Localitate: CALARASI 0 tev = 37.5 C = 23 % Az = 7 Np = 1/6 m2 qsp = w/m2 70 m2 Ldesen L= H= 4 m2 ql 0.055 kW qom = = = 2.14023E-05 hv 2569.82 hv = cp * t + 2501 = 1.86 * 37 + 2501 = 2569.82 0 0 (t = 4 10) C ti = tev - t ti = 37.5 - 10 = 27.5 C ti = (23 26)0C G = Np * qom v = D= tc = (6 8) 0C Q [kW] G [Kg/s] Q [kW] tc [0C] se adopta 8 0C Kg/s = Q [kW] ti - tc [0C) Kg/s Se adopta ti = 26 0C

Kg/s

m/s

tc = ti - tc tc = ti - tc = 26 - 8 = 18 0C hc = 44 [KJ/Kg] ti = 26 0C hi = 53 [KJ/Kg] hi - hc = 9 [KJ/Kg]

Tab. 1.1. Calcul tabelar distributrie aer proaspat:Nr. Crt. 5.4 1 2 3 4 5 6 7 8 9 destinatia Birou 1 Birou 2 Birou contorizare Birou S5 Apa Birou Tehnic 1 Birou Tehnic 2 Birou Auto Oficiu Portar Birou CAB ti [0C] 26 26 26 26 26 26 26 26 26 L [m] 5.85 5.80 5.80 3.00 5.80 5.80 5.80 2.75 3.00 S [m2] 31.59 31.32 31.32 16.2 30.45 30.45 23.59 6.46 15.75 Np buc 5 5 5 3 5 5 4 1 3 Q [W] 2211.30 2192.40 2192.40 1134.00 2131.50 2131.50 1651.30 452.38 1102.50 G [Kg/s] 0.00010701 0.00010701 0.00010701 0.00006421 0.00010701 0.00010701 0.00008561 0.00002140 0.00006421 v [[KJ/Kg] 20664.2 20487.5 20487.5 17661.7 19918.4 19918.4 19288.8 21136.8 17171.1

Tab. 1.2. Dimensionare retea distributie aer:m /h 594 1188 1782 2632 3226 4075 4925 5774 66243

Nr. Tr. 1 2 3 4 5 6 7 8 9

Debit l/s 165.0 330.0 495.0 731.0 896.0 1132.0 1368.0 1604.0 1840.0 m/s 0.165 0.330 0.495 0.731 0.896 1.132 1.368 1.604 1.840

v (impusa) m/s 6.50 7.00 7.50 8.00 8.50 9.00 9.50 10.00 10.50

S (rezultata) m 0.025 0.047 0.066 0.091 0.105 0.126 0.144 0.160 0.175

[mm] axh 125 x 200 240 x 200 350 x 200 460 x 200 550 x 200 650 x 200 750 x 200 800 x 200 850 x 200

S (reala) m 0.025 0.048 0.070 0.092 0.110 0.130 0.150 0.160 0.170

v (reala) m/s 6.60 6.88 7.07 7.95 8.15 8.71 9.12 10.03 10.82

Tab. 1.3. Selectare unitati de climatizare tip ventilo-convectori:Nr. Tr. 1 2 3 4 5 6 7 8 9 destinatia Birou 1 Birou 2 Birou contorizare Birou S5 Apa Birou Tehnic 1 Birou Tehnic 2 Birou Auto Oficiu Portar Birou CAB Q [KW] 2.21 2.19 2.19 1.13 2.13 2.13 1.65 0.45 1.10 Qsens [KW] 2.81 2.17 2.17 1.61 2.17 2.17 1.61 1.61 1.61 Debit apa l/h m/h 666 0.666 524 0.524 524 0.524 373 0.373 524 0.524 524 0.524 373 0.373 373 0.373 373 0.373 Debit aer m/h 610 445 445 380 445 445 380 380 380 tip. aparat ELVIRA ECM 32 ECM 22 ECM 22 ECM 12 ECM 22 ECM 22 ECM 12 ECM 12 ECM 12

Au fost selectati ventilo-convectori Elvira, tip caseta de plafon, cu 2 tevi, la o temperatura a apei 7 - 12 0C

Tab. 1.4. Dimensionarea conductelor pe distributia de agent termic si pierderile de sarcina aferente :Debit Qsens Nr. l/h [l/s] [KW] Tr. A. Distributia agentului termic pe ramura principala 1 373 0.104 1.61 2 746 0.207 2.71 3 1119 0.311 4.32 4 1643 0.456 6.49 5 2016 0.560 8.10 6 2540 0.706 10.27 7 3064 0.851 12.44 8 3730 1.036 15.25 9 4254 1.182 17.42 10 8508 2.363 34.85 Nota. Au fost selectate conducte de distributie din cupru. [mm] 22 x 1,2 28 x 1.2 28 x 1.2 35 x 1.5 35 x 1.5 42 x 1.5 42 x 1.5 42 x 1.5 42 x 1.5 54 x 1,5 R v l Rl

12.8 12.5 25 17.5 26 16 22 31 33 15

0.40 0.48 0.72 0.70 0.86 0.76 0.75 1.11 1.20 0.90

4.2 5.9 1.2 1.2 5.0 0.4 5.6 0.4 3.2 10.5

53.76 73.75 30 21 130 6.4 123.2 12.4 105.6 157.5

CALCULUL PIERDERILOR DE SARCINA PE TRONSOANE Tronson 1Nr. crt. Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 2 2.5 3.5 0.7 2.5 7 1.4 10.9

1 2 3

Tronson 2Nr. Denumire crt. 1 teu trecere la separare 2 teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 3Nr. Denumire crt. 1 teu trecere la separare 2 teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 4Nr. Denumire crt. 1 teu trecere la separare 2 teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 5Nr. Denumire crt. 1 teu trecere la separare 2 teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 6Nr. Denumire crt. 1 teu trecere la separare 2 teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 7Nr. Denumire crt. 1 teu trecere la separare 2 teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 8Nr. Denumire crt. 1 teu trecere la separare 2 teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 9Nr. Denumire crt. 1 teu trecere la separare 2 teu trecere la impreunare 3 robinet sferic TOTAL buc. 1 1 0.3 0.6 0.3 0.6 1 1.9

