIPMENT SHALL BE PROPERLY BONDED AND GROUNDED.
E7. ALL WIRE, VOLTAGES, AMPERAGES AND EQUIPMENT IS SIZED ACCORDING TO TEMPERATURE DERATING AND LOCATION.
E8. ONLY COPPER (CU) CONDUCTORS SHALL BE USED FOR NEW WIRING. CONDUCTORS SHALL BE STRANDED OR SOLID WITH PROPERLY RATED CONNECTORS.
E9. ALL MODULES AND RACKING SHALL BE GROUNDED VIA UL2703-LISTED RACKING SYSTEM'S INTEGRATED GROUNDING (PLEASE SEE DATA SHEET) OR WITH TIN PLATED DIRECT BURIAL RATED LAY IN LUGS USING STAINLESS STEEL HARDWARE, STAR WASHERS, AND THREAD FORMING BOLTS.
CUSTOMER NAME4444 C STREETANYTOWN, CA 99999
A3
3'
16'-7"
3'10
'-10"
3'
2X8 NOMINAL, 24 O.C.
COMPOSITE SHINGLE5" X 5/16" - LAG
2.5" MIN. EMBEDMENT PER SCREW
QMSE-LAG SHINGLE
L-FOOT
IRONRIDGE XR10
SOLAR MODULE
1 2 3 4 51##
##
C
B
A
C
B
A
REV #:DESIGNED BY:
CUSTOMER INFORMATION:
DATE:
12/1/162.0PV-
0
STRUCTURAL UPGRADES
FIRE CLEARANCE
ATTIC VENT
PLUMBING OR ATTIC VENT
CHIMNEY
SKYLIGHT
SOLAR MODULE
SYMBOL KEY:
ROOF
RAFTERS
RAIL
MOUNT
STRING CONFIG.# #
NOTE:MODULES SHALL NOT BE GREATER THAN 8 INCHES ABOVE ROOF COVERING
MODULE SPECIFICATIONS(10) LG LG300N1K-G4MODULE WEIGHT: 37.48MODULE LENGTH: 64.57MODULE WIDTH: 39.37
SCALE : 1 ARRAY LAYOUT3/16" = 1'-0"
SCALE : 2 MOUNTING DETAILNTS
RAFTER SIZE:RAFTER SPAN:RAFTER SPACING:ROOF MATERIAL:
2X8 NOMINAL10' - 7"
24"COMPOSITE SHINGLE
ROOF 1 SPECS
NUMBER OF MODULES:TOTAL MOD. WEIGHT (lbs):RACKING WEIGHT (lbs):ARRAY WEIGHT (lbs):ARRAY AREA (sqft):ARRAY DEAD LOAD (lbs/sqft):NUMBER OF MOUNTS:LOAD PER MOUNT(lbs):ARRAY AZIMUTH(°)ARRAY TILT(°)NUMBER OF FLOORS
10374.8
58432.8176.5
2.522
19.7
231
ARRAY 1 SPECS
180
CUSTOMER NAME4444 C STREETANYTOWN, CA 99999
A4
- +10 MODULES1 STRING OF
(2) #10 PV-Wire(1) #10 EGCFREE AIR
DC ~ AC
INVERTER
__
MPPT 1
OUTPUTEGC
(N) INVERTER W/ INTEGRATED DC DISCONNECTS
PVI-3.0-OUTD-S-US-A
(3) #10 THWN-2(1) #10 EGC1/2" EMT
METERLOCUS
(3) #10 THWN-2(1) #10 EGC1/2" EMT
LINELOAD
AC DISCONNECT, 30AMP,
NON-FUSIBLE, C-H DG221URB
(3) #10 THWN-2(1) #10 EGC1/2" EMT
METER
(E) LOADS
240V 2P 3-W 1F
(E) LOADS
20A 2P
100A MAIN BREAKER
(E) 100A Cutler Hammer MSP(N) ABB RS2-2PN6RAPID SHUTDOWN BOX
PS
RAPID SHUTDOWN
(2) #10 THWN-2(1) #10 EGC1/2" EMT
1 2 3 4 51##
##
C
B
A
C
B
A
REV #:DESIGNED BY:
CUSTOMER INFORMATION:
DATE:
12/1/163.0PV-
DESIGN CONDITIONSHIGHEST 2% DB DESIGN TEMP (°C): 37MIN. MEAN EXTREME ANNUAL DB (°C): -3
0
BREAKERSWITCHSCREW TERMINALFUSE
ELECTRICAL KEY:
SPLICEEARTH GROUNDCHASSIS GROUNDGECEGC
MODULE ELECTRICAL SPECIFICATIONS(10) LG LG300N1K-G4SHORT CIRCUIT CURRENT (lsc): 9.7OPEN CIRCUIT VOLTAGE (Voc): 39.7OPERATING CURRENT (IMP): 9.26OPERATING VOLTAGE (VMP): 32.5MAX SERIES FUSE RATING: 20STC RATING: 300PTC RATING: 279.9
RATED WATTS (EACH):AC OPERATING VOLTAGE (V):AC OPERATING CURRENT (A):NUMBER OF MPPT CHANNELSINVERTER EFFICIENCY:
3300
14.5
0.96
240
ABB PVI-3.0-OUTD-S-US-AINVERTER 1 SPECIFICATIONS
2
INTEGRATED DC DISCONNECT
MAXPOWER POINT CURRENT (Imp):MAX POWER POINT VOLTAGE (Vmp):MAX SYSTEM VOLTAGE (Voc):SOURCE CIRCUIT CURRENT (Isc):MAX SHORT CIRCUIT CURRENT (Isc):
9.332542812.112.1
INVERTER 1 MPPT SPECIFICATIONS
MAX Voc = 10 x [39.7V + (39.7V x -0.0028 x (-3°C - 25°C))] = 428VDCImax = 9.7A x 1 STRING x 1.25 = 12.125A
100 x 1.2 = 120(120 - 100(MCB)) / 125% = 16AMAX ALLOWABLE INV. OUTPUT CURRENT RATING = 16A
CONTINUOUS USE = Imax * 1.25 = 15.16ACONDITIONS OF USE = Imax / Tcorr / Cfill
= 12.1A/0.71/1 = 17.04ACONDUCTOR SIZE FOR 17.04AINSTALLATION SHALL USE MIN. #10 AWG
CONDUIT ELEVATION: 1/2 TO 3-1/2" = 22 °CHIGH AMBIENT TEMPERATURE: 37 °CEXTREME LOW: -3°CROOFTOP AMBIENT TEMP (Tcorr): 59°C = 0.71CONDUIT FILL (Cfill): 1
10 MODULES TOTAL10 x 279.9(PTC WATTS) x 0.96 = 2687 CEC WATTS
PVI-3.0-OUTD-S-US-A MAX OUTPUT CURRENT = 14.5ABREAKER SIZE = 14.5A x 1.25 = 18.125A –» 20A
CUSTOMER NAME4444 C STREETANYTOWN, CA 99999
A5
ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS
TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN
POSITION
NEC 690.17(E)PLACE THIS LABEL ON ALL DISCONNECTING
MEANS WHERE ENERGIZED IN AN OPEN POSITION
WARNING
PHOTOVOLTAIC POWER SOURCE
NEC 690.31 (E) 3 & 4; 2012 IFC 605.11.1PLACE ON ALL JUNCTION BOXES, EXPOSED RACEWAYS EVERY 10' AND 1' FROM BENDS
AND PENETRATIONS, ADJACENT TO THE MAIN SERVICE DISCONNECT
WARNINGWARNING
NEC 690.5(c)PLACE THIS LABEL ON INVERTER(S) OR NEAR
GROUND-FAULT INDICATOR (ON INVERTER(S) U.O.N.)
