855-9x00/2000-000, Rogowski Coils RT 2000 · Rogowski Coils RT 2000 Ip Ø 5 Ø 5 15.7 1500 / 3000...

1
855 Series Rogowski Coils RT 2000 I p Ø 5 Ø 5 1500 / 3000 15.7 27.4 white +V s black -V s Output voltage (open output, no load) - dynamic V out = M x dI p /dt - sinusoidal signal V out = 2 x π x M x f x I p AC Example: V out = 2 x π x 0.064 μH x 50 Hz x 2000 A = 40.2 mV 34.4 Ø max 125 Short description: The Rogowski coil is a closed-air coil with non-magnetic split core, placed around a conductor or a current bar. The magnetic field produced by the AC current flowing through the conductor induces an output voltage in the coil. This measurement procedure provides galvanic isolation between the primary circuit (power) and secondary circuit (measurement). Easy placement of the Rogowski coils allows existing systems to be retrofitted without time-consuming installation or process interruption. The Rogowski coil can be used together with the 857-552 Rogowski Signal Conditioner. Features: Split-core style coil for easy installation Ø 125 mm coil aperture for non-contact measurement 1.5 m or 3 m output cable Insulated plastic case to UL 94-V0 Description Item No. Pack. Unit Rogowski coil RT 2000, 1.5 m output cable 855-9100/2000-000 3 Rogowski coil RT 2000, 3 m output cable 855-9300/2000-000 3 Approvals Conformity marking 1 Standards/Specifications IEC 61010-1:2001 (2nd edition), IEC 61010-2-032:2002, IEC 61010-031:2002 + A1:2008 Technical Data Electrical data Primary rated current I pN 2000 A rms Coil inductance (± 5 %) 190 μH Coil resistance 60 Ω (at 20 °C ambient operating temperature, typ.) Transfer ratio M 0.064 μH (WAGO provides uncalibrated coils with 5 % tolerance) Output signal Example shown above 40.2 mV at I pN = 2000 A, sinusoidal, 50 Hz (open output, no load) Max. operating frequency 500 kHz (open output, no load) Accuracy and dynamic performance: Linearity error none Temperature coefficient 30 ppm/K, related to transfer ratio M Positioning error 855-9100/2000-000: max. 0.65 % 855-9300/2000-000: max. 0,80 % (considering a primary conductor of at least Ø 15 mm perpendicular to the coil) Safety and protection: Nominal isolation voltage 300 V rms (between primary conductor and ground) Voltage for isolation test 3.5 kV rms AC / 50 Hz / 1 min Impulse withstand voltage (1.2/50 μs) 6.5 kV Adjacent contacts 6 mm / 6 mm Comparative Tracking Index (CTI, group I) 600 V (plastic parts) Degree of protection IP2X General specifications: Cable length 855-9100/2000-000: 1.5 m 855-9300/2000-000: 3 m Ambient operating temperature -10 °C ... +65 °C Storage temperature -25 °C ... +70 °C Weight 90 g Technical Data WAGO Kontakttechnik GmbH & Co. KG Subject to design changes 14.01.2015 Postfach 2880 - D-32385 Minden Hansastr. 27 - D-32423 Minden Tel.: +49(0)571/887-0 E-Mail: [email protected] Fax: +49(0)571/887-169 www.wago.com

Transcript of 855-9x00/2000-000, Rogowski Coils RT 2000 · Rogowski Coils RT 2000 Ip Ø 5 Ø 5 15.7 1500 / 3000...

Page 1: 855-9x00/2000-000, Rogowski Coils RT 2000 · Rogowski Coils RT 2000 Ip Ø 5 Ø 5 15.7 1500 / 3000 27.4 white +Vs black-Vs ... The Rogowski coil is a closed-air coil with non-magnetic

855 SeriesRogowski Coils RT 2000

Ip

Ø 5

Ø 5

1500 / 300015.7

27.4

white+Vs

black-Vs

Output voltage (open output, no load)

- dynamic Vout = M x dIp/dt

- sinusoidal signal Vout = 2 x π x M x f x Ip ACExample: Vout = 2 x π x 0.064 μH x 50 Hz x 2000 A = 40.2 mV

34.4

Øm

ax 1

25

Short description:The Rogowski coil is a closed-air coil with non-magnetic split core, placed around a conductor or a current bar.The magnetic field produced by the AC current flowing through the conductor induces an output voltage in the coil.This measurement procedure provides galvanic isolation between the primary circuit (power) and secondary circuit (measurement).Easy placement of the Rogowski coils allows existing systems to be retrofitted without time-consuming installation or process interruption.The Rogowski coil can be used together with the 857-552 Rogowski Signal Conditioner.

Features:• Split-core style coil for easy installation• Ø 125 mm coil aperture for non-contact measurement• 1.5 m or 3 m output cable• Insulated plastic case to UL 94-V0

Description Item No. Pack. Unit

Rogowski coil RT 2000, 1.5 m output cable 855-9100/2000-000 3Rogowski coil RT 2000, 3 m output cable 855-9300/2000-000 3

ApprovalsConformity marking 1

Standards/Specifications IEC 61010-1:2001 (2nd edition), IEC 61010-2-032:2002, IEC 61010-031:2002 + A1:2008

Technical DataElectrical data

Primary rated current IpN 2000 ArmsCoil inductance (± 5 %) 190 μHCoil resistance 60 Ω

(at 20 °C ambient operating temperature, typ.)

Transfer ratio M 0.064 μH(WAGO provides uncalibrated coils with 5 % tolerance)

Output signal Example shown above 40.2 mV at IpN = 2000 A, sinusoidal, 50 Hz (open output, no load)

Max. operating frequency 500 kHz (open output, no load)

Accuracy and dynamic performance:Linearity error noneTemperature coefficient 30 ppm/K, related to transfer ratio MPositioning error 855-9100/2000-000: max. 0.65 %

855-9300/2000-000: max. 0,80 %(considering a primary conductor of at least Ø 15 mm perpendicular to the coil)

Safety and protection:Nominal isolation voltage 300 Vrms

(between primary conductor and ground)Voltage for isolation test 3.5 kVrms AC / 50 Hz / 1 minImpulse withstand voltage (1.2/50 μs) 6.5 kVAdjacent contacts 6 mm / 6 mmComparative Tracking Index (CTI, group I) 600 V (plastic parts)Degree of protection IP2X

General specifications:Cable length 855-9100/2000-000: 1.5 m

855-9300/2000-000: 3 mAmbient operating temperature -10 °C ... +65 °CStorage temperature -25 °C ... +70 °CWeight 90 g

Technical Data

WAGO Kontakttechnik GmbH & Co. KGSubject to design changes 14.01.2015

Postfach 2880 - D-32385 Minden Hansastr. 27 - D-32423 Minden