See also MTL2000 approvals, maximum cable parameters, dimensions and ordering information SPECIFICATION See also ‘Common specification’ Number of channels One, fully floating Location of load Zone 0, IIC, T4–T6 hazardous area if suitably certified Div 1, Group A hazardous location if suitably certified Input and output signal range 4 to 20mA dc Input resistance 200(4V at 20mA) Maximum load resistance 800(16V at 20mA) Output resistance >1MInput and output circuit ripple <100μA peak-to-peak Transfer accuracy at 20°C Better than 20μA Temperature drift <1μA/°C Response time Settles within 200μA of final value after 200ms Power supply 240V ac nominal, 180–260V, 48–65Hz 120V ac nominal, 90–130V, 48–65Hz Power consumption 5VA Ambient temperature limits –20 to +50°C close packed –20 to +60°C at least 5mm apart Safety description 28V, 300, 93mA FM maximum entity parameters V oc = 28Vdc, I sc = 93mA, C a = 0.13μF, L a = 4.2mH This unit may show degraded immunity performance under some EMC test conditions – refer to supplementary specification SUP2442B for further details. The MTL2442B isolates and passes on a 4/20mA signal from a safe- area controller to drive a hazardous-area load such as a current-to- pressure (I/P) converter, a position actuator, or an electrically-driven valve, etc. Input and output circuits float independently to ensure compatibility with all types of drive instrumentation and permit the use of earthed or poorly insulated loads. In conjunction with an MTL2441B repeater power supply, the unit can be used to pass measurement or control signals through a hazardous area between two safe areas. The MTL2442B supersedes the MTL2442 but is designed for 240/120V ac supplies only. For a 24V dc powered model refer to the MTL5045. MTL2442B 4/20mA ISOLATING DRIVER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 I P 4/20mA Input 4/20mA + L N Note: MTL5045 is recommended for applications using 24V dc supplies Hazardous area Safe area Sept 2002 EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283 AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899 ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997 E-mail: [email protected] Web site: www.mtl-inst.com

Transcript of MTL2442B 4/20mA Hazardous area Safe area ISOLATING · PDF fileSee also MTL2000 approvals,...

See also MTL2000 approvals, maximum cable parameters, dimensions andordering information

SPECIFICATIONSee also ‘Common specification’

Number of channelsOne, fully floating

Location of loadZone 0, IIC, T4–T6 hazardous area if suitably certifiedDiv 1, Group A hazardous location if suitably certified

Input and output signal range4 to 20mA dc

Input resistance≤200Ω (4V at 20mA)

Maximum load resistance800Ω(16V at 20mA)

Output resistance>1MΩ

Input and output circuit ripple<100µA peak-to-peak

Transfer accuracy at 20°CBetter than 20µA

Temperature drift<1µA/°C

Response timeSettles within 200µA of final value after 200ms

Power supply240V ac nominal, 180–260V, 48–65Hz120V ac nominal, 90–130V, 48–65Hz

Power consumption5VA

Ambient temperature limits–20 to +50°C close packed–20 to +60°C at least 5mm apart

Safety description28V, 300Ω, 93mA

FM maximum entity parametersVoc = 28Vdc, Isc = 93mA, Ca = 0.13µF, La = 4.2mH

This unit may show degraded immunity performance under some EMCtest conditions – refer to supplementary specification SUP2442B forfurther details.

The MTL2442B isolates and passes on a 4/20mA signal from a safe-area controller to drive a hazardous-area load such as a current-to-pressure (I/P) converter, a position actuator, or an electrically-drivenvalve, etc. Input and output circuits float independently to ensurecompatibility with all types of drive instrumentation and permit the useof earthed or poorly insulated loads. In conjunction with anMTL2441B repeater power supply, the unit can be used to passmeasurement or control signals through a hazardous area betweentwo safe areas. The MTL2442B supersedes the MTL2442 but isdesigned for 240/120V ac supplies only. For a 24V dc poweredmodel refer to the MTL5045.

MTL2442B 4/20mA ISOLATING DRIVER

12345678

910111213141516

_I

P 4/20mA Input4/20mA+

– L

N

Note: MTL5045 is recommended for applications using 24V dc supplies