SmartLetLoose/ONEFire Extinction Board
SmartLetLoose/ONE
Extinction Board Wiring
Extinction Board Wiring
SmartLine panel
Extinction Board Wiring
SmartLight panel
SmartLetLoose/ONE
Initial Wirings
Initial Wirings
Balance MAN-EXT terminals with a 47kΩ resistance
Balance STOP_EXT terminals with a 47kΩ resistance
Balance PRESS terminals with a 47kΩ resistance
SmartLetLoose/ONE
Initial Wirings
Initial Wirings
SmartLetLoose/ONE
If terminals aren’t balanced panel displays:
Fault 01/03Open I/OManualExtinguishExtin.module
Fault 02/03Open I/OLock extinguishExtin.module
Fault 03/03Open I/OPressure switchExtin.module
Initial Wirings
Initial Wirings
Balance PRE-EXT terminals with a 47kΩ resistance
Balance RELEASED terminals with a 47kΩ resistance
SmartLetLoose/ONE
Initial Wirings
Initial Wirings
SmartLetLoose/ONE
If terminals aren’t balancedpanel displays:
Fault 01/02Open I/OPre-extinguishExtin.module.
Fault 02/02Open I/OReleasedExtin.module
Electrovalve Wiring
Electrovalve Wiring
Electrovalve24V
SmartLetLoose/ONE
SmartLetLoose/ONE
If terminals aren’t connectedpanel displays:
Fault 01/01Open I/OValve outputExtin.module
Electrovalve Wiring
Electrovalve Wiring
Manual Extinguish
Manual Extinguish
Connect a callpoint or a generic NO contact to have a manual Extinguish input
NO contact
15kΩ resistance47kΩ resistance
SmartLetLoose/ONE
Stop-Extinguish
Stop-Extinguish
Connect a callpoint or a generic NO contact to have a manual Stop-Extinguish input
NO contact
15kΩ resistance47kΩ resistance
SmartLetLoose/ONE
Stop-Extinguish
Stop-Extinguish
If fire extinguishant system has been stopped, “R” terminal closes to GND:
it can activate a device (eg a led)
+24V
+-
Device
SmartLetLoose/ONE
Pressure Switch
Pressure Switch
A generic NO contact connected to PRESS teminals can be used as:
NO contact
15kΩ resistance47kΩ resistance
SmartLetLoose/ONE
- Supervisory: to monitor gas pressure
- From pressure: to confirm that gas cylinders are empty- From flow detector: to confirm that gas has be released
Pre-Extinguish
Pre-Extinguish
PRE-EXT output (terminals 10-11) is activated on Pre-Extinguish: it can activate some devices
SmartLetLoose/ONE
47 kΩ End of Line resistance on the last device
Pre-Extinguish
SmartLetLoose/ONE
Fault 01/01Short I/OPre-extinguishExtin.module
If panel displays “Short I/O Pre-Extinguish” it will need connect a diode in series (if devices haven’t it)
47 kΩ End of Line resistance on the last device
Released
Released
RELEASED output (terminals 12-13) is activated when gas extinguishant is released:
it can activate some devices.
SmartLetLoose/ONE
47 kΩ End of Line resistance on the last device
Released
SmartLetLoose/ONE
Fault 01/01Short I/OReleasedExtin.module
If panel displays “Short I/O Released” it will need connect a diode in series (if devices haven’t it)
47 kΩ End of Line resistance on the last device
Extinction Board Configuration
Extinction Board have to be configured from panel
SmartLetLoose/ONE
Extinction Board Configuration
Extinction Board Configuration
Extinction Board have to be configured from panel
SmartLine Panel
Enable panel programming phase
SmartLetLoose/ONE
Extinction Board Configuration
Extinction Board have to be configured from panel
SmartLine PanelControl Panel
IN PROGRAMMINGVer: 2.03
01/01/12 17:45
SettingsDisablementMaintenanceProgramming
ConfigurationProgr. ZoneProgr. OutputProgr. Timer
Acquire int.busAcquire ext.bus
Current DevicesExtin.module OExpansion OOk to execute
Current DevicesExtin.module 1Expansion OOk to execute
SmartLetLoose/ONE
Extinction Board Configuration
Extinction Board have to be configured from panel
SmartLight Panel
Enable panel programming phase
SmartLetLoose/ONE
Extinction Board Configuration
Extinction Board have to be configured from panel
SmartLight PanelPanel
IN PROGRAMMINGVer: 2.02
01/01/12 17:45
SettingsDisablementMaintenaceProgramming
ConfigurationProgr.PointProgr.ZoneProgr. Timer
LoopBus
Extinguish board OSmart Level ORepeater OOk to continue
Extinguish board 1Smart Level ORepeater OOk to continue