2

0.5

Tronson 10Nr. Denumire crt. 1 teu trecere la separare 2 teu trecere la impreunare 3 robinet sferic buc. 1 1 4 0.3 0.6 0.5 0.3 0.6 2

4 5 6

Cot drept filtru "y" schimbator de caldura in placi TOTAL

6 1 1

0.6 2.5 3.5

3.6 2.5 3.5 12.5

Stabilirea inaltimii de pompare HRR' HRR'nec

Hpompa

nec

= (Rl+Z)c.c.m.d.

nec

= 1,7 [mCA]nom

Determinarea pompei de circulatie - se face in functie de : ( Q

, HRR' )

nec

Determinarea s-a facut folosind programul de selectie Willo cunoscand urmatoarele date: - Debitul vehiculat: Q = 8,5 [m3/h] - Inaltimea de pompare: H = 1,7 [mCA] - Fluid de lucru: apa rece la temp. de 7 [0C]

In urma selectiei a rezultat o pompa marca Willo, Stratos-E 40/1-4 CAN, 230 [V], 50 [Hz], PN 10, cu turatie variabila, ava - Debitul vehiculat: Q = 8,5 [m3/h] - Inaltimea de pompare: H = 1,7 [mCA]

Dimensionarea hidraulica a circuitelor racordate in paralel cu circuitul cel mai defavorizat (c.c.m.d.)Nr. Tr. 2.1 3.1 4.1 Qsens [KW] 1.61 1.61 2.17 Debit l/h 373 373 524 [l/s] 0.104 0.104 0.146 [mm] 22 x 1.2 22 x 1.2 22 x 1.2 R [mmcA/m] 12.8 12.8 24 v [m/s] 0.4 0.4 0.58 l [m] 2.6 1.2 3.9 Rl [mmcA] 33.28 15.36 93.6

A. Dimensionare hidraulica pe tronsoanele legate in paralel cu c.c.m.d.

5.1 6.1 7.1 8.1 9.1

1.61 2.17 2.17 2.81 2.17

373 524 524 666 524

0.104 0.146 0.146 0.185 0.146

22 x 1.2 22 x 1.2 22 x 1.2 28 x 1.2 22 x 1.2

12.8 24 24 10 24

0.4 0.58 0.58 0.43 0.58

3.7 3.9 2.7 3.9 2.7

47.36 93.6 64.8 39 64.8

CALCULUL PIERDERILOR DE SARCINA PE TRONSOANENr. trons on Ventilo-convector buc 1 1 1 1 1 1 1 1 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 Robinet cu ventil buc 2 2 2 2 2 2 2 2 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 buc 2 2 2 2 2 2 2 2 Cot drept 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9

2.1 3.1 4.1 5.1 6.1 7.1 8.1 9.1

Verificare conditie (Rl + Z)x = (Rl + Z)r si calcul HRech (Z*rob)Nr. tr. 2.1 3.1 4.1 5.1 6.1 7.1 8.1 9.1(Rl +Z)x [Pa] (Rl +Z)r [Pa] Z* echilibrare [Pa]

1204.8 1025.6 2778.1 1345.6 2778.1 2490.1 1392.8 2490.1

1409.6 2250.6 2784.6 3215.1 4925.5 5250.5 6736.8 7411.6

204.8 1225.0 6.5 1869.5 2147.4 2760.4 5344.0 4921.5

Pentru a se realiza echilibrarea hidraulica a circuitelor legate in paralel se va impune o pierdere de sarcina locala egala cu deficitul inregistrat pe fiecare circuit in parte (Z*). Echilibrarea consta in manevrarea ventilului cu ventil si scaun oblic montat pe fiecare consumator.

D [m3/h] 737.1 730.8 730.8 378.0 710.5 710.5 550.4 150.8 367.5

D [l/s] 204.8 203.0 203.0 105.0 197.4 197.4 152.9 41.9 102.1

tip. aparat tip 606 606 606 505 606 606 505 505 505

debit aparat [m3/h] 849.6 849.6 849.6 594 849.6 849.6 594 594 594

debit aparat [l/s] 236 236 236 165 236 236 165 165 165

v (impus) =(G/2)/(3.14*D2/4) =

6.835

e: Z Rl+Z (Rl+Z) Z 80 115 260 245 456 290 282.5 612 750 405

10.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 1.9 12.5

872 103.5 234 220.5 410.4 261 254.25 550.8 1425 5062.5

1409.6 841 534 430.5 1710.4 325 1486.25 674.8 2481 6637.5

1409.6 2250.6 2784.6 3215.1 4925.5 5250.5 6736.75 7411.55 9892.55 16530.05

u turatie variabila, avand urmatoarele caracteristici:

Z [Pa] 872 872 1842.1

Rl+Z [Pa] 1204.8 1025.6 2778.1 Z 80 80 169

10.9 10.9 10.9

10.9 10.9 10.9 10.9 10.9

872 1842.1 1842.1 1002.8 1842.1

1345.6 2778.1 2490.1 1392.8 2490.1

80 169 169 92 169

Localitate: ALEXANDRIA 0 tev = C 38 = Az = Np = qsp = 25 7 %

m2 1/6 75 w/m2 Ldesen + 1 m2 L= H= 4 m2 ql 0.055 kW qom = = = 2.1402E-05 hv 2569.82 hv = cp * t + 2501 = 1.86 * 37 + 2501 = 2569.82 0 (t = 4 10) C ti = tev - t ti = 38 - 10 = 28 0C ti = (23 26) C G = Np * qom Q [kW] v= G [Kg/s] Q [kW] D= tc [0C]0

Kg/s

Se adopta ti = 26 C m3/h 850 1699 2293 34810

0

Kg/s =0

Q [kW] ti - tc [0C)

Kg/s

m/s

tc = (6 8) C0

0

se adopta 8 C

tc = ti - tc tc = ti - tc = 26 - 8 = 18 C hc = 32 [KJ/Kg] ti = 26 C hi = 39 [KJ/Kg] hi - hc = 7 [KJ/Kg]

4669 5857 7045 8233 9421

1 2 3 4 5 6 7 8 9

A. Dimensionar1 2 3 4 5 6 7 8 9 10

Nr. crt.