ELECTRIC SHOCK HAZARDIF A GROUND FAULT IS INDICATED,
NORMALLY GROUNDED CONDUCTORSMAY BE UNGROUNDED AND ENERGIZED
1 2 3 4 51##
##
C
B
A
C
B
A
REV #:DESIGNED BY:
CUSTOMER INFORMATION:
DATE:
12/1/164.0PV-
INTERACTIVE PHOTOVOLTAIC POWER SOURCE
RATED AC OUTPUT CURRENT (A): 14.5
NOMINAL OPERATING AC VOLTAGE (V): 240
WARNING
NEC 690.35(F) PLACE THIS LABEL AT EACH JUNCTION BOX, COMBINER BOX,
DISCONNECT AND DEVICE WHERE ENERGIZED, UNGROUNDED CIRCUITS MAY BE EXPOSED DURING SERVICE:
ELECTRIC SHOCK HAZARDTHE DC CONDUCTORS OF THIS
PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED
NEC 690.56(c)PLACE ON RAPID SHUT DOWN DISCONNECT WHEN RAPID SHUT
DOWN IS INSTALLED
PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN
0
NOTE:BACKGROUND AND LETTERING COLORS FOR SIGNAGE/LABELS SHALL COMPLY WITH (IN ORDER OF PRIORITY) AHJ & FIRE DEPARTMENT AMENDMENTS, STATE CODE, AND ANSI GUIDELINES. THIS PAGE IS INTENDED FOR SIGNAGE/LABEL VERBIAGE ONLY.
NEC 705.12(D)(2)(b)PLACE THIS LABEL AT P.O.C. TO SERVICE
DISTRIBUTION EQUIPMENT (I.E. MAIN PANEL (AND SUBPANEL IF APPLICABLE))
INVERTER OUTPUT CONNECTIONDO NOT RELOCATE THIS OVERCURRENT DEVICE
WARNING
CONTAINS MULTIPLE POWER SOURCES
NEC 705.12(D)(3)PLACE LABEL ON ALL EQUIPMENT CONTAINING
OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO A BUSBAR OR CONDUCTORS SUPPLIED FROM MULTIPLE
SOURCES.
CAUTION
PHOTOVOLTAIC SYSTEM DISCONNECT
RATED MAX POWER POINT CURRENT (Imp):
RATED MAX POWER POINT VOLTAGE (Vmp):
MAX SYSTEM VOLTAGE (Voc):
MAX CIRCUIT CURRENT (Isc):
9.3
428
12.1
325
INVERTER 1 MPPT DC DISCONNECT
CUSTOMER NAME4444 C STREETANYTOWN, CA 99999
A6
ACINV MAIN
M
μ
RS
N
LOCATION OFINVERTERS WITHINTEGRATED DCDISCONNECT
LOCATION OF MAINSERVICE ENTRANCEAND UTILITY METER
DRIVEWAY
POWER TO THIS BUILDING IS SUPPLIED FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN
DIRECTORY LABEL PER NEC 705.10
1 2 3 4 51##
##
C
B
A
C
B
A
REV #:DESIGNED BY:
CUSTOMER INFORMATION:
DATE:
12/1/165.0PV-
0
CUSTOMER NAME4444 C STREETANYTOWN, CA 99999
A7
LG300N1K-G4
60 cellLG’s new module, LG NeON™ 2 Black, adopts Cello technology. Cello technology replaces 3 busbars with 12 thin wires to enhance power output and reliability. LG NeON™ 2 Black demonstrates LG’s efforts to increase
warranty, durability, performance under real environment, and aesthetic design suitable for roofs.
Enhanced Performance WarrantyLG NeON™ 2 Black has an enhanced performance warranty. The annual degradation has fallen from -0.7%/yr to -0.6%/yr. Even after 25 years, the cell guarantees 2.4%p more output than the previous LG NeON™ modules.
High Power OutputCompared with previous models, the LG NeON™ 2 Black
Aesthetic RoofLG NeON™ 2 Black has been designed with aesthetics in mind; thinner wires that appear all black at a distance. The product may increase the value of a property with its modern design.
Double-Sided Cell StructureThe rear of the cell used in LG NeON™ 2 Black will contribute
from the rear of the module is reabsorbed to generate a great amount of additional power.
Better Performance on a Sunny DayLG NeON™ 2 Black now performs better on sunny days
Outstanding DurabilityWith its newly reinforced frame design, LG has extended the warranty of the LG NeON™ 2 Black for an additional 2 years. Additionally, LG NeON™ 2 Black can endure a front load up to 6000 Pa, and a rear load up to 5400 Pa.
About LG Electronics
Innovation fora Better Life
LG Electronics is a global player who has been committed to expanding its capacity, based on solar energy business as its future growth engine. We embarked on a solar energy source research program in 1985,supported by LG Group’s rich experience in semi-conductor, LCD, st Mono X® series to the market in 2010, which were exported to 32 countries inthe following 2 years, thereafter. In 2013, NeON™ (previously known as Mono X® NeON) & 2015 NeON2 with CELLO technology won “Intersolar Award”, which proved LG is the leader of innovation in theindustry.
Dimensions (mm/in)
North America Solar Business TeamLG Electronics U.S.A. Inc1000 Sylvan Ave, Englewood Cliffs, NJ 07632
Contact: lg.solar@lge.comwww.lgsolarusa.com
DS-N2-60-K-G-F-EN-50427
Copyright © 2016 LG Electronics. All rights reserved.01/01/2016
* The distance between the center of the mounting/grounding holes.
Electrical Properties (NOCT*)
Module TypeMaximum Power (Pmax)MPP Voltage (Vmpp)MPP Current (Impp)Open Circuit Voltage (Voc)Short Circuit Current (Isc)
300 W222
30.1
7.38
36.9
7.81* NOCT (Nominal Operating Cell Temperature): Irradiance 800 W/m2, ambient temperature 20 °C, wind speed 1 m/s
Electrical Properties (STC *)
Module TypeMPP Voltage (Vmpp)MPP Current (Impp)Open Circuit Voltage (Voc)Short Circuit Current (Isc)
Operating Temperature (°C)Maximum System Voltage (V) Maximum Series Fuse Rating (A)Power Tolerance (%)
-40 ~ +90
1000 (IEC/UL)
20
0 ~ +3
300 W32.5
9.26
39.7
9.70
18.3
* STC (Standard Test Condition): Irradiance 1000 W/m², Module Temperature 25 °C, AM 1.5* The nameplate power output is measured and determined by LG Electronics at its sole and absolute discretion.
LG300N1K-G4
Innovation for a Better Life
Detail X Detail Y Detail Z Long side frame
7.5
/ 0.3
0
4.0
/ 0.1
6
5.5 / 0.22
R1.5 / R0.06
4.0 / 0.16Ø8.2 / Ø0.32
10.0 / 0.39
29.0 / 1.14
40.0
/ 1.
57
10.0 / 0.39
29.0 / 1.14
40.0
/ 1.
