Multi-turn actuator Motor
Type
Outputspeed[rpm]
Max. torque [Nm] Motor type
Nominal power1) PN [kW]
Speed[rpm]
Nominal current2)
IN [A]
Max. current3)
Imax [A]
Starting currentIA [A] cos ϕ
Overcurrent prot. device setting [A]
AUMA power class switchgears
Contactor Thyristor
SAEx07.2
4.8
30
VDX0063-4-0.02 0.02 1,680 0.3 0.2 0.7 0.40 0.2 A1 –6.7 0.3 0.3 0.7 0.40 0.3 A1 –9.6 VDX0063-4-0.04 0.04 1,680 0.3 0.3 0.7 0.50 0.3 A1 –13 0.3 0.4 0.7 0.50 0.4 A1 –19 VDX0063-2-0.06 0.06 3,360 0.4 0.4 1.4 0.57 0.4 A1 –26 0.4 0.5 1.4 0.57 0.5 A1 –38 ADX0063-4-0.10 0.10 1,680 0.7 0.7 1.7 0.42 0.7 A1 –54 0.7 0.7 1.7 0.42 0.7 A1 –75 ADX0063-2-0.20 0.20 3,360 0.6 0.9 3.2 0.60 0.9 A1 –108 0.6 0.9 3.2 0.60 0.9 A1 –150 ADX0063-2-0.30 0.30 3,360 0.7 1.1 3.2 0.70 1.1 A1 –216 25 0.7 1.2 3.2 0.70 1.2 A1 –
SAEx07.6
4.8
60
VDX0063-4-0.03 0.03 1,680 0.3 0.3 0.7 0.43 0.3 A1 –6.7 0.3 0.3 0.7 0.43 0.3 A1 –9.6 VDX0063-4-0.06 0.06 1,680 0.4 0.5 1.2 0.38 0.5 A1 –13 0.4 0.5 1.2 0.38 0.5 A1 –19 VDX0063-2-0.12 0.12 3,360 0.5 0.7 2.2 0.52 0.7 A1 –26 0.5 0.7 2.2 0.52 0.7 A1 –38 ADX0063-4-0.20 0.20 1,680 1.2 1.4 3.3 0.42 1.4 A1 –54 1.2 1.5 3.3 0.42 1.5 A1 –75 ADX0063-2-0.40 0.40 3,360 1.2 1.7 6.5 0.53 1.7 A1 –108 1.2 1.8 6.5 0.53 1.8 A1 –150 ADX0063-2-0.50 0.50 3,360 1.2 2.2 6.5 0.62 2.2 A1 –216 50 1.2 2.3 6.5 0.62 2.3 A1 –
SAEx10.2
4.8
120
VDX0071-4-0.06 0.06 1,680 0.4 0.4 1.5 0.40 0.4 A1 –6.7 0.4 0.4 1.5 0.40 0.4 A1 –9.6 VDX0071-4-0.12 0.12 1,680 0.7 0.8 2.2 0.40 0.8 A1 –13 0.7 0.9 2.2 0.40 0.9 A1 –19 VDX0071-2-0.25 0.25 3,360 0.9 1.1 3.3 0.52 1.1 A1 –26 0.9 1.3 3.3 0.52 1.3 A1 –38 ADX0071-4-0.40 0.40 1,680 1.8 1.9 6.2 0.42 1.9 A1 –54 1.8 2.2 6.2 0.42 2.2 A1 –75 ADX0071-2-0.70 0.70 3,360 2.2 2.6 12 0.54 2.6 A1 –108 2.2 2.9 12 0.54 2.9 A1 –150 ADX0071-2-1.00 1.00 3,360 2.5 3.8 12 0.64 3.8 A1 –216 100 2.5 4.0 12 0.64 4.0 A1 –
SAEx14.2
4.8
250
VDX0090-4-0.12 0.12 1,680 0.4 0.6 2.0 0.60 0.6 A1 –6.7 0.4 0.7 2.0 0.60 0.7 A1 –9.6 VDX0090-4-0.25 0.25 1,680 0.7 1.2 3.8 0.60 1.2 A1 –13 0.7 1.2 3.8 0.60 1.2 A1 –19 VDX0090-2-0.45 0.45 3,360 1.1 2.2 6.5 0.64 2.2 A1 –26 1.1 2.5 6.5 0.64 2.5 A1 –38 ADX0090-4-0.75 0.75 1,680 1.8 2.9 12 0.62 2.9 A1 –54 1.8 3.6 12 0.62 3.6 A1 –75 ADX0090-2-1.40 1.40 3,360 3.4 5.1 28 0.60 5.1 A2 –108 3.4 6.5 28 0.60 6.5 A2 –150 ADX0090-2-1.80 1.80 3,360 3.9 8.0 28 0.65 8.0 A2 –216 200 3.9 8.0 28 0.65 8.0 A2 –
SAEx14.6
4.8
500
VDX0090-4-0.20 0.20 1,680 0.7 0.7 3.8 0.54 0.7 A1 –6.7 0.7 0.7 3.8 0.54 0.7 A1 –9.6 VDX0090-4-0.40 0.40 1,680 1.2 2.2 6.8 0.56 2.2 A1 –13 1.2 2.5 6.8 0.56 2.5 A1 –19 VDX0090-2-0.80 0.80 3,360 2.6 3.6 13 0.51 3.6 A1 –26 2.6 4.0 13 0.51 4.0 A1 –38 ADX0090-4-1.60 1.60 1,680 3.9 5.5 28 0.57 5.5 A2 –54 3.9 6.5 28 0.57 6.5 A2 –75 ADX0090-2-3.00 3.00 3,360 6.5 9.5 42 0.60 9.5 A2 –108 6.5 12 42 0.60 12 A2 –150 ADX0090-2-3.30 3.30 3,360 6.9 15 42 0.65 13 A2 –216 400 6.9 16 42 0.65 13 A2 –
SAEx16.2
4.8
1,000