1 2 3

Nr. crt. 1 2

Nr. crt. 1 2

Nr. crt. 1 2

Nr. crt. 1 2

Nr. crt. 1 2

Nr. crt. 1 2

Nr. crt. 1 2

Nr. crt. 1 2

3

Nr. crt. 1 2 3 4 5

6

Stabilirea ina HRR' HRR'nec

Hp = 1,9

nec

Determinarea s

In urma selecti

Dimensionare

A. Dimensionar2.1 3.1 4.1 5.1

6.1 7.1 8.1 9.1

2.1 3.1 4.1 5.1 6.1 7.1 8.1 9.1

2.1 3.1 4.1 5.1 6.1 7.1 8.1 9.1

Tab. 1.1. Calcul tabelar distributrie aer proaspat:Nr. Crt. 1 2 3 4 5 6 7 8 9 destinatia Birou 1 Birou 2 Birou contorizare Birou S5 Apa Birou Tehnic 1 Birou Tehnic 2 Birou Auto Oficiu Portar Birou CAB ti [0C] 26 26 26 26 26 26 26 26 26 L [m] 6.85 6.80 6.80 4.00 6.80 6.80 6.80 2.75 4.00 S [m2] 36.99 36.72 36.72 21.6 35.7 35.7 28.84 6.46 21.00 Np buc 6 6 6 4 6 6 5 1 4 Q [W] 2774.25 2754.00 2754.00 1620.00 2677.50 2677.50 2163.00 484.69 1575.00 G [Kg/s] 0.00012841 0.00012841 0.00012841 0.00008561 0.00012734 0.00012734 0.00010701 0.00002140 0.00007491

v[[KJ/Kg] 21604.01 21446.32 21446.32 18923.22 21025.8 21025.8 20212.8 22646.54 21025.8

D [m3/h] 1189.0 1180.3 1180.3 694.3 1147.5 1147.5 927.0 207.7 675.0

D [l/s] 330.3 327.9 327.9 192.9 318.8 318.8 257.5 57.7 187.5

Tab. 1.2. Dimensionare retea distributie aer:Debit Nr. Tr. 1 2 3 4 5 6 7 8 9 l/s 236.0 472.0 637.0 967.0 1297.0 1627.0 1957.0 2287.0 2617.0 m/s 0.236 0.472 0.637 0.967 1.297 1.627 1.957 2.287 2.617 v (impusa) S (rezultata) [mm] m m/s axh 6.50 0.036 150 x 250 7.00 0.067 275 x 250 7.50 8.00 8.50 9.00 9.50 10.00 10.50 0.085 0.121 0.153 0.181 0.206 0.229 0.249 340 x 250 480 x 250 600 x 250 725 x 250 825 x 250 900 x 250 975 x 250 S (reala)

m0.038 0.069 0.085 0.120 0.150 0.181 0.206 0.225 0.244

v (reala) m/s 6.29 6.87 7.49 8.06 8.65 8.98 9.49 10.16 10.74

v (impus) =(G/2)/(3.14*D /4) =

2

Tab. 1.3. Selectare unitati de climatizare tip ventilo-convectori:

Nr. Tr. 1 2 3 4 5 6 7 8 9

destinatia Birou 1 Birou 2 Birou contorizare Birou S5 Apa Birou Tehnic 1 Birou Tehnic 2 Birou Auto Oficiu Portar Birou CAB

Q [KW] 2.77 2.75 2.75 1.62 2.68 2.68 2.16 0.48 1.58

Qsens [KW] 2.87 2.87 2.87 2.02 2.87 2.87 2.02 1.03 2.02

Debit apa l/h 670 670 670 450 670 670 450 220 450 m/h 0.67 0.67 0.67 0.45 0.67 0.67 0.45 0.22 0.45

Debit aer m/h

tip. aparat ADELIA 1200 x 600 1200 x 600 1200 x 600 900 x 600 1200 x 600 1200 x 600 900 x 600 600 x 600 900 x 6000

VCV - caseta liniara, de plafon (2 tevi), t. apa

Au fost selectati ventilo-convectori Adelia, tip caseta liniara de plafon, cu 2 tevi, la o temperatura a apei 7 - 12 C

Dimensionarea hidraulica a circuitului cel mai defavorizat (c.c.m.d.).Nr. Tr. Qsens [KW] Debit [m3/h] [mm] R v l Rl Z Rl+Z

A. Dimensionare hidraulica pe tronsoanele legate in paralel cu c.c.m.d.1 0.450 2.02 15 2 0.900 3.60 20 3 1.120 4.63 25 4 1.790 7.50 32 5 2.240 9.52 32 6 2.910 12.39 32 7 3.580 15.26 40 8 4.250 18.13 40 9 4.920 21.00 40 10 9.840 41.99 50 Nota. Au fost selectate conducte de distributie din PVC. 36 32 12.5 9.6 13 22 12 16 19 22 0.54 0.63 0.45 0.48 0.57 0.76 0.60 0.73 0.81 1.00 4.2 6.3 1.3 1.0 6.0 1.0 6.1 1.0 3.3 10.5 151.2 201.6 16.25 9.6 78 22 73.2 16 62.7 231 10.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 1.9 12.5 2201.8 179.55 90 103.5 147.15 261 162 240.75 624.15 6250 3713.8 2195.55 252.5 199.5 927.15 481 894 400.75 1251.15 8560

CALCULUL PIERDERILOR DE SARCINA PE TRONSOANE Tronson 1

Nr. crt.

Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL

buc. 1 2 2

2.5 3.5 0.7

2.5 7 1.4 10.9

1 2 3

Tronson 2Nr. crt. 1 2 Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 3Nr. crt. 1 2 Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 4Nr. crt. 1 2 Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 5Nr. crt. 1 2 Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 6

Nr. crt. 1 2

Denumire teu trecere la separare teu trecere la impreunare TOTAL

buc. 1 1

0.3 0.6

0.3 0.6 0.9

Tronson 7Nr. crt. 1 2 Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 8Nr. crt. 1 2 Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 9Nr. crt. 1 2 Denumire teu trecere la separare teu trecere la impreunare robinet sferic TOTAL buc. 1 1 0.3 0.6 0.3 0.6 1 1.9

3

2

0.5

Tronson 10Nr. crt. 1 2 3 4 5 Denumire teu trecere la separare teu trecere la impreunare robinet sferic Cot drept filtru "y" buc. 1 1 4 6 1 0.3 0.6 0.5 0.6 2.5 0.3 0.6 2 3.6 2.5

6

schimbator de caldura in placi TOTAL

1

3.5

3.5 12.5

Stabilirea inaltimii de pompare HRR' HRR'nec

Hpompa

nec

= (Rl+Z)c.c.m.d.

nec

= 1,9 [mCA]nom

Determinarea pompei de circulatie - se face in functie de : ( Q

, HRR' )

nec

Determinarea s-a facut folosind programul de selectie Willo cunoscand urmatoarele date: - Debitul vehiculat: Q = 9,84 [m3/h] - Inaltimea de pompare: H = 1,9 [mCA] 0 - Fluid de lucru: apa rece la temp. de 7 [ C]

In urma selectiei a rezultat o pompa marca Willo, Stratos-E 50/1-8 CAN, 230 [V], 50 [Hz], PN 10, cu turatie variabila, avand urmatoarele ca - Debitul vehiculat: Q = 8,5 [m3/h] - Inaltimea de pompare: H = 1,7 [mCA]

Dimensionarea hidraulica a circuitelor racordate in paralel cu circuitul cel mai defavorizat (c.c.m.d.)Nr. Tr. 2.1 3.1 4.1 5.1 Qsens [KW] 2.02 1.03 2.87 2.02 Debit 3 [m /h] 0.450 0.220 0.670 0.450 [mm] 15 15 20 15 R v l Rl Z Rl+Z

A. Dimensionare hidraulica pe tronsoanele legate in paralel cu c.c.m.d.36 12.5 18 36 0.54 0.29 0.48 0.54 2.6 1.2 3.9 3.7 93.6 15 70.2 133.2 10.9 10.9 10.9 10.9 1602.3 457.8 1253.5 1602.3 2538.3 607.8 1955.5 2934.3

6.1 7.1 8.1 9.1

2.87 2.87 2.87 2.87

0.670 0.670 0.670 0.670

20 20 20 20

18 18 18 18

0.48 0.48 0.48 0.48

3.9 2.7 3.9 2.7

70.2 48.6 70.2 48.6

10.9 10.9 10.9 10.9

1253.5 1253.5 1253.5 1253.5

1955.5 1739.5 1955.5 1739.5

CALCULUL PIERDERILOR DE SARCINA PE TRONSOANENr. tronso n Ventilo-convector buc 1 1 1 1 1 1 1 1 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 Robinet cu ventil buc 2 2 2 2 2 2 2 2 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 Cot drept buc 2 2 2 2 2 2 2 2 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9

2.1 3.1 4.1 5.1 6.1 7.1 8.1 9.1

Verificare conditie (Rl + Z)x = (Rl + Z)r si calcul HRech (Z*rob)Nr. tr. 2.1 3.1 4.1 5.1 6.1 7.1 8.1 9.1(Rl +Z)x [Pa] (Rl +Z)r [Pa] Z* echilibrare [Pa]

2538.3 607.8 1955.5 2934.3 1955.5 1739.5 1955.5 1739.5

3713.8 5909.4 6161.9 6361.4 7288.5 7769.5 8663.5 9064.3

1175.5 5301.6 4206.4 3427.1 5333.0 6030.0 6708.0 7324.8

Pentru a se realiza echilibrarea hidraulica a circuitelor legate in paralel se va impune o pierdere de sarcina locala egala cu deficitul inregistrat pe fiecare circuit in parte (Z*). Echilibrarea consta in manevrarea ventilului cu ventil si scaun oblic montat pe fiecare consumator.

tip. aparat tip 707 707 707 606 707 707 707 505 606

debit aparat [m3/h] 1188 1188 1188 849.6 1188 1188 1188 594 849.6

debit aparat [l/s] 330 330 330 236 330 330 330 165 236

=(G/2)/(3.14*D /4) =

2

6.771

ta liniara, de plafon (2 tevi), t. apa 7-120C

(Rl+Z) Z 202 199.5 100 115 163.5 290 180 267.5 328.5 500

3713.8 5909.35 6161.85 6361.35 7288.5 7769.5 8663.5 9064.25 10315.4 18875.4

ariabila, avand urmatoarele caracteristici:

Z 147 42 115 147

115 115 115 115

Tab. 1.1. Calcul tabelarLocalitate: tev = = Az = Np = qsp = L= H= Nr. Crt. 32.8 35 6 1/5 650

C % m2

1 2 3 4 5 6 7 8 9

w/m2 2 Ldesen + 0.5 m2

m 4 ql 0.055 kW qom = = = 2.1402E-05 hv 2569.82 hv = cp * t + 2501 = 1.86 * 37 + 2501 = 2569.82 0 (t = 4 10)0C ti = tev - t ti = 32.8 - 10 = 26.5 C ti = (23 26)0C Se adopta ti = 26 0C G = Np * qom Q [kW] Kg/s v= G [Kg/s] Q [kW] D= = 0 tc [ C] tc = (6 8) 0C se adopta 8 0C

Kg/s

Q [kW] 0 ti - tc [ C)0

Kg/s

m/s

m /h 594 1188 1782 2632 3226 4075 4925 5774 6624

3

Nr. Tr. 1 2 3 4 5 6 7 8 9

tc = ti - tc tc = ti - tc = 26 - 8 = 18 C hc = 29 [KJ/Kg] ti = 26 C hi = 38 [KJ/Kg] hi - hc = 9 [KJ/Kg]0

Nr. Tr.1 2 3 4 5 6 7 8 9

Au fost selectati ventilo-convecto la o temperatura a apei 7 - 120C

Dimensionarea hidraulicaNr. Tr.

A. Dimensionare hidraulica a

1 2 3 4 5 6 7 Nota. Au fost selectate conducte

CALCULUL PIERDERILOR D Tronson 1Nr. crt.