SmartLetLoose/ONE
Programming
Enable panel programming phase
SmartLetLoose/ONE
Programming
Extinction board is programmed the same way both from SmartLine panel and from SmartLight panel
Programming
Control PanelIN PROGRAMMING
Ver: 2.0301/01/12 17:45
SettingsDisablementMaintenanceProgramming
Progr. OutputProgr. TimerProgr. HolidayExtinguish
Zone mask:Zone 01 YESZone 02 YESZone 03 YES
Mode:At least 2
SmartLetLoose/ONE
YES: Zone activates extinguish commands NO: Zone doesn’t activate extinguish commandsAt least 1: The extinguishant gas release will activate if at least one of the selected zones go into alarm status At least 2: The extinguishant gas release will activate if at least two of the selected zones go into alarm statusAll zones: The extinguishant gas release will activate if all selected zones go into alarm status
Programming
Control PanelIN PROGRAMMING
Ver: 2.0301/01/12 17:45
SettingsDisablementMaintenanceProgramming
Progr. OutputProgr. TimerProgr. HolidayExtinguish
Zone mask:Zone 01 YESZone 02 YESZone 03 YES
Confirm exting.Do not confirm
SmartLetLoose/ONE
Do not confirm: extinguishment module doesn’t await confirmationWait for press.: extinguishment module awaits confirmation from pressure switchWait for flow: extinguishment module awaits confirmation from flow detector
Programming
Control PanelIN PROGRAMMING
Ver: 2.0301/01/12 17:45
SettingsDisablementMaintenanceProgramming
Progr. OutputProgr. TimerProgr. HolidayExtinguish
Zone mask:Zone 01 YESZone 02 YESZone 03 YES
Pressure switchSupervisory
SmartLetLoose/ONE
Supervisory: PRESS input monitors gas pressure From pressure: PRESS input confirm that gas cylinders are emptyFrom flow det.: PRESS input confirm that gas has be released
Programming
Control PanelIN PROGRAMMING
Ver: 2.0301/01/12 17:45
SettingsDisablementMaintenanceProgramming
Progr. OutputProgr. TimerProgr. HolidayExtinguish
Zone mask:Zone 01 YESZone 02 YESZone 03 YES
Pressure switchSupervisory
SmartLetLoose/ONE
Other programming
T.pre-extinct00 min. 10 secPre-extinction time
T. extinguish00 min. 02 sec
T. extinguish
Extinguish time
If it is undefined, valve switch will be open until reset T. pre-ext. man
00 min. 00 secManual Pre-extinction time
T.Confirm ext.00 min. 05 sec
Delay between valve switch activation and confirmation
T.Gap discharge00 min. 05 sec
Pause between one gas discharge and another in the event
of non-confirmation
Advanced Programming
Advanced Programming
SmartLetLoose/ONE
- Lock extinguish when the room has open doors
SmartLine Panel
Advanced Programming
SmartLetLoose/ONE
Connect the series of NC doors contact between “I/O” and “-” terminals
Advanced Programming
SmartLetLoose/ONE
Program I/O Line as “Extinction control Input”
“Stop Extinction”
“”Swap Alarm-Fault bands”
Advanced Programming
Control PanelIN PROGRAMMING
Ver: 2.0301/01/12 17:45
ConfigurationProgr. ZoneProgr. OutputProgr. Timer
SmartLetLoose/ONE
- Lock extinguish when the room has open doors
SmartLine panel
Programming from panel
01 <Zone 0102 <Zone 0203 <Zone 0304 <Zone 04
SettingsDisablementMaintenanceProgramming
10 min. 00 sec.Filter time 30Detection lineI/O line
<Zone 01>I.EXTINGUISHDisable exting.NC input NO
Program “I.EXTINGUISH”
Advanced Programming
Control PanelIN PROGRAMMING
Ver: 2.0301/01/12 17:45
ConfigurazioneProgr. ZoneProgr. UsciteProgr. Timer
SmartLetLoose/ONE
- Lock extinguish when the room has open doors 01 <Zone 01
02 <Zone 0203 <Zone 0304 <Zone 04
SettingsDisablementMaintenanceProgramming
10 min. 00 sec.Filter time 30Detection lineI/O line
<Zone 01>I.EXTINGUISHLock extinguishNC input NO
Program “Lock extinguish”
SmartLine panel
Advanced Programming
SmartLetLoose/ONE
- Lock extinguish when the room has open doors
<Zone 01>I.EXTINGUISHLock extinguishNC input YESProgram “NC input YES”
SmartLine panel
Control PanelIN PROGRAMMING
Ver: 2.0301/01/12 17:45
ConfigurazioneProgr. ZoneProgr. UsciteProgr. Timer
01 <Zone 0102 <Zone 0203 <Zone 0304 <Zone 04
SettingsDisablementMaintenanceProgramming
10 min. 00 sec.Filter time 30Detection lineI/O line