SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

33
SmartLetLoose/ONE Fire Extinction Board

Transcript of SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Page 1: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

SmartLetLoose/ONEFire Extinction Board

Page 2: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

SmartLetLoose/ONE

Extinction Board Wiring

Extinction Board Wiring

SmartLine panel

Page 3: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Extinction Board Wiring

SmartLight panel

SmartLetLoose/ONE

Page 4: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Initial Wirings

Initial Wirings

Balance MAN-EXT terminals with a 47kΩ resistance

Balance STOP_EXT terminals with a 47kΩ resistance

Balance PRESS terminals with a 47kΩ resistance

SmartLetLoose/ONE

Page 5: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Initial Wirings

Initial Wirings

SmartLetLoose/ONE

If terminals aren’t balanced panel displays:

Fault 01/03Open I/OManualExtinguishExtin.module

Fault 02/03Open I/OLock extinguishExtin.module

Fault 03/03Open I/OPressure switchExtin.module

Page 6: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Initial Wirings

Initial Wirings

Balance PRE-EXT terminals with a 47kΩ resistance

Balance RELEASED terminals with a 47kΩ resistance

SmartLetLoose/ONE

Page 7: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Initial Wirings

Initial Wirings

SmartLetLoose/ONE

If terminals aren’t balancedpanel displays:

Fault 01/02Open I/OPre-extinguishExtin.module.

Fault 02/02Open I/OReleasedExtin.module

Page 8: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Electrovalve Wiring

Electrovalve Wiring

Electrovalve24V

SmartLetLoose/ONE

Page 9: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

SmartLetLoose/ONE

If terminals aren’t connectedpanel displays:

Fault 01/01Open I/OValve outputExtin.module

Electrovalve Wiring

Electrovalve Wiring

Page 10: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Manual Extinguish

Manual Extinguish

Connect a callpoint or a generic NO contact to have a manual Extinguish input

NO contact

15kΩ resistance47kΩ resistance

SmartLetLoose/ONE

Page 11: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Stop-Extinguish

Stop-Extinguish

Connect a callpoint or a generic NO contact to have a manual Stop-Extinguish input

NO contact

15kΩ resistance47kΩ resistance

SmartLetLoose/ONE

Page 12: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Stop-Extinguish

Stop-Extinguish

If fire extinguishant system has been stopped, “R” terminal closes to GND:

it can activate a device (eg a led)

+24V

+-

Device

SmartLetLoose/ONE

Page 13: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Pressure Switch

Pressure Switch

A generic NO contact connected to PRESS teminals can be used as:

NO contact

15kΩ resistance47kΩ resistance

SmartLetLoose/ONE

- Supervisory: to monitor gas pressure

- From pressure: to confirm that gas cylinders are empty- From flow detector: to confirm that gas has be released

Page 14: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Pre-Extinguish

Pre-Extinguish

PRE-EXT output (terminals 10-11) is activated on Pre-Extinguish: it can activate some devices

SmartLetLoose/ONE

47 kΩ End of Line resistance on the last device

Page 15: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Pre-Extinguish

SmartLetLoose/ONE

Fault 01/01Short I/OPre-extinguishExtin.module

If panel displays “Short I/O Pre-Extinguish” it will need connect a diode in series (if devices haven’t it)

47 kΩ End of Line resistance on the last device

Page 16: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Released

Released

RELEASED output (terminals 12-13) is activated when gas extinguishant is released:

it can activate some devices.

SmartLetLoose/ONE

47 kΩ End of Line resistance on the last device

Page 17: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Released

SmartLetLoose/ONE

Fault 01/01Short I/OReleasedExtin.module

If panel displays “Short I/O Released” it will need connect a diode in series (if devices haven’t it)

47 kΩ End of Line resistance on the last device

Page 18: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Extinction Board Configuration

Extinction Board have to be configured from panel

SmartLetLoose/ONE

Extinction Board Configuration

Page 19: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Extinction Board Configuration

Extinction Board have to be configured from panel

SmartLine Panel

Enable panel programming phase

SmartLetLoose/ONE

Page 20: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Extinction Board Configuration

Extinction Board have to be configured from panel

SmartLine PanelControl Panel

IN PROGRAMMINGVer: 2.03

01/01/12 17:45

SettingsDisablementMaintenanceProgramming

ConfigurationProgr. ZoneProgr. OutputProgr. Timer

Acquire int.busAcquire ext.bus

Current DevicesExtin.module OExpansion OOk to execute

Current DevicesExtin.module 1Expansion OOk to execute

SmartLetLoose/ONE

Page 21: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Extinction Board Configuration

Extinction Board have to be configured from panel

SmartLight Panel

Enable panel programming phase

SmartLetLoose/ONE

Page 22: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Extinction Board Configuration

Extinction Board have to be configured from panel

SmartLight PanelPanel

IN PROGRAMMINGVer: 2.02

01/01/12 17:45

SettingsDisablementMaintenaceProgramming

ConfigurationProgr.PointProgr.ZoneProgr. Timer

LoopBus

Extinguish board OSmart Level ORepeater OOk to continue

Extinguish board 1Smart Level ORepeater OOk to continue

SmartLetLoose/ONE

Page 23: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Programming

Enable panel programming phase

SmartLetLoose/ONE

Programming

Extinction board is programmed the same way both from SmartLine panel and from SmartLight panel

