DataSite Product Profile - Oil & Gas Industry -...
Click here to load reader
Transcript of DataSite Product Profile - Oil & Gas Industry -...
Product Profile
Allen-Bradley DataSite™ RTU and Electronic Flow Meter
Oil and Gas Industry
OverviewWhen you need a rugged Remote Terminal Unit (RTU), the Allen-BradleyDataSite™ controller from Rockwell Automation is an excellent technology for service in harsh and extreme industrial environments likeoil, gas, pipeline, electrical and industrial combustion applications. It isideal for applications that require wide temperature ratings and lowpower consumption, and applications that are remote and powered bysolar cells or wind power. Electronic flow meter versions of DataSite incorporate AGA 3, AGA 7, and AGA 8 algorithms for computation of natural gas flow, making it well-suited for remote site natural gas well-head monitoring.
You also have the option to purchase the DataSiteas a configured panel in a rugged NEMA 4X enclosure, which can be wall or pipe-mounted. Takeadvantage of the standardized design with multipleoptions such as an operator interface, wireless radiomodems (three standard options, including antenna and cable accessories or the option to useyour own) and a 12V DC or 24V DC system configuration.
Help reduce your leadtime and engineering costs with our standardproduct. Program with industry leading RTU software, ISaGRAF, asoftware environment designed to facilitate the task of automationthroughout the life cycle of a system, from system design tocommissioning, operation, and maintenance. The developmentworkbench is the entry point for ISaGRAF and provides powerful, easy-to-use graphical and textual editors, such as docking toolbars,resizeable split windows, drag-and-drop and cut-and-paste.
DataSite Features� Advanced 32-bit processor with
embedded real-time multi-taskoperating system (RTOS)
� I/O: 8 analog inputs (2 with point-to-point HART interface), 2 analog out, 8discrete inputs, 4 discrete outputs, 3pulse inputs
� Communication Options: EmbeddedEthernet, two serial ports(RS232/RS485) and one HART multi-drop interface; native protocolsinclude Modbus RTU, Modbus ASCII,and Modbus TCP
� 6M FLASH, 1MRAM and 32KFerroelectric RAM for long termstorage of configured parameters
� HiBeam Technology: allows theDataSite to act as a web and event-based data server. HiBeam also hastools for interfacing with yourcontroller-based data through astandard web browser. Display devicedata and act on the controller dataremotely over the Internet
DataSite Configured Panel � Standardized design with multiple
options to meet your applicationneeds and help reduce your leadtime
� Multiple radio options make it easierto integrate into your system
� UL Listed, Class I, Div. 2., Groups A, B,C and D
www.klinkmann.com6 / 2011
Electronic Flow Meter RTU*
With 0...10Vdc Analog Inputs 1758-FLO301 (AGA 3**, 7, 8 calculations) 1758-RTU201
With 4...20mA Analog Inputs 1758-FLO302 (AGA 3**, 7, 8 calculations) 1758-RTU202
Processor 32-bit ARM processor, 3MHz clock frequency, integrated watchdog timer
Memory 2M (program Flash) + 4M (data Flash) + 1M (data SRAM) +32K FRAM
Non-volatile RAM With no power, the Flash storage retains contents for 10 years
Operating System ISaGRAF with online editing capability, IEC61131 and IEC 61499 compliant
Power Input 12V dc, 1.2W nominal power consumption, <1.0W in sleep mode (configurable)
Analog Inputs (6) 16-bit, accuracy +/- 0.1% of full scale at 25º CInput Impedance: 100k Ω for 0...10V dc, 170 Ω for 4...20 mA
Analog Inputs with HART Point-to-Point Interface (2) Two 16-bit analog input channels with HART point-to-point interface
Analog Outputs (2)4...20 mA, 16-bit, accuracy +/- 0.2% of full scale at 25º CMax Load Impedance: 1000 Ω with 24V dc loop power,
400 Ω with 12V dc loop power
Discrete Inputs (8) 12...24V dc (on-state)
Pulse Inputs (3) 8...24 V dc, 10 KHz with filter off, 30 Hz with filters on
Discrete Outputs (4) FET, 12...24V dc, 200mA
HART Multipoint Interface Supports 13 devices, 1200 bps
Serial Communication PortsRS 232 Serial port, RS 485 Serial port,
Baud rates: 2400, 4800, 9600, 19200, 38400, 57600(Recommended RS 232 cable: 1747-CP3)
Ethernet Communication Ports RJ45, 10-100 Mbps
Serial Protocols Modbus RTU / ASCII
Ethernet Protocols Modbus TCP/IP
Dimensions 213 x 130 x 56 mm
Operating Temperature -40ºC...+70ºC, 5...95% relative humidity, non-condensing
Shock 15g in any axis
Vibration Frequencies up to 150 Hz, Amplitute 0.0015 in. max., peek-to-peek, Acceleration to 2g
Standards and Regulatory Compliance CE, UL, Class 1, Div. II, Groups A, B, C, D
* RTU does not have AGA 3, AGA 7, AGA 8 calculations** Complies with AGA Report #3 1992
For the Configured DataSite panel, selection guide information can befound in publication: 1748-SG001A-EN-E
DataSite Specifications
Publication 1758-PP001D-EN-P, October 2010Copyright ©2010 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Yekaterinburgtel. +7 343 376 [email protected]
St. Petersburgtel. +7 812 327 [email protected]
Moscowtel. +7 495 641 [email protected]
Кievtel. +38 044 495 33 [email protected]
Helsinkitel. +358 9 540 [email protected]
Vilniustel. +370 5 215 [email protected]
Rigatel. +371 6738 [email protected]
Мinsktel. +375 17 200 [email protected]
Tallinntel. +372 668 [email protected]
Samaratel. +7 846 273 95 [email protected]
www.klinkmann.com
Rockwell_Logic_Programmable_DataSite_RTU_Oil-Gas_Profile_en_0611.pdf