1 2 3

Tronson 2Nr. crt. 1 2

Tronson 3Nr. crt. 1 2

Tronson 4Nr. crt. 1 2

3

Tronson 5Nr. crt. 1 2

Tronson 6

Nr. crt. 1 2

Tronson 7Nr. crt. 1 2 3 4 5 6

Stabilirea inaltimii de pom

HRR'nec Hpompanec = (Rl HRR'nec = 2,3 [mCA]

Determinarea pompei de c

Determinarea s-a facut folos

In urma selectiei a rezultat o

Dimensionarea hidraulicaNr. Tr. 7.41 7.4 7.3 7.2 7.1 2.1 3.1 4.1 7.5 7.31 7.21 7.11

B. Dimensionare hidraulica pe

CALCULUL PIERDERILOR D Tronson 7.5Nr. crt.

1 2 3

Tronson 7.4Nr. crt. 1 2

Tronson 7.3Nr. crt. 1 2

Tronson 7.2Nr. crt. 1 2

Tronson 7.1Nr. crt. 1 2

3

Tronson 2.1Nr. crt.

1 2 3

Tronson 3.1Nr. crt.

1 2 3

Tronson 4.1Nr. crt.

1 2 3

Tronson 7.41Nr. crt.

1 2 3

Tronson 7.31Nr. crt.

1 2 3

Tronson 7.21

Nr. crt.

1 2 3

Tronson 7.11Nr. crt.

1 2 3

Nr. tr. 2.1 3.1 4.1 7.1 7.5 7.31 7.21 7.11

Tab. 1.1. Calcul tabelar distributrie aer proaspat:destinatia Birou 1 Birou 2 Birou contorizare Birou S5 Apa Birou Tehnic 1 Birou Tehnic 2 Birou Auto Oficiu Portar Birou CAB ti [0C] 26 26 26 26 26 26 26 26 26 L [m] 6.35 6.30 6.30 3.50 6.30 6.30 6.30 2.75 3.50 S [m2] 33.34 33.08 33.08 18.38 33.08 33.08 26.22 6.46 18.38 Np buc 7 7 7 4 7 7 5 1 4 Q [W] 2166.94 2149.88 2149.88 1194.38 2149.88 2149.88 1703.98 420.06 1194.38 G

v

D [m3/h] 722.3 716.6 716.6 398.1 716.6 716.6 568.0 140.0 398.1

D [l/s] 200.6 199.1 199.1 110.6 199.1 199.1 157.8 38.9 110.6

tip. aparat tip 606 606 606 505 606 606 505 505 505

[Kg/s] [[KJ/Kg] 0.00014982 14464.0 0.00014982 14350.1 0.00014982 14350.1 0.00008561 13951.5 0.00014982 14350.1 0.00014982 0.00010701 0.00002140 0.00008561 14350.1 15923.3 19627.0 13951.5

Tab. 1.2. Dimensionare retea distributie aer:Debit l/s 165.0 330.0 495.0 731.0 896.0 1132.0 1368.0 1604.0 1840.0 m/s 0.165 0.330 0.495 0.731 0.896 1.132 1.368 1.604 1.840 v (impusa) S (rezultata) [mm] m m/s axh 6.50 0.025 125 x 200 7.00 0.047 240 x 200 7.50 8.00 8.50 9.00 9.50 10.00 10.50 0.066 0.091 0.105 0.126 0.144 0.160 0.175 350 x 200 450 x 200 525 x 200 625 x 200 725 x 200 800 x 200 850 x 200 S (reala)

m0.025 0.048 0.070 0.090 0.105 0.125 0.145 0.160 0.170

v (reala) m/s 6.60 6.88 7.07 8.12 8.53 9.06 9.43 10.03 10.82

v (impus) =(G/2)/(3.14*D2/4) =

Tab. 1.3. Selectare unitati de climatizare tip ventilo-convectori:

destinatiaBirou 1 Birou 2 Birou contorizare Birou S5 Apa Birou Tehnic 1 Birou Tehnic 2 Birou Auto Oficiu Portar Birou CAB

Q [KW] 2.17 2.15 2.15 1.19 2.15 2.15 1.70 0.42 1.19

Qsens [KW] 2.34 2.34 2.34 1.45 2.34 2.34 1.82 1.20 1.20

Debit apa l/h m/h 535 0.535 535 0.535 535 0.535 250 0.250 535 0.535 535 0.535 400 0.400 210 0.210 210 0.210

Debit aer tip. aparat H-silence m/h 480 HS 3.4 480 HS 3.4 480 HS 3.4 240 HS 1.4 480 HS 3.4 480 HS 3.4 360 HS 2.4 240 HS 1.3 240 HS 1.3

VCV - carcasat de pardoseala (2 tevi, 3 randuri x.3 si 4

Au fost selectati ventilo-convectori Hegoa Silence, tip necarcasati de plafon, cu 2 tevi, 3 si 4 randuri, la o temperatura a apei 7 - 120C

Dimensionarea hidraulica a circuitului cel mai defavorizat (c.c.m.d.).Qsens [KW] Debit 3 m /h [mm] R v l Rl Z Rl+Z (Rl+Z)

A. Dimensionare hidraulica a c.c.m.d. (tronsoanele 1, 2, 3, 4, 5, 6 si 7)0.250 1.45 1/2" 0.785 3.79 3/4" 1.320 6.13 1" 1.855 8.47 1" 3.710 16.94 1 1/4" 5.600 25.84 40 7.490 34.74 40 Nota. Au fost selectate conducte de distributie din otel. 16 26 15 33 27 18 23 0.38 0.73 0.56 0.87 0.96 0.86 0.97 8.00 6.45 6.45 6.45 12.00 0.05 2.50 128 167.7 96.75 212.85 324 0.9 57.5 13.7 0.9 0.9 1.9 0.9 0.9 12.5 2315.3 162 202.5 841.7 565.2 364.5 8275 3595.3 1839.0 1170.0 2970.2 3805.2 373.5 8850.0 3595.3 5434.3 6604.3 9574.5 13379.7 13753.2 22603.2

CALCULUL PIERDERILOR DE SARCINA PE TRONSOANE Tronson 1Denumire buc.

ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL

1 2 6

2.5 3.5 0.7

2.5 7 4.2 13.7

Tronson 2Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 3Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 4Denumire teu trecere la separare teu trecere la impreunare robinet sferic TOTAL buc. 1 1 0.3 0.6 0.3 0.6 1 1.9

2

0.5

Tronson 5Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 6

Denumire teu trecere la separare teu trecere la impreunare TOTAL

buc. 1 1

0.3 0.6

0.3 0.6 0.9

Tronson 7Denumire teu trecere la separare teu trecere la impreunare robinet sferic Cot drept filtru "y" schimbator de caldura in placi TOTAL buc. 1 1 4 6 1 1 0.3 0.6 0.5 0.6 2.5 3.5 0.3 0.6 2 3.6 2.5 3.5 12.5

Stabilirea inaltimii de pompare HRR'nec Hpompanec = (Rl+Z)c.c.m.d. HRR'nec = 2,3 [mCA] Determinarea pompei de circulatie - se face in functie de : ( Qnom, HRR'nec) Determinarea s-a facut folosind programul de selectie Willo cunoscand urmatoarele date: - Debitul vehiculat: Q = 7,49 [m3/h] - Inaltimea de pompare: H = 2,3 [mCA] - Fluid de lucru: apa rece la temp. de 7 [0C]

In urma selectiei a rezultat o pompa marca Willo, Stratos-E 40/1-4 CAN, 230 [V], 50 [Hz], PN 10, cu turatie variabila, avand urmatoarele caracteri

- Debitul vehiculat: Q = 7,49 [m /h] - Inaltimea de pompare: H = 2,3 [mCA]

3

Dimensionarea hidraulica a circuitelor racordate in paralel cu circuitul cel mai defavorizat (c.c.m.d.)Qsens [KW] 1.20 2.40 4.22 6.56 8.90 2.34 2.34 2.34 1.20 1.82 2.34 2.34 Debit m3/h 0.210 0.420 0.820 1.355 1.890 0.535 0.535 0.535 0.210 0.400 0.535 0.535 [mm] 1/2" 1/2" 3/4" 3/4" 1" 3/4" 3/4" 3/4" 1/2" 3/4" 3/4" 3/4" R v l Rl Z Rl+Z (Rl+Z)

B. Dimensionare hidraulica pe tronsoanele legate in paralel cu c.c.m.d.12 8 23 17.5 36 13 13 13 12 7.5 13 13 0.33 0.34 0.6 0.6 0.89 0.4 0.4 0.4 0.33 0.33 0.4 0.4 8.20 2.60 6.45 6.45 4.00 0.40 0.40 0.40 5.30 0.40 0.40 0.40 98.40 20.80 148.35 112.88 144.00 5.20 5.20 5.20 63.60 3.00 5.20 5.20 13.7 0.9 0.9 0.9 1.9 13.7 13.7 13.7 13.7 13.7 13.7 13.7 748.02 52.02 162 162 763.8 1096 1096 1096 748.02 748.02 1096 1096 1732.02 260.02 1645.5 1290.75 2203.8 1148 1148 1148 1384.02 778.02 1148 1148 1732.02 1992.04 3637.54 4928.29 7132.09 1148 1148 1148 1384.02 778.02 1148 1148

CALCULUL PIERDERILOR DE SARCINA PE TRONSOANE Tronson 7.5Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Tronson 7.4Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 7.3Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 7.2Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 7.1Denumire teu trecere la separare teu trecere la impreunare robinet sferic TOTAL buc. 1 1 0.3 0.6 0.3 0.6 1 1.9

2

0.5

Tronson 2.1Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2

TOTAL

13.7

Tronson 3.1Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Tronson 4.1Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Tronson 7.41Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Tronson 7.31Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Tronson 7.21

Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL

buc. 1 2 6

2.5 3.5 0.7

2.5 7 4.2 13.7

Tronson 7.11Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Verificare conditie (Rl + Z)x = (Rl + Z)r si calcul HRech (Z*rob)(Rl +Z)x [Pa] (Rl +Z)r [Pa] Z* echilibrare [Pa]

3595.3 2447.3 1148 5434.3 4286.3 1148 6604.3 5456.3 1148 13753.2 6621.1 7132.09 1732.0 348.0 1384.02 1992.0 1214.0 778.02 3637.5 2489.5 1148 4928.3 3780.3 1148 Pentru a se realiza echilibrarea hidraulica a circuitelor legate in paralel

debit aparat [m3/h] 849.6 849.6 849.6 594 849.6 849.6 594 594 594

debit aparat [l/s] 236 236 236 165 236 236 165 165 165

6.835

ardoseala (2 tevi, 3 randuri x.3 si 4 randuri x.4) apa 7-120C

Z 169 180 225 443 628 405 662

, avand urmatoarele caracteristici:

Z 54.6 57.8 180 180 402 80 80 80 54.6 54.6 80 80

Tab. 1.1. CalcuLocalitate: CRAIOVA 0 C tev = 36.5 = 35 % Az = 7 m 1/6 75 w/m2 Ldesen + 0.5 m2 L= H= 4 m2 ql 0.055 kW qom = = = 2.1402E-05 hv 2569.82 hv = cp * t + 2501 = 1.86 * 37 + 2501 = 2569.82 0 0 (t = 4 10) C ti = tev - t ti = 36.5 - 10 = 26.5 C Np = qsp = ti = (23 26) C0 2

Nr. Crt. 1 2 3 4 5 6 7 8 9

Kg/s

Se adopta ti = 26 C m3/h 594 1188 1782 26320

0

G = Np * qom Q [kW] Kg/s v= G [Kg/s] Q [kW] D= = tc [0C] 0 0 tc = (6 8) C se adopta 8 C

Q [kW] ti - tc [0C)

Kg/s

m/s

Nr. Tr. 1 2 3 4 5 6 7 8 9

tc = ti - tc tc = ti - tc = 26 - 8 = 18 C hc = 44 [KJ/Kg] ti = 26 C hi = 53 [KJ/Kg] hi - hc = 9 [KJ/Kg]0

3481 4331 5180 6030 6880

Nr. Tr. 1 2 3 4 5 6 7 8 9

Au fost selectati ventilola o temperatura a apei

Dimensionarea hidrNr. Tr.

