03 Generator Selection Tool - GENSIZE Bob Patrick Oct08 Form) [Compatibility Mode]

Post on 21-Apr-2015

130 views 2 download

Transcript of 03 Generator Selection Tool - GENSIZE Bob Patrick Oct08 Form) [Compatibility Mode]

Cummins Power Generation

P T i i M d l 7Power Training Module 7

Generator Sizing

Bob PatrickOctober 2008

Sizing the Genset for Motors….

Two Factors – must have1 Available additional engine torque to support both1. Available additional engine torque to support both

the existing load plus accelerate the motor up to full speed within the spec limits.p p(Acceleration Torque = advised Nm x rpm x 2π/60 = watts)

2 Alt t bilit t th t i h2. Alternator capability to overcome the motor inrush and sustain the voltage within the spec limits.

2

DOL Starters

REN

T

600Current

Power Factor

Direct On-Line (DOL) Start

High Locked Rotor Current (kVA) POW

ER

, CU

RR

1.0

R (L

AG

GIN

G)

g ( )

Shown for 100% Rated VoltageN

T TO

RQ

UE,

P

OW

ER F

ACTO

R

Starting PF 0.2 to 0.4 for 3 Ø Motors

Higher Starting Requirements

PER

CEN

100 0.2

PO

Motor Torque

3

g g q

PERCENT MOTOR RATED SPEED20 40 60 80 100

Load Torque0

Star-delta Starting…Typical kW demand of motor…

Reduced Starting ImpactReduced Starting Impact

Watch out for the transition (kVA)

Potential start failure if alternator cannot sustain voltage in transition. Typical kVA demand of motor…ca ot susta o tage t a s t o

4

Soft Starting…

Motor Response for Soft Starter

5

Regenerative Load

Reverse power needs to be considered.

6

Regenerative LoadStage 1:-Stage 1:Genset Supplies Site Loads

Stage 2:-Lift M t P dLift Motor Produces Reverse Power 200kW

100kW Load Bank Removes Risk of Reverse Power

7

Transients

Step Loading the Generator

•Apply Load in Increments

•Apply Large Motor Loads First

•Limit Voltage and Frequency dip

•Ultimately reduce genset size

Step Starting Sequence

8

Step Starting Sequence

ISO 8528 - 5

ISO 8528 ifi d i d fISO 8528 specifies design and performance criteria of Reciprocating Internal Combustion (RIC) engine and an Alternating Current (AC)(RIC) engine and an Alternating Current (AC) generator when operating as a unit.

9

Voltage Transients….ISO 8528-5 Transient Requirements

10

Frequency Transients….ISO 8528-5 Transient Requirements

11

Transients….ISO 8528-5 Performance Classes

Class G1

This applies to generating set applications where the connected loads are such that only basic parameters of voltage and frequency need to be specifiedvoltage and frequency need to be specified.

EXAMPLE General-purpose applications (lighting and other simple electrical loads)simple electrical loads).

12

Transients….ISO 8528-5 Performance Classes

Class G2

This applies to generating set applications where its voltage characteristics are very similar to those for the commercial public utility electrical power system with which it operatespublic utility electrical power system with which it operates. When load changes occur, there may be temporary but acceptable deviations of voltage and frequency.

EXAMPLE Lighting systems, pumps, fans and hoists.

13

Transients….ISO 8528-5 Performance Classes

An example of Class G2 voltage and frequency requirements:

Transient Frequency Dip </= 10%Frequency Recovery Time </= 5 SecsSteady State Voltage Deviation </= +/- 2.5%Transient Voltage Dip </= 20%Voltage Recovery Time </= 6 Secs

14

Transients….ISO 8528-5 Performance Classes

Class G3

This applies to applications where the connected equipment makes severe demands on the stability and level of the frequency voltage and waveform characteristics of thefrequency, voltage and waveform characteristics of the electrical power supplied by the generating set.

EXAMPLE Telecommunications and thyristor-controlledEXAMPLE Telecommunications and thyristor-controlled loads. It should be remembered that both rectifier and thyristor-controlled loads may need special consideration with respect to their effect on generator-voltage waveform.

15

p g g

Transients….ISO 8528-5 Performance Classes

Class G4

This applies to applications where the demands made on the stability and level of the frequency, voltage and waveform characteristics of the electrical power supplied by thecharacteristics of the electrical power supplied by the generating set are exceptionally severe.

EXAMPLE Data-processing equipment or computer systemsEXAMPLE Data-processing equipment or computer systems.

16

Voltage Transients….

L k d R t C f

Locked Rotor Curve

Locked Rotor Curve for1400kVA alternator

Used to aid sizingg

Approx 14% dip at1000kVA (depends onvoltage)voltage)

Allow 0.5% Volts Dip forevery 1% Freq Dip

17

Sizing….

Can be very simple – a simple addition with diversity, etc., or...y, ,More complex when considering difficult loads and load step sequencing.

Difficult loads: Electric motors, UPS, Lighting, Medical equipment

18

Medical equipment

Power SuiteCummins Power Suite.lnk

Cummins Sizing Tool Gensize (To calculate your generator requirements)generator requirements)

Has a database using CPG product test dataHas a database using CPG product test data

19

Power Suite Demonstration

Any Questions before we move onAny Questions before we move on

Bob Patrick

20

Bob PatrickOctober 2008

GenSize™ UpdatePSG/P l TPSG/Proposals Team

Part IIb – Training….

Bob PatrickO t b 2008October 2008

Installing Power Suite Central UpdateInstall Power Suite 4.0 From CD

Auto update from central database,http://www.cumminspower.com/na/technical/powersuite/webcenter/

Central database replaces

PC running Power Suite V4 0

original database

Power Suite Central Library

22

PC running Power Suite V4.0y& Update CD

Updates Via Internet

Auto-updates from central database,p ,http://www.cumminspower.com/na/technical/powersuite/webcenter/

Select: Updated files for Europe, Middle East and Africa.