57
Short side frame
40 / 1.57
270
/ 0.6
3
170
/ 6.6
9
105
/ 4.1
3
(Z view)Ø8.2 / Ø0.32Mounting holes(8ea)
(X view)5.5 x 4.0 / 0.22 x 0.16
Drain holes(4ea)
Ø4.3 / Ø0.17
Grounding holes(12ea)
1000 / 39.37
(Distance between mounting holes)
(Size of short side)
1640
/ 64
.57
(Siz
e of
long
sid
e)
960 / 37.80
1100
/ 4
3.31
Junction box
1000 / 39.37Cable length
(Dis
tanc
e be
twee
n m
ount
ing
hole
s)
1300
/ 52
.18
(Dis
tanc
e be
twee
n m
ount
ing
hole
s)
Drain holes(4ea)
(Y view)4.0 x 7.5 / 0.16 x 0.30Characteristic Curves
Mechanical Properties
CellsCell Vendor Cell Type Cell Dimensions # of BusbarDimensions (L x W x H)
Front LoadRear LoadWeightConnector TypeJunction BoxLength of Cables Glass Frame
6 x 10
LG
Monocrystalline / N-type
156.75 x 156.75 mm / 6 inches
12 (Multi Wire Busbar)
1640 x 1000 x 40 mm64.57 x 39.37 x 1.57 inch
6000 Pa / 125 psf
5400 Pa / 113 psf
17.0 ± 0.5 kg / 37.48 ± 1.1 lbs
MC4, MC4 Compatible, IP67
IP67 with 3 Bypass Diodes
2 x 1000 mm / 2 x 39.37 inch
High Transmission Tempered Glass
Anodized Aluminum
Temperature Characteristics
NOCTPmppVocIsc
45 ± 3 °C
-0.38 %/°C
-0.28 %/°C
0.03 %/°C
Module Fire Performance (USA)Fire Rating (for CANADA)Product WarrantyOutput Warranty of Pmax
IEC 61215, IEC 61730-1/-2
IEC 62716 (Ammonia Test)
IEC 61701 (Salt Mist Corrosion Test)
ISO 9001
UL 1703
Type 2 (UL 1703)
Class C (ULC/ORD C1703)
12 years
Linear warranty** 1) 1st year: 98%, 2) After 2nd year: 0.6%p annual degradation, 3) 83.6% for 25 years
Curr
ent
(A)
Isc,
Voc
, Pm
ax (%
)
Voltage (V)
Temperature (°C)
10.001000W
600W
200W
800W
400W
6.00
2.00
8.00
4.00
0.00 10.00 30.0020.00 40.0015.00 35.0025.00 45.005.00
Isc
Voc
Pmax
140
60
100
20
120
40
80
0-40 900 25-25 50 75
A8
7
Mechanical Installation
Module Mounting
solar modules is contingent upon modules being mounted in accordance with the requirements described in this section.
considered to comply with the requirements of UL 1703 unless the module with hardware that has been tested and evaluated with the module under this standard or by a field inspection certifying that the installed module complies with the requirements of UL 1703.
Site ConsiderationLGE solar modules should be mounted in a location that meets the following requirements.Operating Temperature
Design Strength
75lb/ft2. (Mounting by using frame bolts holes)
Excluded Operating Environments
operated in a location where they could come in direct contact with salt water or ammonia.
Mounting MethodsGeneral Information
sunlight exposure.
that the front/top glass faces downward in order to prevent water from entering the junction box, which could cause a safety hazard.
Clearance between the solar module frames and structures such as roofs or ground is required to prevent wiring damage and to allow air to circulate behind the solar module. The recommended standoff height is a minimum of 100mm.
mounted over a fire-resistant roof covering rated for the application. The fire resistance of the solar module is class C after ANSI/UL790.
class rating.
its factory frame is fully intact.
authorized and qualified individual
the solar module and reduce the strength of the frame.
frames to avoid tension from thermal expansion.
mounted in the manner specified in the mechanical mounting instructions.
The module is considered to be in compliance with UL1703 only when the module in mounted in the manner specified by the mounting instructions below.
mounted with racking and mounting products certified and listed for system fire class rating in accordance with UL1703 edition 2014 and UL2703 edition 2014.
for fire safety guidelines and requirements for any building or structure on to which the panels will be installed.
recommended to be taken an appropriate countermeasure to prevent possible damages to the lower side frame by slipping snow. (A snow guard should be installed in accordance with the manufacturer’s instructions.)
Solar module
Roof
Supporting part
A9
Solar inverters
ABB string invertersPVI-3.0/3.6/3.8/4.2-TL-OUTD 3.0kW to 4.2kW
This family of single-phase string
inverters complements the typical
number of rooftop solar panels
enabling homeowners to get the most
efficient energy harvesting for the size
of the property.
This inverter offers a dual input
section that processes two strings
with independent Multiple Power Point
Tracking (MPPT).
This is especially useful for rooftop
installations with two different
orientations from two sub-arrays
oriented in different directions, or
unbalanced strings (for example: East
and West).
The dual-input sections with
independent MPPT enable a more
optimal energy harvesting condition.
The high-speed MPPT offers real-
time power tracking and improved
energy harvesting.
The flat efficiency curve ensures high-
efficiency at all output levels allowing
a consistent and stable performance
across the entire input voltage and
output power range.
The transformerless operation gives the
highest efficiency of up to 97.0 percent.
The wide input voltage range makes
the inverter suitable to low-power
installations with reduced string size.
This rugged, outdoor inverter has
been designed to be a completely
sealed unit, to withstand the harshest
environmental conditions.
Highlights:
Single-phase and three-phase output
grid connection
Wide input-voltage range for
increased stringing flexibility and
energy harvesting
The high-speed and precise MPPT
algorithm offers real-time power
tracking and improved energy
harvesting
Outdoor NEMA 4X rated enclosure
for unrestricted use under any
environmental conditions
Integrated DC disconnect switch
in compliance with international
Standards (-S Version)
2 ABB solar inverters | Product flyer for PVI-3.0/3.6/3.8/4.2-TL-OUTD
Technical data and typesType code PVI-3.0-OUTD-US PVI-3.6-OUTD-US PVI-3.8-OUTD-US PVI-4.2-OUTD-US
General specifications
Nominal output power 3000W 3600W3300
W3800W 4200W
Maximum output power wattage3000
W 33001
W33001
W3600
W40001
W40001
W3300
W42001
W42001
W4200
W46001
W46001
WRated grid AC voltage 208V 240V 277V 208V 240V 277V 208V 240V 277V 208V 240V 277VInput side (DC)Number of independent MPPT channels 2 2 2 2Maximum usable power for each channel 2000W 3000W 3000W 3000WAbsolute maximum voltage (Vmax) 600VStart-up voltage (Vstart) 200V (adj. 120-350V)Full power MPPT voltage range 160-530V 120-530V 140-530V 140-530VOperating MPPT voltage range Maximum current (Idcmax) for both MPPT in parallel
20A 32A 32A 32A
Maximum usable current per channel 10A 16A 16A 16AMaximum short circuit current limit per channel
12.5A 20.0A 20.0A 20.0A
Number of wire landing terminals per channel 2 pairsArray wiring termination Terminal block, pressure clamp, AWG20-AWG6Output side (AC)
Grid connection type1Ø/ 2W
Split- Ø/3W
1Ø/ 2W
1Ø/ 2W
Split- Ø/3W
1Ø/ 2W
1Ø/ 2W
Split- Ø/3W
1Ø/ 2W
1Ø/ 2W
Split- Ø/3W
1Ø/ 2W
Adjustable voltage range (Vmin-Vmax) (V)183- 228V
211- 264V
244- 304V
183- 228V
211- 264V
244- 304V
183- 228V
211- 264V
244- 304V
183-228V
211- 264V
244- 304V
Grid frequency 60HzAdjustable grid frequency range 57-60.5Hz
Maximum current (Iac,max) 14.5A 14.5A 12.0A 17.2A 16.0A 16.0A 16.0A 16.0A 16.0A 20.0A 20.0A 20.0A
Power factor > 0.995 (adjustable to ±0.8)Total harmonic distortion at rated power < 2%Grid wiring termination type Terminal block, Pressure clamp, AWG20-AWG6Input protection devicesReverse polarity protection YesOver-voltage protection type Varistor, 2 for each channelPV array ground fault detection Pre start-up R
ISO and dynamic GFDI (requires floating arrays)
Output protection devicesAnti-islanding protection Meets UL1741 / IEEE1547 requirementsOver-voltage protection type Varistor, 2 (L1 - L2 / L1 - G)Maximum AC OCPD rating 20A 20A 15A 25A 20A 20A 20A 20A 20A 25A 25A 25AEfficiencyMaximum efficiency 96.9% 97% 97% 97%CEC efficiency 96%Operating performanceNighttime consumption < 0.6W
RMS
Stand-by consumption < 8WRMS
CommunicationUser-interface 16 characters x 2 lines LCD displayRemote monitoring (1xRS485 incl.) VSN700 Data Logger (opt.), VSN300 Wifi Logger Card (opt.)EnvironmentalAmbient air operating temperature range -13°F to +140°F (-25°C to 60°C) with derating above 122°F (50°C)Ambient air storage temperature range -40°F to +176°F (-40°C to +80°C)Relative humidity 0-100% RH condensingAcoustic noise emission level < 50 db (A) @1mMaximum operating altitude without derating 6560ft (2000m)1. Capability enabled at nominal AC voltage and with sufficient DC power available.
