aplicatia2 Adin1
description
Transcript of aplicatia2 Adin1
-
Aplicatia 2
= 1.05 Cext= 12.50 [mg/m3]
F10= F20
= 2.00 q= 2520 [mg/h] F04= F03
= 0.33 = 1.20 [ kg/m3]
F21= F32
= 1.50 n= 1.00 [h-1]
F43= F41
F41 F32
5 [m]
[m]
F10 50.60 [kg/h]
F20 48.40 [kg/h]
F03 33.0 [kg/h]
F04 66.0 [kg/h]
F04
F20F10
Z3Z4
Sa se calculeze indicele de eficienta a ventilarii pentru incaperea din figura de mai jos, cu dimensiunile Lxlxh
= 5 x 5 x 3.3 m, daca se cunosc:
F21
F43 F03
[m]
[m]
2.5 2.5
Z1 Z2
Determinarea debitelor de aer de intrare si iesire
F04+F03=F10+F20=n*V*a
1.80
1.50
-
Z1 (1)
Z2 (2)
Z3 (3)
Z4 (4)
A A-1
0.33 1.00 1.00 -0.67
-1 1.50 0.67 0.22
B X
50.60 72.60
-33.00 26.40
F21 24.20 [kg/h]
F32 72.60 [kg/h]
F43 39.60 [kg/h]
F41 26.40 [kg/h]
Z1 0
Z2 -0.00018
Z3 0
Z4 0.000179
Z1
Z2
Z3
Z4
F21+F41-F10=0
-F21+F32-F20=0
F43-F32+F03=0
-F43-F41+F04=0
*F32+F41=F10
F32*(1-)=F20
*F41-F32=-F03
F41*(-1-)=-F40
Matricea coeficientilorInversa matricei
coeficientilor
Matricea termenilor
liberi
1. Ecuatia de continuitate
2. Ecuatia de continuitate a masei de poluant
F41*C4+F21*C2-F10*C1+q1=0
F32*C3-(F21+F20)*C2+q2=0
F03*Cext+F43*C4-F32*C3+q3=0
F04*Cext-(F43+F41)*C4+q4=0
Bilantul pe zone
Din ecuatiile (1) si (2)
-
Matricea coeficientilor Matricea termenilor liberi
A C1 C2 C3 C4 B
Z1 -50.60 24.20 0.00 26.40 0
Z2 0.00 -72.60 72.60 0.00 -2520
Z3 0.00 0.00 -72.60 39.60 -412.5
Z4 0.00 0.00 0.00 -66.00 -825
Inversa matricei coeficientilor
A-1
X
-0.01976 -0.0066 -0.0066 -0.0119 C1 29.10 [mg/h]
0 -0.0138 -0.0138 -0.0083 C2 47.21 [mg/h]
0.00 0.0000 -0.0138 -0.0083 C3 12.50 [mg/h]
0.00 0.0000 0.0000 -0.0152 C4 12.50 [mg/h]
c= Ce/CCe= (F10*C1+F20*C2)/(F10+F20)
C= (C3*V3+C4*V4)/(V3+V4)
c= 3.04Ce= 37.95
C= 12.50
3. Calculul eficientei ventilarii c