Application Guide M-0390 Syncrocloser ® Check Plus Relay

Transcript of Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse...

Page 1: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power

Application Guide

M-0390 Syncrocloser®

Check Plus Relay

Page 2: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power

SYNCROCLOSER®

LINE

Syncrocloser®

Check Plus RelayM-0390

• Panel-mounted directupgrade for G.E. IJS andSLJ, and WestinghouseCVE relays

• Accurate, independentphase, time, voltage,and ΔΔΔΔΔF functions

• Transducer and statusoutputs are standardfeatures

• Modular constructionallows cards to be removedwhile unit is installed

• Dead line/dead bus closurecapability is standard

• Does not require aseparate power source

• Complete test andcheckout from front panel

• 20 A output relaycontacts open 0.9 Ainductive at 125 V dc

• Temperature rangeof –40° to +80° C

Industry Leader Since 1969Made in the USA

Page 3: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power

–2–

M-0390 Specification

InputsLine voltage, nominal 120 V ac, 150 V ac maximum continuous. Will withstand 200 V ac for 1 sec.

Bus voltage, nominal 120 V ac, 150 V ac maximum continuous. Will withstand 200 V ac for 1 sec.

Enable Sync-Check (by closing contact*).

Open circuit voltage = 10 to 15 V dc; closed circuit current = 0.02 to 0.04 mA dc.

NOTE: One input must be greater than 100 V ac to ensure the Output Relay will close.

Enable Dead Closing (by closing contact*).

*NOTE: Requires use of gold-plated contacts located close to the unit or a permanent jumper on the backof the unit.

BurdenWhichever input voltage is high, 4 VA; other input, 1 VA.

ControlsPHASE LIMIT: 0 to 45° or 0 to 90° (switch selectable), dial accuracy 5% of full scale.

TIME LIMIT to close after PHASE LIMIT OK: 0 to 1.5 sec. or 0 to 15 sec. (switch selectable), dialaccuracy 10% of full scale.

ΔΔΔΔΔF LIMIT: 0.01 to 0.5 Hz, dial accuracy 5% of full scale.

UPPER VOLTAGE LIMIT, either input: 110 to 140 V ac, dial accuracy 5% of full scale.

LOWER VOLTAGE LIMIT, either input: 90 to 120 V ac, dial accuracy 5% of full scale.

DEAD LIMIT: 10 to 90 V ac, dial accuracy 10% of full scale.

Programmable SetpointsSwitches are provided on the Phase Verifier printed circuit board to modify the range of the PHASE LIMITand TIME LIMIT controls. The PHASE range may be set in the X1 or X2 position. In the X2 position, thefront panel PHASE LIMIT control setpoint will be multiplied by 2, and the X2 LED on the M-0390 front panelwill light to indicate a 0 to 90° PHASE LIMIT control range. The TIME range may be set in the X1 or X10position. In the X10 position, the front panel TIME LIMIT control setpoint will be multiplied by 10, and theX10 LED on the front panel will light indicating a 0 to 15 sec. TIME LIMIT range. Switches are provided onthe Voltage Verifier printed circuit board to select dead line or dead bus closing.

LED IndicatorsPHASE LIMIT OK: Phase angle is within limit setting.

PHASE X2: PHASE setting is multiplied by 2.

TIME X10: TIME setting is multiplied by 10.

OUTPUT CLOSED: Output Relay Contacts have closed in the OPERATE mode.

TEST CLOSE: Conditions are correct to close the Output Relay Contacts in the TEST mode (although theOutput Relay Contacts are disabled).

ΔΔΔΔΔF LIMIT - ΔΔΔΔΔF OK: ΔF is within the ΔΔΔΔΔF LIMIT setting.

UPPER VOLTAGE LIMIT - L OK: Line voltage is below the UPPER VOLTAGE LIMIT setting.

UPPER VOLTAGE LIMIT - B OK: Bus voltage is below the UPPER VOLTAGE LIMIT setting.

DEAD LINE/BUS DETECT - L HOT: Line voltage is above the DEAD LIMIT setting.

DEAD LINE/BUS DETECT- B HOT: Bus voltage is above the DEAD LIMIT setting.

LOWER VOLTAGE LIMIT - L OK: Line voltage is above the LOWER VOLTAGE LIMIT setting.

LOWER VOLTAGE LIMIT - B OK: Bus voltage is above the LOWER VOLTAGE LIMIT setting.