Page 24: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Programming

Control PanelIN PROGRAMMING

Ver: 2.0301/01/12 17:45

SettingsDisablementMaintenanceProgramming

Progr. OutputProgr. TimerProgr. HolidayExtinguish

Zone mask:Zone 01 YESZone 02 YESZone 03 YES

Mode:At least 2

SmartLetLoose/ONE

YES: Zone activates extinguish commands NO: Zone doesn’t activate extinguish commandsAt least 1: The extinguishant gas release will activate if at least one of the selected zones go into alarm status At least 2: The extinguishant gas release will activate if at least two of the selected zones go into alarm statusAll zones: The extinguishant gas release will activate if all selected zones go into alarm status

Page 25: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Programming

Control PanelIN PROGRAMMING

Ver: 2.0301/01/12 17:45

SettingsDisablementMaintenanceProgramming

Progr. OutputProgr. TimerProgr. HolidayExtinguish

Zone mask:Zone 01 YESZone 02 YESZone 03 YES

Confirm exting.Do not confirm

SmartLetLoose/ONE

Do not confirm: extinguishment module doesn’t await confirmationWait for press.: extinguishment module awaits confirmation from pressure switchWait for flow: extinguishment module awaits confirmation from flow detector

Page 26: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Programming

Control PanelIN PROGRAMMING

Ver: 2.0301/01/12 17:45

SettingsDisablementMaintenanceProgramming

Progr. OutputProgr. TimerProgr. HolidayExtinguish

Zone mask:Zone 01 YESZone 02 YESZone 03 YES

Pressure switchSupervisory

SmartLetLoose/ONE

Supervisory: PRESS input monitors gas pressure From pressure: PRESS input confirm that gas cylinders are emptyFrom flow det.: PRESS input confirm that gas has be released

Page 27: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Programming

Control PanelIN PROGRAMMING

Ver: 2.0301/01/12 17:45

SettingsDisablementMaintenanceProgramming

Progr. OutputProgr. TimerProgr. HolidayExtinguish

Zone mask:Zone 01 YESZone 02 YESZone 03 YES

Pressure switchSupervisory

SmartLetLoose/ONE

Other programming

T.pre-extinct00 min. 10 secPre-extinction time

T. extinguish00 min. 02 sec

T. extinguish

Extinguish time

If it is undefined, valve switch will be open until reset T. pre-ext. man

00 min. 00 secManual Pre-extinction time

T.Confirm ext.00 min. 05 sec

Delay between valve switch activation and confirmation

T.Gap discharge00 min. 05 sec

Pause between one gas discharge and another in the event

of non-confirmation

Page 28: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Advanced Programming

Advanced Programming

SmartLetLoose/ONE

- Lock extinguish when the room has open doors

SmartLine Panel

Page 29: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Advanced Programming

SmartLetLoose/ONE

Connect the series of NC doors contact between “I/O” and “-” terminals

Page 30: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Advanced Programming

SmartLetLoose/ONE

Program I/O Line as “Extinction control Input”

“Stop Extinction”

“”Swap Alarm-Fault bands”

Page 31: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Advanced Programming

Control PanelIN PROGRAMMING

Ver: 2.0301/01/12 17:45

ConfigurationProgr. ZoneProgr. OutputProgr. Timer

SmartLetLoose/ONE

- Lock extinguish when the room has open doors

SmartLine panel

Programming from panel

01 <Zone 0102 <Zone 0203 <Zone 0304 <Zone 04

SettingsDisablementMaintenanceProgramming

10 min. 00 sec.Filter time 30Detection lineI/O line

<Zone 01>I.EXTINGUISHDisable exting.NC input NO

Program “I.EXTINGUISH”

Page 32: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Advanced Programming

Control PanelIN PROGRAMMING

Ver: 2.0301/01/12 17:45

ConfigurazioneProgr. ZoneProgr. UsciteProgr. Timer

SmartLetLoose/ONE

- Lock extinguish when the room has open doors 01 <Zone 01

02 <Zone 0203 <Zone 0304 <Zone 04

SettingsDisablementMaintenanceProgramming

10 min. 00 sec.Filter time 30Detection lineI/O line

<Zone 01>I.EXTINGUISHLock extinguishNC input NO

Program “Lock extinguish”

SmartLine panel

Page 33: SmartLetLoose/ONE Fire Extinction Board. SmartLetLoose/ONE Extinction Board Wiring SmartLine panel.

Advanced Programming

SmartLetLoose/ONE

- Lock extinguish when the room has open doors

<Zone 01>I.EXTINGUISHLock extinguishNC input YESProgram “NC input YES”

SmartLine panel

Control PanelIN PROGRAMMING

Ver: 2.0301/01/12 17:45

ConfigurazioneProgr. ZoneProgr. UsciteProgr. Timer

01 <Zone 0102 <Zone 0203 <Zone 0304 <Zone 04

SettingsDisablementMaintenanceProgramming

10 min. 00 sec.Filter time 30Detection lineI/O line