Additional highlights- RS-485 communication interface
(for connection to laptop or datalogger)
- Available with the optional VSN300i ogger ard for ea and
a ordable wirele monitoring- ompliant with N 0 when
u ed with A Rapid Shutdowndevice
- ome tandard with Arc aultircuit nterruptor (A ) to compl
with N 0
A10
Product flyer for PVI-3.0/3.6/3.8/4.2-TL-OUTD | ABB solar inverters 3
Block diagram of PVI-3.0/3.6/3.8/4.2-TL-OUTD
Technical data and typesType code PVI-3.0-OUTD-US PVI-3.6-OUTD-US PVI-3.8-OUTD-US PVI-4.2-OUTD-US
Mechanical specificationsEnclosure rating NEMA 4XCooling Natural convectionDimensions H x W x D 33.8 x 12.8 x 8.7in (859 x 325 x 222mm)2
Weight <47.3lb (21.3kg)2
Shipping weight < 60lb (27.0kg)2
Mounting system Wall bracket
Conduit connections2
Trade size KOs (2ea x 1/2”) and (2ea x 1-1/4”, 3 places side, front, rear) Side: (2) plugged 3/4” openings, (2) Concentric KOs 3/4”, 1”
Back: (4) Concentric EKOs 3/4”, 1”DC switch rating (per contact) (A/V) 25/600Safety and ComplianceIsolation level Transformerless (floating array)
Safety and EMC standardUL1741, IEEE1547, IEEE1547.1, CSA-C22.2 N. 107.1-01, UL1998 UL 1699B, FCC Part
15 Class BSafety approval cCSAus
Regional Compliance Rule 21, HECO, NEC 2014 690.11, NEC 690.12 with ABB Rapid Shutdown deviceAvailable modelsWith DC switch, wiring box, arc fault detector and interrupter
PVI-3.0-OUTD-S-US-A
PVI-3.6-OUTD-S-US-A
PVI-3.8-OUTD-S-US-A
PVI-4.2-OUTD-S-US-A
2. When equipped with optional DC switch and wiring box.All data is subject to change without notice
IN1
IN2
+
-
+
-
-S VERSION
IN1
+
-
IN2
+
-
MPPT 2(DC/DC)
MPPT 1(DC/DC) BULK CAPS
INVERTER(DC/AC) LINE
FILTERGRID PARALLEL
RELAY
L1
L2
PE
RESIDUAL CURRENTDETECTION
DC/DCDSP
CONTR.
DC/ACDSP
CONTR.
μP
CONTROL CIRCUIT
RS485
+ T/R
- T/R
RTN
REMOTE CONTROL*
+ R
- R
ALARM
N.C
N.O
C
GROUNDFAULT
DETECTION
N
* Remote control function not available on -A version
IN1
IN2
+
-
+
-
DCAFDI
IN1.1(+)
IN1.2(+)
IN1.1(-)
IN1.2(-)
IN1
IN2
+
-
+
-
IN2.1(+)
IN2.2(+)
IN2.1(-)
IN2.2(-)
STANDARD VERSION
IN1
IN2
+
-
+
-
-A VERSION
IN1
IN2
+
-
+
-
5,00%
10,00%
15,00%
20,00%
25,00%
30,00%
35,00%
40,00%
45,00%
50,00%
55,00%
60,00%
65,00%
70,00%
75,00%
80,00%
85,00%
90,00%
95,00%
100,00%
215 250 300 345 400 480
[%]
of
Ra
ted
Po
we
r
MPPT Voltage [V]
97,0
96,6
96
94,8
94,4
95,2
94
93,6
93,2
92,8
92,4
92
91,6
95,6
97,0
96,4
96,4
96
95,2
96
95,2
96,2
96
94 94
92 92
92
91
92
93
94
95
96
97
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
y, %
200 Vdc
340 Vdc
480 Vdc
PVI-4.2-OUTD-US PVI-4.2-OUTD-US
FF0 002
DQD 507 Rev. 2012-05-22 Page 1
Certificate of Compliance Certificate: 2708406 Master Contract: 259813
Project: 2722409 Date Issued: April 24, 2014
Issued to: ABB, Inc. 16250 W. Glendale Drive New Berlin, WI 53151 USA
The products listed below are eligible to bear the CSA Mark shown with adjacent indicators 'C' and 'US' for Canada and US or with adjacent
indicator 'US' for US only or without either indicator for Canada only.
Issued by: Jocelyn Jens Product Group Coordinator
Authorized by: Lindsay Clark Operations Manager
PRODUCTS
CLASS 5311 09 - POWER SUPPLIES - Distributed Generation Power Systems Equipment CLASS 5311 89 - POWER SUPPLIES - Distributed Generation - Power Systems Equipment
- Certified to U.S. Standards
Utility Interactive Inverter, Models PVI-4.2-OUTD-US, PVI-3.8-OUTD-US, PVI-3.6-OUTD-US, PVI-3.0-OUTD-US, PVI-4.2-OUTD-S-US, PVI-3.8-OUTD-S-US, PVI-3.6-OUTD-S-US, PVI-3.0-OUTD-S-US, PVI-4.2-OUTD-S-US-A, PVI-3.8-OUTD-S-US-A, PVI-3.6-OUTD-S-US-A, PVI-3.0-OUTD-S-US-A, PVI-4.2-OUTD-US-W, PVI-3.8-OUTD-US-W, PVI-3.6-OUTD-US-W and PVI-3.0-OUTD-US-W; provided with two DC input channels, permanently connected, system ratings as follows:
Notes: 1. All above models in this series may include expansion board with wireless antennae option and will be
identified with model designation including “–Z” suffix.2. For details related to rating, size, configuration, etc. reference should be made to the CSA Certification
Record or the Certificate of Compliance Annex A.
A11
2 ABB solar inverters | Product flyer for RSD
Type code 2-String pass-through 2-String combined 4-String combined
PV source conductor input
Max input current (per string) 11.25A
Max input voltage 600VNumber of input strings 2 2 4Conductor size 14-8 AWGPV output conductors outputNumber of output circuits 2 1 2Conductor size 12-6 AWGDC disconnect N/A Yes YesControl powerPower consumption <5W, 24V/0.2A <2.5W, 24V/0.1A <5W, 24V/0.2AMaximum power conductor size 12 AWGE-stop button OptionalEnvironmentalMounting angle 0-90°Dimensions H x W x D 10.54“x8.54“x5.32“ (without mounting bracket)Weight 6lb 5.8lb 6.2lbOperating temperature range -25°C to +70°CEnclosure rating NEMA 4XCertifications UL1741:2010, FCC Part 15 Class BWarrantyStandard warranty 10 YearsAvailable modelsRapid shutdown kit RS2-2PN6-kit RS2-1CN6-kit RS4-2CN6-kitRapid shutdown rooftop box for 2-box system N/A RS2-1CN6 N/AOptional emergency stop 1SFA611821R1026Information in this document is subject to change without notice
< 10 ft.
+24V RSD power PV systemdisconnect
Utilitygrid
~
Rooftop 1
Rooftop 2
PV String 1
PV String 2
PV String 3
PV String 4
ABB rapidshutdown
PV output MPPT1
PV output MPPT2
ABB rapidshutdown
Rapid shutdown wiring diagram: 2-RSD system
Technical data and types
Two RS2-1CN6 boxes may be powered by one power supply. For PV systems requiring two RSD boxes order the
RS2-1CN6- kit and one RS2-1CN6 box.