Page 4: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power

–3–

M-0390 Specification

Breaker Close Relay• Two form A output contacts rated to make 10 A at up to 250 V dc; interrupt 0.9 A, 125 V dc or

0.4 A at up to 250 V dc inductive load. Open contacts will withstand 1500 V ac for 1 minute.Contacts to ground will withstand 1500 V ac for 1 minute. Contacts may be paralleled to make 20A at up to 250 V dc.

• One normally open output contact rated to make 10 A at up to 250 V dc; interrupt 0.9 A, 125 V dcor 0.4 A at up to 250 V dc inductive load. Open contacts will withstand 1500 V ac for 1 minute.Contacts to ground will withstand 1500 V ac for 1 minute. A normally closed light duty contact isprovided that opens when either the line or bus is above 80 V ac 10 V. The contact closeswhen both the line and bus voltage drop below 50 V ac 10V. The light duty contact is rated at3 A at up to 240 V ac.

Response TimeThe M-0390 will close the breaker with proper phase angle only after the time set by the TIME LIMITcontrol, assuming the ΔF is within limits. After the timer has timed out, the M-0390 will respond to correctvoltage conditions in approximately 0.2 sec. In closing on dead line or dead bus, the phase and frequencyconditions are ignored so that the unit will close upon a voltage below set threshold in approximately 1.5sec.

Status Relay ContactsThese are light duty, form C contacts rated for 3 A at 120 V ac noninductive load. They are intendedprimarily for status interrogation by supervisory and may be used to light local lights.

Phase Status: Phase angle is within the limit setting.

Voltage Status: Line and Bus voltages are within the limit settings.

ΔΔΔΔΔF Status: ΔF is within the limit setting.

Dead Line/Dead Bus Status Option: See BREAKER CLOSE RELAY option 2 above.

Analog Output OptionsSCADA-compatible analog outputs are provided that can be connected for either voltage or currentoutputs, and may be used as transducer outputs or for interrogation of the unit while in operation.

Phase• 0 to 10 V dc = 0 to 180°, accuracy 3°. Load: 5 K or greater.

• 0 to 1.0 mA dc = 0 to 180°, accuracy 3°. Load: 10 K or less.

Other voltage/current ranges can be set by external precision resistors.

Line/Bus Voltage• 0 to 7.5 V dc = 0 to 150 V rms, accuracy 5% of full scale. Load: 3 K or greater.

• 0 to 1.0 mA dc = 0 to 150 V rms, accuracy 5% of full scale. Load: 10 K or less.

Other voltage/current ranges can be set by external precision resistors.

NOTE: The Analog Outputs are not isolated from each other. A common zero volt reference (AnalogCommon) is used for all analog outputs.

M-0292 Test Cable Set OptionThe M-0292 Test Cable Set allows the Power Supply, Phase Verifier, and Voltage Verifier / SynchronizerBoards of the M-0390 to be tested either in the field or in the laboratory. The cable set allows the boards tobe physically removed from the case while remaining electrically connected for testing.

Page 5: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power

BECKWITH ELECTRIC CO., INC.6190 - 118th Avenue North • Largo, Florida 33773-3724 U.S.A.

PHONE (727) 544-2326 • FAX (727) [email protected]

www.beckwithelectric.comISO 9001:2008

Field TestingTwo OPERATE/TEST switches, located on the M-0390 front panel, internally disable the Output Relayand disconnect the Bus and Line V.T. inputs when in the TEST position. This isolates the V.T. inputs of theM-0390 from the external wiring and ensures that the Output Relay Contact will not close while the unit isbeing tested. The M-0390 can then be checked by applying 120 V ac nominal Line and Bus inputs at therespective jacks on the front panel.

CalibrationNo circuit calibration is required; complete, solid-state design has no circuit calibration controls.

ReliabilityThe most advanced and stable solid-state components are used to achieve an accuracy and reliability ofservice not usually available for this class of relay. The reliability is enhanced by the basic stability of thecircuits; no temperature compensation is used.

Transient ProtectionInput and output circuits are protected against system transients. The M-0390 will exhibit no componentfailure or false commands when subjected to the requirements of ANSI/IEEE C37.90.1-1989, whichdefines oscillatory and fast transient surge withstand capability. All inputs and outputs will withstand1500 V ac to chassis or instrument ground for one minute. Voltage inputs are electrically isolated fromeach other, from other circuits, and from ground.