A. Dimensionare hidra

1 2 3 4 5 6 7 Nota. Au fost selectate c

CALCULUL PIERDER Tronson 1Nr. crt.

1 2 3

Tronson 2Nr. crt. 1 2

Tronson 3Nr. crt. 1 2

Tronson 4Nr. crt. 1 2

3

Tronson 5Nr. crt. 1 2

Tronson 6Nr. crt. 1 2

Tronson 7Nr. crt. 1 2 3 4 5 6

Stabilirea inaltimii

HRR'nec Hpompanec

HRR'nec = 2,4 [mCA

Determinarea pomp

Determinarea s-a fac

In urma selectiei a re

Dimensionarea hidrNr. Tr. 7.5 7.4 7.3 7.2 7.1 2.1 3.1 4.1 7.41 7.31 7.21 7.11

A. Dimensionare hidra

CALCULUL PIERDER Tronson 7.5Nr. crt.

1 2 3

Tronson 7.4Nr. crt. 1 2

Tronson 7.3Nr. crt. 1 2

Tronson 7.2Nr. crt. 1 2

Tronson 7.1Nr. crt. 1 2

3

Tronson 2.1Nr. crt.

1 2 3

Tronson 3.1Nr. crt.

1 2 3

Tronson 4.1Nr. crt.

1 2 3

Tronson 7.41Nr. crt.

1 2 3

Tronson 7.31Nr. crt.

1 2 3

Tronson 7.21Nr. crt.

1 2 3

Tronson 7.11Nr. crt.

1 2 3

Verificare conditie (Nr. tr. 2.1 3.1 4.1 7.1 7.41 7.31 7.21 7.11

Tab. 1.1. Calcul tabelar distributrie aer proaspat:destinatia Birou 1 Birou 2 Birou contorizare Birou S5 Apa Birou Tehnic 1 Birou Tehnic 2 Birou Auto Oficiu Portar Birou CAB ti [0C] 26 26 26 26 26 26 26 26 26 L [m] 6.50 6.30 6.30 3.50 6.30 6.30 6.30 2.75 3.50 S [m2] 34.13 33.08 33.08 18.38 33.08 33.08 26.22 6.46 18.38 Np buc 6 6 6 3 6 6 5 1 3 Q [W] 2559.38 2480.63 2480.63 1378.13 2480.63 2480.63 1966.13 484.69 1378.13 G [Kg/s] 0.00012841 0.00012841 0.00012841 0.00006421 0.00012841 0.00012841 0.00010701 0.00002140 0.00006554

v[[KJ/Kg] 19930.71 19317.45 19317.45 21463.84 19317.45 19317.45 18373.04 22646.54 21025.8

D [m3/h] 853.1 826.9 826.9 459.4 826.9 826.9 655.4 161.6 459.4

D [l/s] 237.0 229.7 229.7 127.6 229.7 229.7 182.0 44.9 127.6

tip. aparat tip 606 606 606 505 606 606 606 505 505

Tab. 1.2. Dimensionare retea distributie aer:Debit l/s 165.0 330.0 495.0 731.0 967.0 1203.0 1439.0 1675.0 1911.0 m/s 0.165 0.330 0.495 0.731 0.967 1.203 1.439 1.675 1.911 v (impusa) m/s 6.50 7.00 7.50 8.00 8.50 9.00 9.50 10.00 10.50 S (rezultata)

m0.025 0.047 0.066 0.091 0.114 0.134 0.151 0.168 0.182

[mm] axh 130 x 200 240 x 200 325 x 200 450 x 200 560 x 200 660 x 200 750 x 200 850 x 200 900 x 200

S (reala)

m0.026 0.048 0.065 0.090 0.112 0.132 0.150 0.170 0.180

v (reala) m/s 6.35 6.88 7.62 8.12 8.63 9.11 9.59 9.85 10.62

v (impus) =(G/2)/(3.14*D2/4) =

Tab. 1.3. Selectare unitati de climatizare tip ventilo-convectori:

destinatia Birou 1 Birou 2 Birou contorizare Birou S5 Apa Birou Tehnic 1 Birou Tehnic 2 Birou Auto Oficiu Portar Birou CAB

Q [KW] 2.56 2.48 2.48 1.38 2.48 2.48 1.97 0.48 1.38

Qsens [KW] 2.68 2.68 2.68 1.67 2.49 2.49 2.35 1.00 1.67

Debit apa l/h 595 595 595 370 570 570 500 225 370 m/h 0.595 0.595 0.595 0.37 0.57 0.57 0.5 0.225 0.37

Debit aer m/h 600 600 600 360 480 480 480 240 360

tip. aparat HEGOA H 4.3 H 4.3 H 4.3 H 2.3 H 3.4 H 3.4 H 3.3 H 1.3 H 2.3

VCV - carcasat de pardoseala (2 tevi, 3 randuri x.3

Au fost selectati ventilo-convectori Hegoa, tip carcasati de pardoseala, cu 2 tevi, 3 si 4 randuri, la o temperatura a apei 7 - 120C

Dimensionarea hidraulica a circuitului cel mai defavorizat (c.c.m.d.).Qsens [KW] Debit l/h [l/s] [mm] 18 x 1 28 x 1,2 35 x 1.5 35 x 1.5 42 x 1.5 54 x 1.5 54 x 1.5 R [mmcA/m] 32 17.5 17 30 32 15 23 v [m/s] 0.58 0.60 0.67 0.94 1.12 0.90 1.15 l [m] 8.00 6.45 6.45 6.45 12.00 0.05 2.50 Rl [mmcA] 256.00 112.88 109.65 193.50 384.00 0.75 57.50 Z [Pa] 2315.3 162 202.5 841.7 565.2 364.5 8275 Rl+Z [Pa] 4875.3 1290.8 1299.0 2776.7 4405.2 372.0 8850.0

A. Dimensionare hidraulica a c.c.m.d. (tronsoanele 1, 2, 3, 4, 5, 6 si 7)370 0.103 1.67 965 0.268 4.35 1560 0.433 7.03 2155 0.599 9.71 4310 1.197 19.42 6545 1.818 29.42 8780 2.439 39.42 Nota. Au fost selectate conducte de distributie din cupru. 13.7 0.9 0.9 1.9 0.9 0.9 12.5

CALCULUL PIERDERILOR DE SARCINA PE TRONSOANE Tronson 1Denumire buc.

ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL

1 2 6

2.5 3.5 0.7

2.5 7 4.2 13.7

Tronson 2Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 3Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 4Denumire teu trecere la separare teu trecere la impreunare robinet sferic TOTAL buc. 1 1 0.3 0.6 0.3 0.6 1 1.9

2

0.5

Tronson 5Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 6Denumire teu trecere la separare teu trecere la impreunare buc. 1 1 0.3 0.6 0.3 0.6

TOTAL

0.9

Tronson 7Denumire teu trecere la separare teu trecere la impreunare robinet sferic Cot drept filtru "y" schimbator de caldura in placi TOTAL buc. 1 1 4 6 1 1 0.3 0.6 0.5 0.6 2.5 3.5 0.3 0.6 2 3.6 2.5 3.5 12.5

Stabilirea inaltimii de pompare HRR'nec Hpompanec = (Rl+Z)c.c.m.d. HRR'nec = 2,4 [mCA] Determinarea pompei de circulatie - se face in functie de : ( Qnom, HRR'nec) Determinarea s-a facut folosind programul de selectie Willo cunoscand urmatoarele date: - Debitul vehiculat: Q = 8780 [l/h] = 8,78 [m3/h] - Inaltimea de pompare: H = 2,4 [mCA] - Fluid de lucru: apa rece la temp. de 7 [0C]

In urma selectiei a rezultat o pompa marca Willo, Stratos 40/1-8 CAN, 230 [V], 50 [Hz], PN 10, cu turatie variabila, avand urmatoarele caracteristic - Debitul vehiculat: Q = 2,4 [m3/h] - Inaltimea de pompare: H = 8,78 [mCA]

Dimensionarea hidraulica a circuitelor racordate in paralel cu circuitul cel mai defavorizat (c.c.m.d.)Qsens [KW] 1.67 2.67 5.02 7.51 10.00 2.68 2.68 2.68 1.00 2.35 2.49 2.49 Debit l/h 370 595 1095 1665 2235 595 595 595 225 500 570 570 [l/s] 0.103 0.165 0.304 0.463 0.621 0.165 0.165 0.165 0.063 0.139 0.158 0.158 [mm] 18 x 1 22 x 1.2 28 x 1.2 35 x 1.5 42 x 1.5 22 x 1.2 22 x 1.2 22 x 1.2 18 x 1 22 x 1.2 22 x 1.2 22 x 1.2 R [mmcA/m] 32 27 23 18 13 27 27 27 13 24 26 26 v [m/s] 0.58 0.62 0.7 0.7 0.67 0.62 0.62 0.62 0.38 0.58 0.61 0.61 l [m] 5.30 2.60 6.45 6.45 4.00 0.40 0.40 0.40 8.20 0.40 0.40 0.40 Rl [mmcA] 169.60 70.20 148.35 116.10 52.00 10.80 10.80 10.80 106.60 9.60 10.40 10.40 Z [Pa] 2315.3 173.7 222.3 220.5 427.5 2644.1 2644.1 2644.1 890.5 2315.3 2555.05 2555.05 Rl+Z [Pa] 4011.3 875.7 1705.8 1381.5 947.5 2752.1 2752.1 2752.1 1956.5 2411.3 2659.05 2659.05

A. Dimensionare hidraulica pe tronsoanele legate in paralel cu c.c.m.d.13.7 0.9 0.9 0.9 1.9 13.7 13.7 13.7 13.7 13.7 13.7 13.7

CALCULUL PIERDERILOR DE SARCINA PE TRONSOANE Tronson 7.5Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Tronson 7.4Denumire teu trecere la separare teu trecere la impreunare buc. 1 1 0.3 0.6 0.3 0.6

TOTAL

0.9

Tronson 7.3Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 7.2Denumire teu trecere la separare teu trecere la impreunare TOTAL buc. 1 1 0.3 0.6 0.3 0.6 0.9

Tronson 7.1Denumire teu trecere la separare teu trecere la impreunare robinet sferic TOTAL buc. 1 1 0.3 0.6 0.3 0.6 1 1.9

2

0.5

Tronson 2.1Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Tronson 3.1Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Tronson 4.1Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Tronson 7.41Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Tronson 7.31Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Tronson 7.21Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept TOTAL buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2 13.7

Tronson 7.11Denumire ventilo-convector Robinet cu ventil si scaun oblic Cot drept buc. 1 2 6 2.5 3.5 0.7 2.5 7 4.2

TOTAL

13.7

Verificare conditie (Rl + Z)x = (Rl + Z)r si calcul HRech (Z*rob)(Rl +Z)x [Pa] (Rl +Z)r [Pa] Z* echilibrare [Pa]

2752.1 2752.1 2752.1 8921.8 1956.5 2411.3 2659.05 2659.05

4875.3 6166.1 7465.1 15019.0 4011.3 4887.0 6592.8 7974.3

2123.2 3414.0 4713.0 6097.2 2054.8 2475.7 3933.8 5315.3

Pentru a se realiza echilibrarea hidraulica a circuitelor legate in paralel se va impune o pierdere de sarcina locala egala cu deficitul inregistrat pe fiecare circuit in parte (Z*). Echilibrarea consta in manevrarea ventilului cu ventil si scaun oblic montat pe fiecare consumator.

debit aparat [m3/h] 849,6 849.6 849.6 594 849.6 849.6 849.6 594 594

debit aparat [l/s] 236 236 236 165 236 236 236 165 165

6.835

pardoseala (2 tevi, 3 randuri x.3 si 4 randuri x.4) apa 7-120C

(Rl+Z) [Pa]

Z4875.3 6166.1 7465.1 10241.8 14647.0 15019.0 23869.0 169 180 225 443 628 405 662

d urmatoarele caracteristici:

(Rl+Z) [Pa] 4011.3 4887 6592.8 7974.3 8921.8 2752.1 2752.1 2752.1 1956.5 2411.3 2659.05 2659.05 Z 169 193 247 245 225 193 193 193 65 169 186.5 186.5