Product flyer for RSD | ABB solar inverters 3
InverterDC disconnect
PV outputpositive
Rapid shutdown box Inverter / inverter switch-box
PV outputnegative
Outputterminalblocks
Controlpowersupply
IN 1+and 2+
Dischargecircuit
Localdisconnecting
means
Customer ACdisconnect
AC grid
RS2-1CN6 two strings in, one PV output
IN 1-and 2-
Inverter
DC disconnectRapid shutdown box Inverter / inverter switch-box
Outputterminalblocks
Controlpowersupply
In 1+and 2+
Dischargecircuit
Localdisconnecting means
Customer ACdisconnect
AC grid
RS4-2CN6 four strings in, two PV outputs
PV output 1positive
PV output 1negative
PV output 2positive
PV output 2negative
Outputterminalblocks
In 1-and 2-
In 3-and 4-
In 3-and 4-
Inverter
DC disconnectRapid shutdown box Inverter / inverter switch-box
Outputterminalblocks
Controlpowersupply
In 1+
In 1-
In 1+Discharge
circuit Customer ACdisconnect
AC grid
RS2-2PN6 two strings in, two strings out
Outputterminalblocks
PV string1positive
PV string 1negative
PV string 2positive
PV string 2negative
In 1-
In 2+
In 2-
Block diagram for rapid shut down models
This 2-string model combines the strings to one PV output circuit. The RS2-1CN6 includes a disconnect switch on the
front cover to disconnect the PV output conductors from the equipment down stream. Auxillary terminals are provided for
connecting an emergency stop button, if desired.
This 4-string model combines 2-strings together in two separate PV output circuits. The RS4-2CN6 includes a disconnect
switch on the front cover to disconnect the PV output conductors from the equipment downstream. Auxillary terminals are
provided for connecting an emergency stop button, if desired.
The RS2-2PN6 is a 2-string pass-through with no string combining and no local disconnecting means included. Auxillary
terminals are provided for connecting an emergency stop button, if desired.
A12
Certificate A .. ®
TUVRheinland
_ce_rt
_ifi
_,ca
_te
_n
_o_. -----11 CU 72150214 01 . \ · t--1---------------
License Holder: Power-One 3201 East Harbour Drive Phoenix AZ 85034 USA
Test report no.: USA-ZZ 31580190 001
Tested to: UL 1741:2010
Manufacturing Plant: ABB Inc. 16250 W Glendale Drive New Berlin WI 53151 USA
Client Reference: Bob White
CSA C22.2.107.l-01 (R2006)
Certified Product: Rapid Shut Down Device License Fee - Units
Model Designation: 1) RS4-2CN6, 2) RS2-2PN6, 3) RS2-1CN6 (trademark: ABB)
Rated Voltage: Rated Current: Protection Class: Max. Short-Circuit
DC 90-580V lOA max. (per channel) I Current (input/output): 1) ,3)
2) 11.25/22.5A 22. SA
contd. Special Remarks: To be installed according to the licensee's installation instructions. Also evaluated to NFPA 70: 2014, Article 690.12.
Appendix: 1, 1-6
Licensed Test mark:
I TUVRheinland
I
C - us
7
7
Date of Issue (day/mo/yr) 13/04/2015
TUV Rhelnland of Nonh America, Inc., 12 Commerce Road, Newtown, CT 06470, Tel (203) 426-0888 Fax (203) 426-4009
Certificate ---------i CU, 721502.14 02 Certificate no.
I
License Holder: Power-One 3201 East Harbour Drive Phoenix AZ 85034 USA
Manufacturing Plant: ABB Inc. 16250 W Glendale Drive New Berlin WI 53151 USA
Test report no.: USA-ZZ 31580190 001 Client Reference: Bob White
Tested to: UL 1741:2010 CSA C22.2.107.l-01 (R2006)
Certified Product: Rapid Shut Down Device
contd.
Output Current:
Rated Ambient Temperature: Enclosure Index:
Licensed Test mark:
1) 20A max. (per channel)2) 1 OA max. (per channe 1)
3) 20A max.-25 ° C to +7o 0 cType 4X
A.. ® TUVRheinland
License Fee - Units
Date of Issue (day/mo/yr) 13/04/2015
TUV Rhelnland of North America, Inc., 12 Commerce Road, Newtown, CT 06470, Tel (203) 426-0888 Fax (203) 426-4009
A13
Tech Brief
The UFO family of components eliminates the need for separate grounding hardware by bonding solar modules directly to IronRidge XR Rails. All system types that feature the UFO family—Flush Mount, Tilt Mount and Ground Mount—are fully listed to the UL 2703 standard.
UFO hardware forms secure electrical bonds with both the module and the rail, resulting in many parallel grounding paths throughout the system. This leads to safer and more reliable installations.
UFO Family of Components
The UFO securely bonds solar modules to XR Rails. It comes assembled and lubricated, and
he gore
The UFO securely bRails. It comes asse
The Stopper Sleeve snaps onto the UFO, converting it into a bonded end clamp.
Each Bonded Splice uses self-drilling screws to form a secure connection. No bonding strap needed.
The bonding bolt attaches and bonds the L-foot to the rail. It is installed with the same socket as the rest of the system.
A single Grounding Lug connects an entire row of PV modules to the grounding conductor.
Each Bonded Splice uses lf d illi f
The IronRidge Flush Mount, Tilt Mount, and Ground Mount Systems have been listed to UL 2703 by Intertek Group plc.
UL 2703 is the standard for evaluating solar mounting systems. It ensures these devices will maintain strong electrical and mechanical connections over an extended period of time in extreme outdoor environments.
Tech Brief
XR Rails XR1000 Only
UFO/Stopper
Bonded Splice N/A
Grounding Lugs 1 per Row 1 per Row 1 per Array
Microinverters & Power
Optimizers
Enphase - M250-72, M250-60, M215-60, C250-72Darfon - MIG240, MIG300, G320, G640
SolarEdge - P300, P320, P400, P405, P600, P700, P730
Fire Rating Class A Class A N/A
ModulesTested or Evaluated with over 400 Framed Modules
Refer to installation manuals for a detailed list.
Approved Enphase microinverters can provide equipment grounding of IronRidge systems, eliminating the need for
same rail and connected to the same Engage cable is required. Refer to installation manuals for additional details.
A14
FLUSH MOUNT INSTALLATION MANUAL - 2© 2016 IRONRIDGE, INC. VERSION 1.20
RATINGS
MARKINGS
#5003288
#5004376
#5003320
UL 2703 LISTED
•
••••
CLASS A SYSTEM FIRE RATING PER UL 1703
•
• Any module-to-roof gap is permitted, with no perimeter guarding required. This rating is applicable with any third-partyattachment.
•
STRUCTURAL CERTIFICATION
•
FLUSH MOUNT INSTALLATION MANUAL - 9© 2016 IRONRIDGE, INC. VERSION 1.20
MODULE COMPATIBILITY
MAKE MODELS
Astronergy Solar
Canadian Solar
ET Solar
GigaWatt Solar
Hanwha Solarcan be blank or B.
Hyundai
Itek
Panasonic
Phono Solar
Prism Solar
REC Solar
RenesolaAbv-b, Bb, Bb-b, Bbh, Bbh-b, Bbv, Bbv-b, Db, or Db-b.