All faces of the relay, with the chassis solidly grounded, have been exposed to Radio Frequency Immunitytesting and have successfully passed with a field intensity of 20 volts per meter at typical utility frequenciesof 144 MHz, 148 MHz, 438 MHz, and at 450 MHz.

EnvironmentalTemperature Range: Stated accuracies are maintained from –40° to +80° C; analog output signals to +60°C.

Humidity: Stated accuracies are maintained at up to 85% relative humidity (non-condensing).

Fungus Resistance: A conformal printed circuit board coating inhibits fungus growth.

PhysicalSize and Mounting: The unit is designed for semiflush panel mounting, compatible with G.E. type S1 andWestinghouse type FT-21 drawout relay cases. Refer to the Application Guide for specific dimensions. Atransparent cover is supplied with the unit.

Approximate Weight: 12 lb (5.5 kg).

Approximate Shipping Weight: 14 lb (6.4 kg).

PatentU.S. Patent 4,218,625.

WarrantyThe M-0390 Syncrocloser® Check Plus Relay is covered by a five year warranty from date of shipment.

Specification is subject to change without notice.

800-0390-SP-01MC2 01/13© Beckwith Electric Co. All Rights Reserved.Printed in USA

Page 6: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power

��������������� ������������������������������� ��!���!������"�!#���!���!���������� ���$��!������!%������������������ ���&���'%���(�����$�!�%�������������������)����������#�!�����) ��� ��'����������������!���"�������� ���&���%���(�*�)�+�!��� ��������!���+���������+�����!������!����!�� ���� ��+�������������������� ���$��!'������!%�����(

DANGER! HIGH VOLTAGE

– This sign warns that the area is connected to a dangerous high voltage, and youmust never touch it.

PERSONNEL SAFETY PRECAUTIONSThe following general rules and other specific warnings throughout the manual must be followed during application,test or repair of this equipment. Failure to do so will violate standards for safety in the design, manufacture, and intendeduse of the product. Qualified personnel should be the only ones who operate and maintain this equipment. BeckwithElectric Co., Inc. assumes no liability for the customer’s failure to comply with these requirements.

– This sign means that you should refer to the corresponding section of the operation

manual for important information before proceeding.

Always Ground the Equipment

To avoid possible shock hazard, the chassis must be connected to an electrical ground. When servicingequipment in a test area, the Protective Earth Terminal must be attached to a separate ground securelyby use of a tool, since it is not grounded by external connectors.

Do NOT operate in an explosive environmentDo not operate this equipment in the presence of flammable or explosive gases or fumes. To do so wouldrisk a possible fire or explosion.

Keep away from live circuitsOperating personnel must not remove the cover or expose the printed circuit board while power is ap-plied. In no case may components be replaced with power applied. In some instances, dangerous volt-ages may exist even when power is disconnected. To avoid electrical shock, always disconnect power anddischarge circuits before working on the unit.

Exercise care during installation, operation, & maintenance proceduresThe equipment described in this manual contains voltages high enough to cause serious injury or death.Only qualified personnel should install, operate, test, and maintain this equipment. Be sure that all per-sonnel safety procedures are carefully followed. Exercise due care when operating or servicing alone.

Do not modify equipmentDo not perform any unauthorized modifications on this instrument. Return of the unit to a BeckwithElectric repair facility is preferred. If authorized modifications are to be attempted, be sure to followreplacement procedures carefully to assure that safety features are maintained.

Page 7: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power

PRODUCT CAUTIONSBefore attempting any test, calibration, or maintenance procedure, personnel must be completely familiarwith the particular circuitry of this unit, and have an adequate understanding of field effect devices. If acomponent is found to be defective, always follow replacement procedures carefully to that assure safetyfeatures are maintained. Always replace components with those of equal or better quality as shown in theParts List of the Instruction Book.

Avoid static chargeThis unit contains MOS circuitry, which can be damaged by improper test or rework procedures. Careshould be taken to avoid static charge on work surfaces and service personnel.

Use caution when measuring resistancesAny attempt to measure resistances between points on the printed circuit board, unless otherwise notedin the Instruction Book, is likely to cause damage to the unit.

Page 8: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power

800-0390-AG-MC4 01/13© 1999 Beckwith Electric Co. All Rights Reserved.Printed in USA

SStanley
Page 9: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power

This Page Left Intentionally Blank

Page 10: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 11: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 12: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 13: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 14: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 15: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 16: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 17: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 18: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 19: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 20: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 21: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 22: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 23: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 24: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 25: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power
Page 26: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power

Legal Information

PatentThe units described in this manual are covered byU.S. Patents, with other patents pending.