23

Updates Via InternetAuto Updates –GenSize™ for MSWindows

24

Cummins Power Suite

Opening Screen: Create New Project

With Project highlightedClick on “Open”

25

• The opening screen allows import previous or create new project

G i M i S S tti U Gensize Main Screen: Setting Up Project Parameters

Current Project ParametersCurrent Project Parameters

26

• Expand New Project in left column

Gensize Main Screen: Setting Up Project Parameters

Shows current loadsand steps available

27

G i M i S S tti U Gensize Main Screen: Setting Up Project Parameters

Click on “EditClick on Edit Project”

28

• Once expanded right click on project and select “Edit Project”

Gensize Main Screen: Setting Up Gensize Main Screen: Setting Up Project Parameters

Select Parameters tab

29

• Project parameters box will appear

Gensize Main Screen: Setting Up Project Parameters

Current Project Parameters

30

• Set the required project parameters

Gensize Main Screen: Setting Up Project Parameters

Once complete, click “OK” to continue

31

Gensize Main Screen: Creating Loads

Add lighting load by clicking

th b lbon the bulb

32

• Select load type from toolbar

Gensize Main Screen: Creating Loads

Enter 100kW lighting loadg g

Click “Next” for more options

33

• Example shows 3 phase 100 kW fluorescent lights

Gensize Main Screen: Creating Loads

Shows requirements for 100kW light load

Click “Finish” to complete load

34

• Review Load Requirements

Gensize Main Screen: Creating Loads

Light load nowLight load now created

Whilst highlighted, the light load

tparameters appear

35

• Lighting load appears in left pane

Gensize Main Screen: Creating Loads

Light Load can now be dragged in to step 1gg p

36

• Apply load to desired load step

Gensize Main Screen: Creating Loads

Project can now be sized by clicking the

“Size Project ”

Step 1 showing Light Load

jbutton

37

• Minimum Requirements For Sizing Project

Gensize Main Screen: Sizing ProjectGensize Main Screen: Sizing Project

38

• Gensize calculating project requirements to find match

Reports: Recommended Generator Model

RecommendedModel

Project parameters Performance Vs Requirements

39

R t R d d G t Reports: Recommended Generator Model

RecommendedModelModel

L d tPerformance Vs

Load parameters Requirements

40

R t R d d G t Reports: Recommended Generator Model

RecommendedModel

G t C fiPerformance Vs

Model

Generator Config Requirements

41

R t R d d G t Reports: Recommended Generator Model

Click for full genset report

42

• Changing the report type

R t R d d G t Reports: Recommended Generator Model

43

• Printable Genset Report

R t R d d G t Reports: Recommended Generator Model

Close Report

44

R t R d d G t Reports: Recommended Generator Model

Switch to Table View

45

Reports: Recommended Generator Reports: Recommended Generator Model

46

• Table View Used For Cross Referencing Models

R t R d d G t Reports: Recommended Generator Model

Switch to library

47

y

Central Library CD

Exit Library toExit Library to return Gensize

48

• Shows recommended model and technical data

Gensize Main Screen: Adding Load Steps

To add single load step click here

49

• Extra load steps can be added at any time

Gensize Main Screen: Adding Load Stepsp

Second Load Stepp

50

G i M i S Addi L d Gensize Main Screen: Adding Load Steps

You can define the number of steps

required

51

• There are 2 ways to add extra load steps

Gensize Main Screen: Adding Load Steps

52

• Specify number of required load steps

Gensize Main Screen: Adding Load Steps

53

• New loads can then be added to each step

Gensize Main Screen: Adding Load Steps

Here we will add 400HP motor400HP motor

Cli k “N t” fClick “Next” for more options

54

• New loads can then be added to each step

Gensize Main Screen: Adding Load Steps

Click “Finish”

55

G SGensize Main Screen: Adding Load Steps

New motor load added

Motor load dragged to ggStep 2

56

• Adding the new load to Step 2

G SGensize Main Screen: Adding Load Steps

57

• Sized generator with 2 load steps

G i M i S Ch Gensize Main Screen: Change Quantity

58

• Quantities of each load can be changed

Gensize Main Screen: Change Quantity

Quantity changes to 2y g

59

• Quantities of each load can be changed

G i M i S S i Gensize Main Screen: Saving Projects

Project can be saved at any time using

the File menu

60

G i M i S S i Gensize Main Screen: Saving Projects

File Name

Directory

File Name

61

• Default projects directory

Gensize Main Screen: Saving Projects

62

• Check for confirmation before closing!

Workshop

Lighting LoadsGeneral LoadsGeneral LoadsUPS LoadsMotor LoadsMotor LoadsRound-Up

63

LIGHTING LOADS

Power input

Lighting requirement

Type of load

Requirement for generator

64

LIGHTING LOADS

Power factor requirements

65

GENERAL LOADS

Power inputs

PowerPower requirements

Requirement for generator

66

GENERAL LOADS

Both Start and run power factors must be entered

67

UPS LOAD

UPS Output power

UPS requirement

UPS type

Requirement for generator

68

UPS LOAD

UPS characteristics hi h i i lwhich are crittical.

69

MOTOR LOADS

Motor shaft power

Motor requirement

Motor type

Requirement for generator

70

MOTOR LOADS

Motor starting type

Motor starting characteristics

Motor r nningMotor running characteristics

71

Thank you for your time

Any Questions

Bob Patrick

72

Bob PatrickOctober 2008