Renogy
Silfab
SolarWorld
Stion
SunEdison
Suniva
Sunpower
Sunpreme
Suntech
Trina
Winaico
A15
5224 South 39th Street, Phoenix, Arizona 85040 tel: (602) 438-2500 fax: (602) 438-2505 ROC#291316 www.smleng.com
Starling Madison Lofquist, Inc. Consulting Structural and Forensic Engineers
IronRidge December 18, 2014 1495 Zephyr Ave Page 1 of 20 Hayward, CA 94544
Attn: Mr. David F. Taggart, Vice President Products
Subject: IronRidge XR10 Rail, Roof Flush Mounting System – Structural Analysis
Dear Sir:
We have analyzed the IronRidge XR10 Rail for the subject solar module support system and determined that, for the configurations and criteria described below, it is in compliance with the applicable sections of the following Reference Documents:
Codes: ASCE/SEI 7-10 Min. Design Loads for Buildings & Other Structures California Building Code 2012 Edition
Other: AC428, Acceptance Criteria for Modular Framing Systems Used to Support PV Modules, dated Effective November 1, 2012 by ICC-ES Aluminum Design Manual, 2010 Edition
The IronRidge XR10 Rail is an extruded aluminum section with an overall depth of 1.75 in. and a net area of 0.363 sq.in. The rails are used to support solar modules, typically, on the roof of a building. See Exhibit A – attached. The rails are clamped to aluminum angle brackets that are either attached directly to the roof framing or attached to a stand that is screwed to the roof framing. The rails are mounted across the slope with a small clearance (flush mounting) to the underlying roof structure. The installed solar modules are at the same slope as the underlying roof structure.
All loads are transferred to the roof framing through the angle brackets by simple bi-axial flexure of the rails. The maximum span of the rails is governed by either the mid-span flexural stresses or the deflection requirement that the rail not come into contact with the roof.
The effect of seismic loads (for all design categories A-F) have been determined to be less than the effect due to wind loads in all load conditions and combinations. Therefore, the maximum allowable spans for common load cases are shown in the tables below. Tables 1A-9A are for modules with a maximum long dimension of 67.5 inches and Tables 1B-9B are for modules with a maximum long dimension of 78.5 inches.
IronRidge December 18, 2014 Mr. David F. Taggart Page 5 of 20 IronRidge XR10 Rail, Roof Flush Mounting System – Structural Analysis
Starling Madison Lofquist, Inc. Consulting Structural and Forensic Engineers
- 5 -
Table 4A MAXIMUM SPANS (in) Roof Slope 7° to 27° Wind Zone 1 (67.5" Max Module Length)XR10Rail
WindSpeed Ground Snow Load
Exposure mph 0 psf 10psf
20psf
30psf
40psf
50psf
60psf
70psf
80psf
90psf
Category B
100 75 65 55 49 43 39 35 33 31 29 105 75 65 55 49 43 39 35 33 31 29 110 75 65 55 49 43 39 35 33 31 29 120 75 65 55 49 43 39 35 33 31 29 130 75 65 55 49 43 39 35 33 31 29 140 71 65 55 49 43 39 35 33 31 29 150 66 65 55 49 43 39 35 33 31 29 160 62 62 54 48 43 39 35 33 31 29 170 59 59 53 47 43 39 35 33 31 29
Category C
100 75 65 55 49 43 39 35 33 31 29 105 75 65 55 49 43 39 35 33 31 29 110 75 65 55 49 43 39 35 33 31 29 120 70 65 55 49 43 39 35 33 31 29 130 65 64 54 48 43 39 35 33 31 29 140 60 60 53 48 43 39 35 33 31 29 150 56 56 52 47 43 39 35 33 31 29 160 53 53 51 46 42 39 35 33 31 29 170 50 50 50 45 41 38 35 33 31 29
Category D
100 75 65 55 49 43 39 35 33 31 29 105 73 65 55 49 43 39 35 33 31 29 110 70 65 55 49 43 39 35 33 31 29 120 64 64 54 48 43 39 35 33 31 29 130 60 60 53 47 43 39 35 33 31 29 140 55 55 52 46 42 39 35 33 31 29 150 52 52 50 46 42 39 35 33 31 29 160 49 49 49 45 41 38 35 33 31 29 170 46 46 46 44 40 37 35 33 31 29
Notes – see page 20
A16
IronRidge December 18, 2014 Mr. David F. Taggart Page 6 of 20 IronRidge XR10 Rail, Roof Flush Mounting System – Structural Analysis
Starling Madison Lofquist, Inc. Consulting Structural and Forensic Engineers
- 6 -
Table 5A MAXIMUM SPANS (in) Roof Slope 7° to 27° Wind Zone 2 (67.5" Max Module Length)
XR10Rail
WindSpeed Ground Snow Load
Exposure mph 0 psf 10psf
20psf
30psf
40psf
50psf
60psf
70psf
80psf
90psf
Category B
100 72 65 55 49 43 39 35 33 31 29 105 69 65 55 49 43 39 35 33 31 29 110 66 65 55 49 43 39 35 33 31 29 120 60 60 55 49 43 39 35 33 31 29 130 56 56 55 49 43 39 35 33 31 29 140 52 52 52 49 43 39 35 33 31 29 150 49 49 49 49 43 39 35 33 31 29 160 46 46 46 46 43 39 35 33 31 29 170 43 43 43 43 43 39 35 33 31 29
Category C
100 61 61 55 49 43 39 35 33 31 29 105 58 58 55 49 43 39 35 33 31 29 110 56 56 55 49 43 39 35 33 31 29 120 51 51 51 49 43 39 35 33 31 29 130 48 48 48 48 43 39 35 33 31 29 140 44 44 44 44 43 39 35 33 31 29 150 41 41 41 41 41 39 35 33 31 29 160 39 39 39 39 39 39 35 33 31 29 170 36 36 36 36 36 36 35 33 31 29
Category D
100 56 56 55 49 43 39 35 33 31 29 105 54 54 54 49 43 39 35 33 31 29 110 52 52 52 49 43 39 35 33 31 29 120 47 47 47 47 43 39 35 33 31 29 130 44 44 44 44 43 39 35 33 31 29 140 41 41 41 41 41 39 35 33 31 29 150 38 38 38 38 38 38 35 33 31 29 160 36 36 36 36 36 36 35 33 31 29 170 33 33 33 33 33 33 33 33 31 29
Notes – see page 20
IronRidge December 18, 2014 Mr. David F. Taggart Page 7 of 20 IronRidge XR10 Rail, Roof Flush Mounting System – Structural Analysis
Starling Madison Lofquist, Inc. Consulting Structural and Forensic Engineers
- 7 -
Table 6A MAXIMUM SPANS (in) Roof Slope 7° to 27° Wind Zone 3 (67.5" Max Module Length)
XR10Rail
WindSpeed Ground Snow Load
Exposure mph 0 psf 10psf
20psf
30psf
40psf
50psf
60psf
70psf
80psf
90psf
Category B
100 59 59 55 49 43 39 35 33 31 29 105 56 56 55 49 43 39 35 33 31 29 110 54 54 54 49 43 39 35 33 31 29 120 49 49 49 49 43 39 35 33 31 29 130 46 46 46 46 43 39 35 33 31 29 140 42 42 42 42 42 39 35 33 31 29 150 40 40 40 40 40 39 35 33 31 29 160 37 37 37 37 37 37 35 33 31 29 170 35 35 35 35 35 35 35 33 31 29
Category C
100 50 50 50 49 43 39 35 33 31 29 105 48 48 48 48 43 39 35 33 31 29 110 45 45 45 45 43 39 35 33 31 29 120 42 42 42 42 42 39 35 33 31 29 130 39 39 39 39 39 39 35 33 31 29 140 36 36 36 36 36 36 35 33 31 29 150 33 33 33 33 33 33 33 33 31 29 160 31 31 31 31 31 31 31 31 31 29 170 29 29 29 29 29 29 29 29 29 29
Category D
100 46 46 46 46 43 39 35 33 31 29 105 44 44 44 44 43 39 35 33 31 29 110 42 42 42 42 42 39 35 33 31 29 120 38 38 38 38 38 38 35 33 31 29 130 35 35 35 35 35 35 35 33 31 29 140 33 33 33 33 33 33 33 33 31 29 150 31 31 31 31 31 31 31 31 31 29 160 29 29 29 29 29 29 29 29 29 29 170 27 27 27 27 27 27 27 27 27 27
Notes – see page 20
A17
�
8431 Murphy Drive Middleton, WI 53562 USA
Telephone: 608.836.4400 Facsimile: 608.831.9279 www.intertek.com
����������� �� �� � �����
�
����������� ��������� ��������������������� � ���������� ���������������������� � �� ���������� ��� ������� � �������� ������� ���� � ���������������� ������������� ��������� ��� �� ��� ������������� ������� ���������� ���� � ��������������������� �� �������� � �� ��� ���� �� �������� ���������������� �� ���������� ����������� �������������������������������� ��������� ���������� �����!���� �������� ������ ���"��� ������ �������������� ��� ������ ���������� ������#��������� ����� � ����������������� ��������� �������������� ������ ��� ��� �� ����� ���� ������ ������������� ��� ����������������� ��������� � ��������������� ��������� �� $������ �������� ������������� ���������� ������������� ������ �� ���������� �� ��$������ ���������������� �������� ����������� ������� �� � ����� ���� ������ �������������������������������������� � ����� ���� �����������
�GFT-OP-11a (24-MAR-2014)�
�
����������������� ���������� � ����� ������������������������ ��������������������� ˇˇ ˆˇ ˙ˆ ˝˛ ˇ˙ �������������
����������� �������������������������������� ���������������������������� ������������������������������������� ������� ������������ �������������������������������������������
������������� ������!� ° ������� ����!��ˇ˙ "#�$�%&' �() �!�* �' + � � �,( ��" ˙ #���-�(��
"�������#���������!� .��&�������'�����+��&�/�������!��
$���%� �"���������&����������!�
.���, ������������������������0.��&������1�'��������2!��,�����(�.���������3� �4�+����%���%%����������+&��������5'%��ˇ �˝�����6 ��������%&���)�������������!��,�����(�.���������3� �����%����%���%%����������+��&�5'%�ˇ �˝�����6 ��������%&���)�������������!��5������+ ��&���#7���%�1���������8��+�����&��8�������&��������3���������&����3���)����2 �%� ��&�����������&����'���������8�����������������'���%�����+���8'��&�����3���� �������������������������!�� ��%� ����� ����������� �9���!��5&��� ����������%%����8���+��&���'�° ��������� �6:��%� �'� ��3����&�!��
'����!� ° ��������.��&������+��&�/ ˜ �˜�����(�������!� ° ��������.��&������$�������)�����!� -4��;˛6 �1���������#!������ˇ# !62���������3����3��'����������'����� �����������) ���� �
,���%����������������) ���� �����< ����4���3� �-���+ ��&��.���0�������&���)������������������������ �.������������������=��!�˝> ��˛ ˇ #�$� �������%�-4ˇ;˛ 6�5&����������������� �)!�ˇ> �˝˛ ˇ ˙ �1��������6ˇ !̋ 2���������3����3��'�3��.���0�������&���)������������������������!�
*��� �����������%�+ ���!� ������?�5��������� ) ����� ( ����!�>˙ 6ˇ ��%&'���)����������� �@���#6#A��
#���� �,��!� ˛>ˆ ˝; ˆ˝˛ ˇ�����˛ 6ˆˇ ; ˆ˝˛ˇ #�,���$��������������!� ˇ ˛ˇ; A"6˙6 ���0��ˇ ˇ �ˇ˛ˇ ;A "6˙ 6�°̆ 0̨ ˛ˇ � ��˛ˇ" ˇ#" ;>���0˛˛ ��B �ˇ ˛ˇ" ""˙ "˝ ���0˛˛ˇ � ˇ 0� ˇ !�,������� �������������� ����� ���������������������������������������-�������������������,������������������������������������������������ ��������� � � � �
&�����������!� ,& ���$��8��&� $����������!� ,&��� �����,����!� 5��&�������°° �. ��������������� ,����!����������������� 5��&�������� �.���������������� � � �)�%�����!�������� � )�%�����!������ �#��!������������������� ˛#ˆ˝#ˆ ˝˛ˇA � #��!�� ˛#ˆ˝#ˆ ˝˛ˇA �
�
A18
Sources: American Wood Council, NDS 2005, Table 11.2 A, 11.3.2 A
Notes: 1) Thread must be embedded in a rafter or other structural roof member. 2) See NDS Table 11.5.1C for required edge distances.
Lag pull-out (withdrawal) capacities (lbs) in typical lumber:
.50 798 266
.46 705
.46 705
212
.46 705
.55 921
.42 615 205
.50 798 266
E-Mount Lag QMSE - LAG
Sep-2014, Rev 1BI 7.2.3-31
1st course
3rd course
2nd course
You are now ready for the rack of your
choice. Follow all the directions of
the rack manufacturer as well as the
module manufacturer.
All roofi ng manufacturers’ written
instructions must also be followed
by anyone modifying a roof system.
Consult the roof manufacturer's specs
and instructions prior to touching
the roof.
Using drill with 7/32" bit, drill pilot hole into roof and rafter, taking care to drill square to the roof. Do not use mount as a drill guide. Drill should be ‘long style bit’, aka ‘aircraft extension bit’ to drill a 1¾ " deep hole into rafter.
Clean off any sawdust, and fi ll hole with sealant compatible with roofi ng materials.
Slide the fl ashing into position. Insert the rubber plug into the QBlock cavity.
Slide the washer and the L-foot (not included) onto the lag screw.
Sep-2014, Rev 1
E-Mount Lag Installation InstructionsInstallation Tools Required: tape measure, roofi ng bar, chalk line, stud fi nder, caulking gun, sealant compatible with roofi ng materials, drill with 7/32" long-style bit, drill or impact gun with 1/2" socket.
Locate, choose, and mark centers of rafters to be mounted. Select the courses of shingles where mounts will be placed.
Carefully lift composition roof shingle with roofi ng bar, just above placement of mount. Remove nails as required. See "Proper Flashing Placement" on next page.
Insert fl ashing between 1st and 2nd course. Slide up so top edge of fl ashing is at least 3/4" higher than the drip edge of the 3rd course and lower fl ashing edge is above the drip edge of 1st course. Mark center for drilling.
Using a 1/2 inch socket on an impact gun drive the lag screw until the QBlock stops rotating easily. DO NOT over-torque.
BI 7.2.3-31
WARNING: Quick Mount PV products are NOT designed for and should NOT be used to anchor fall protection equipment.
A19
LGate 120 RESIDENTIAL SOLAR MONITORING SOLUTION
Product Datasheet
The LGate 120 is a single-phase electronic watt-hour meter for remote monitoring of solar photovoltaic systems. It features a smart communications module to automatically transmit meter data over cellular or Ethernet networks allowing system owners and operators to easily manage distributed solar assets.
The LGate 120 combines a revenue-grade, solid-state power meter with an advanced communications gateway. These components work in conjunction to remotely monitor the performance of residential solar energy installation regardless of panel or inverter type. The LGate 120 is a one-piece completely under glass meter which installs easily using a standard socket base. Performance data is uploaded in near real-time to the Locus Energy SolarOS monitoring platform which provides a suite of tools and analytics for asset managers.
DATA COLLECTION
AC energy data is collected by the meter and passed to the communications module. Additional system performance data can be collected directly from meteorological sensors and supported inverters via available RS-485 or Zigbee connections. All data is stored in non-volatile memory and then automatically uploaded to the SolarOS and SolarNOC platforms.
NETWORK CONNECTIVITY
The communications gateway inside the LGate 120 supports plug and play connectivity through a cellular or available Ethernet network connection. Once the unit is installed and powered on, it will immediately begin transmitting data without any configuration. For maximum reliability, the communications gateway will automatically route uploads between the wireless and wired connections if either of the networks are unavailable.