Buyer shall hold harmless and indemnify the Seller,its directors, officers, agents, and employees fromany and all costs and expense, damage or loss,resulting from any alleged infringementof UnitedStates Letters Patent or rights accruing thereform ortrademarks, whether federal, state, or common law,arising from the Seller’s compliance with Buyer’sdesigns, specifications, or instructions.

WarrantySeller hereby warrants that the goods which are thesubject matter of this contract will be manufacturedin a good workmanlike manner and all materialsused herein will be new and reasonably suitable forthe equipment. Seller warrants that if, during aperiod of five years from date of shipment of theequipment, the equipment rendered shall be foundby the Buyer to be faulty or shall fail to peform inaccordance with Seller’s specifications of theproduct, Seller shall at his expense correct thesame, provided, however, that Buyers shall ship theequipment prepaid to Seller’s facility. The Seller’sresponsibility hereunder shall be limited to replace-ment value of the equipment furnished under thiscontract.

Seller makes no warranties expressed or impliedother than those set out above. Seller specificallyexcludes the implied warranties of merchantibilityand fitness for a particular purpose. There are nowarranties which extend beyond the descriptioncontained herein. In no event shall Seller be liable forconsequential, exemplary, or punitive damages ofwhatever nature.

Any equipment returned for repair must be sentwith transportation charges prepaid. The equipmentmust remain the property of the Buyer. The afore-mentioned warranties are void if the value of theunit is invoiced to the Seller at the time of return.

IndemnificationThe Seller shall not be liable for any propertydamages whatsoever or for any loss or damagearising out of, connected with, or resulting fromthis contract, or from the performance or breachthereof, or from all services covered by or furnishedunder this contract.

In no event shall the Seller be liable for special,incidental, exemplary, or consequential damages,including but not limited to, loss of profits orrevenue, loss of use of the equipment or anyassociated equipment, cost of capital, cost ofpurchased power, cost of substitute equipment,facilities or services, downtime costs, or claims ordamages of customers or employees of the Buyerfor such damages, regardless of whether said claimor damages is based on contract, warranty, tortincluding negligence, or otherwise.

Under no circumstances shall the Seller be liablefor any personal injury whatsoever.

It is agreed that when the equipment furnishedhereunder are to be used or performed in connec-tion with any nuclear installation, facility, oractivity, Seller shall have no liability for anynuclear damage, personal injury, property damage,or nuclear contamination to any property located ator near the site of the nuclear facility. Buyer agreesto indemnify and hold harmless the Seller againstany and all liability associated therewith whatso-ever whether based on contract, tort, or otherwise.Nuclear installation or facility means any nuclearreactor and includes the site on which any of theforegoing is located, all operations conducted onsuch site, and all premises used for such opera-tions.

Notice:Any illustrations and descriptions by BeckwithElectric Co., Inc. are for the sole purpose ofidentification.

The drawings and/or specifications enclosed hereinare the proprietary property of Beckwith ElectricCo., Inc., and are issued in strict confidence;therefore, shall not be used as a basis of reproduc-tion of the apparatus described therein withoutwritten permission of Beckwith Electric Co., Inc.

No illustration or description contained hereinshall be construed as an express warranty ofaffirmation, promise, description, or sample, andany and all such express warranties are specificallyexcluded nor shall such illustration or descriptionimply a warranty that the product is merchantableor fit for a particular purpose. There shall be nowarranties which extend beyond those contained inthe Beckwith Electric Co., Inc. terms of sale.

All rights reserved by Beckwith Electric Co., Inc. No reproduction may be made without prior written approvalof the Company.

Page 27: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power

This Page Left Intentionally Blank

Page 28: Application Guide M-0390 Syncrocloser Check Plus Relay · Check Plus Relay M-0390 ... Westinghouse type FT-21 drawout relay cases. ... In no case may components be replaced with power

BECKWITH ELECTRIC CO., INC.6190 - 118th Avenue North • Largo, Florida 33773-3724 U.S.A.

PHONE (727) 544-2326 • FAX (727) [email protected]

www.beckwithelectric.comISO 9001:2008

800-0390-AG-MC4 01/13© 1999 Beckwith Electric Co. All Rights Reserved.Printed in USA