FEATURES
• ANSI C12.20 power meter• RS-485 and Zigbee inputs• GSM cellular or Ethernet connectivity• Over the air firmware updates
• Easy, low cost installation• Doesn’t require entrance into the building• Plug and play activation• LCD display
DATALOGGER
Processor ARM9 embedded CPU
OS Custom version of Linux 2.6, OTA firmware updates
Memory 128 MB RAM
Display LCD screen
SPECIFICATIONS
PHYSICAL
Enclosure NEMA 3R Type
Weight 8 oz
Dimensions 6.95” x 6.5” x 7.3”
Environment -20 to 60C, all-weather
Warranty 5 year limited warranty
DIAGRAM – TYPICAL CONFIGURATION
DIMENSIONS
Shielded CAT5
LEGEND
6.95 in
6.31 in
5.46 in
6.00 in
7.30 in
SOCKET METER
COMPLIANCE
ANSI 12.20 class 0.2%
FCC Part 15B
PTCRB
AT&T Carrier Compliance
PV ARRAY
ELECTRICALSERVICE
INVERTER(S)
INTERNET
LGATE 120
METER BASE METER MODULELOCUS ENERGYCOMM MODULE
POWER
Accuracy ANSI 12.20 (Class 0.2%)
Voltage Inputs 120 - 480 VAC
Max. Current Input 200 A
Service Type Single phase , 60 Hz
Socket Type 2S
COMMUNICATION INTERFACE OPTIONS
Model Number LGate120-3Gx LGate120-3Gy LGate120-3Gz
Cellular - 3G GSM
RS-485 2 and 4 wire
Modbus
Zigbee
Ethernet RJ-45 10/100, DHCP/Static
A20
125 & 200 Amp
011 (closed) U204 (open)
Single M
eter Sockets
Without B
ypass
Data subject to change without notice. Consult local utility for area acceptance. All dimensions are in inches.
Single Meter Sockets - Without Bypass
Meter Mounting Equipment5
Part/UPC Catalog Amp Service ConnectionsNumber Number Rating Jaws Type Access Line Load Neutral
78205142000 011 125 4 1Ø/3W OH/UG #14 - 2/0 #14 - 2/0 #14 - 2/078205142040 011 F 125 4 1Ø/3W OH/UG #14 - 2/0 #14 - 2/0 #14 - 2/078205142045 011 MS73 125 4 1Ø/3W OH/UG #14 - 2/0 #14 - 2/0 #14 - 2/078205142050 011 SF 125 4 1Ø/3W OH/UG #14 - 2/0 #14 - 2/0 #14 - 2/078205144030 927 100 7 3Ø/4W OH/UG #14 - 1/0 #14 - 1/0 #14 - 2/078205156000 204 200 4 1Ø/3W OH #6 - 250MCM #6 - 250MCM #6 - 350MCM78205156020 204 F 200 4 1Ø/3W OH #6 - 250MCM #6 - 250MCM #6 - 350MCM78205156030 204 F MS73 200 4 1Ø/3W OH #6 - 250MCM #6 - 250MCM #6 - 350MCM78205156040 204 MS68 200 4 1Ø/3W OH #6 - 250MCM #6 - 250MCM #6 - 350MCM78205156035 204 MS68A 200 4 1Ø/3W OH #6 - 250MCM #6 - 250MCM #6 - 350MCM78205108490 204 MS73 200 4 1Ø/3W OH #6 - 250MCM #6 - 250MCM #6 - 350MCM78205156005 U204 200 4 1Ø/3W UG #6 - 250MCM #6 - 250MCM #6 - 350MCM78205156045 U204 F 200 4 1Ø/3W UG #6 - 250MCM #6 - 250MCM #6 - 350MCM78205156060 U204 F MS73 200 4 1Ø/3W UG #6 - 250MCM #6 - 250MCM #6 - 350MCM78205156070 U204 MS73 200 4 1Ø/3W UG #6 - 250MCM #6 - 250MCM #6 - 350MCM78205156140 U207 200 7 3Ø/4W OH/UG #6 - 250MCM #6 - 250MCM #6 - 250MCM78205156170 U207 F 200 7 3Ø/4W UG #6 - 250MCM #6 - 250MCM #6 - 250MCM78205156180 U207 MS73 200 7 3Ø/4W OH/UG #6 - 250MCM #6 - 250MCM #6 - 250MCM
Part/UPC Catalog Overall Dimensions Top KnockoutNumber Number Height Width Depth Provision Layout
78205142000 011 12” 8” 45/8” AW Hub Fig. 178205142040 011 F 12” 8” 45/8” 2” max KO Fig. 178205142045 011 MS73 12” 8” 45/8” AW Hub Fig. 178205142050 011 SF 12” 8” 45/8” 2” max KO Fig. 178205144030 927 17” 8” 45/8” AW Hub Fig. 178205156000 204 15” 8” 45/8” AW Hub Fig. 278205156020 204 F 15” 8” 6” 2” max KO Fig. 278205156030 204 F MS73 15” 8” 6” 2” max KO Fig. 278205156040 204 MS68 15” 8” 45/8” AW / 2” Hub Fig. 278205156035 204 MS68A 15” 8” 45/8” AW / 2” Hub Fig. 278205108490 204 MS73 15” 8” 45/8” None Fig. 278205156005 U204 15” 12” 45/8” None Fig. 378205156045 U204 F 15” 12” 6” (2) 2” max KO Fig. 378205156060 U204 F MS73 15” 12” 6” None Fig. 378205156070 U204 MS73 15” 12” 45/8” None Fig. 378205156140 U207 18” 12” 5” AW Hub Fig. 478205156170 U207 F 18” 12” 5” 21/2” max KO Fig. 478205156180 U207 MS73 18” 12” 5” AW Hub Fig. 4
Application• Single meter position• Receive ANSI C12.10 watthour meters• Surface or flush mount (see chart)
Construction• Ring type• NEMA Type 3R• ANSI 61 gray E-coat finish• Aluminum snap ring included
Standards Accessories• UL 414 Listed • 5th Jaw Kit - 50365• ANSI C12.7 • 200A Triplex Ground - ETB200
• AW Hub
AIC Note:For short circuit currentratings see page 131.
Fig. 1
Fig. 3
Top Provision
Top Provision
Fig. 2
Fig. 4
Knockouts - Conduit Sizes
1W = 1⁄4"1A = 1⁄2"2A = 1⁄2" - 1⁄4"4F = 2” - 11⁄2" - 11⁄4" - 1"4G = 21⁄2" - 2” - 11⁄2" - 11⁄4"Top Provision = See Chart
Knockout Layouts
125 & 200 Amp
Sin
gle
Met
er S
ocke
ts
Wit
hout
Byp
ass
Data subject to change without notice. Consult local utility for area acceptance. All dimensions are in inches.
Single Meter Sockets - Without Bypass
6Meter Mounting Equipment
2A
Style # Suffixes
011 F - Flush Mount(U) 204 MS68 - 2” Conduit Hub(U) 207 MS68A - MS73 + MS68927 MS73 - AL Screw Type Ring
SF - Semi Flush MountSS - Stainless Steel
Top ProvisionTop Provision
1A
4F
4F 4Fbothsides
1W
4F
4G
4G
4G
4G
4G4G
4F4F
bothsides
4Gbothsides
1A
4F
4F
4Fbothsides
A21
Locus Energy, LLC www.locusenergy.com
October 22nd, 2013
This letter is to certify that the LGate 120 and LGate 320 are communication boards built into the Vision Meter 2S CL200 and 16S CL320 socket meters, respectively. Each of these meters was certified to the ANSI C12.20 (class 0.2%) standard by Underwriters Laboratory on June 7, 2013 as part of the Vision Meter Family (Project Number 12CA71134, Job Number 1001541515, and Report Number R12CA71134-ANSI).
ANSI C12.20 is currently recognized as the industry standard for electrical socket meters in both utility and PV monitoring applications. These tests cover both meter accuracy as well as several safety standards including electrical and environmental safety, as well as resistance to various types of mechanical shock. As electrical socket meters are generally installed and maintained by trained and certified professionals, rather than consumers, they do not fit the typical criteria for additional types of UL or IEC certification.
If you have any further questions regarding the product certification of any Locus Energy LGate-branded device, please contact us at support@locusenergy.com.
The Locus Energy Team
A22