VDX0112-4-0.40 0.40 1,680 1.0 2.0 7.3 0.65 2.0 A1 –6.7 1.0 2.1 7.3 0.65 2.1 A1 –9.6 VDX0112-4-0.80 0.80 1,680 2.0 3.6 16 0.57 3.6 A1 –13 2.0 4.0 16 0.57 4.0 A1 –19 VDX0112-2-1.50 1.50 3,360 4.1 6.5 29 0.60 6.5 A2 –26 4.1 7.6 29 0.60 7.6 A2 –38 ADX0112-4-3.00 3.00 1,680 6.2 9.5 44 0.71 9.5 A2 –54 6.2 12 44 0.71 12 A2 –75 ADX0112-2-5.00 5.00 3,360 8.0 18 83 0.80 18 A3 –108 8.0 22 83 0.80 18 A3 –150 800 ADX0112-2-6.00 6.00 3,360 8.7 25 83 0.83 18 A3 –216 8.7 33 83 0.83 18 A3 –
1) – 3) Refer to notes on page 2.
SAEx 07.2 – SAEx 16.2Electrical data Multi-turn actuators for open-close duty with 3-phase AC motorsShort-time duty S2 - 15 min, 660 V/60 Hz
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.
Y005.245/003/en Issue 2.13 Page 1/2
Notes on table on page 1
1) Nominal power PN Mechanical power output at motor shaft at running torque of multi-turn actuator (corresponds to approx. 35 % of maximum torque).
The consumed electrical power can be calculated using the following formula:
P = U x I x cos ϕ x √3
2) Nominal current IN Current at running torque
3) Max. current Imax Current at maximum torque
Notes on installation and sizing
Motor data Motor data is approximate. Due to usual manufacturing tolerances, there may be deviations from the values given.
Thermoswitches/PTC thermistors To protect against overheating, thermoswitches or PTC thermistors are embedded in the motor windings.
Actuators without integral controls (AUMA NORM):
Thermoswitches or PTC thermistors have to be considered within the external controls (refer to terminal plan).
Note: Failure to connect thermoswitches or PTC thermistors shall void our warranty for the motor. According to EN 60079-14, a thermal overcurrent protection device (e.g. motor protection switch) must be installed for explosion-proof actuators in addition to the thermoswitches. PTC thermistors additionally require a suitable tripping device in the controls.
Rating of the thermoswitches
AC current DC current250 V, 50 – 60 Hz 60 V 1.0 A
cos ϕ = 1 2.5 A 42 V 1.2 Acos ϕ = 0.6 1.6 A 24 V 1.5 A
Actuators with AM or AC integral controls:
Thermal motor protection is already integrated.
Mains voltage, mains frequency Permissible variation of the mains voltage: ±10 %
Permissible variation of the mains frequency: ±5 %
Switchgear sizing For motor operation, reversing contactors (mechanically, electrically and electronically locked) or thyristors (elec-tronically locked) can be used.
Actuators without integral controls (AUMA NORM):
Switchgears are supplied by the customer. We recommend specifi cation of switchgears suitable for their rated operating power/motor power in compliance with the assigned AUMA power class.
Switchgear assignment to AUMA power classes:
AUMA power class
Reversing contactorRated power according to IEC 60947-4-1:2010 AC-3
Reversing contactormotor power according to UL/CSA at
400 V AC 480 V AC 600 V ACA1 4.0 kW 5.0 hp 5.0 hpA2 7.5 kW 10 hp 10 hpA3 15 kW 20 hp 25 hpA4 30 kW 60 hp 60 hpA5 55 kW 75 hp 100 hp
Actuators with AM or AC integral controls:
Required switchgears are already integrated.
SAEx 07.2 – SAEx 16.2Electrical data Multi-turn actuators for open-close duty with 3-phase AC motorsShort-time duty S2 - 15 min, 660 V/60 Hz
Y005.245/003/en Issue 2.13 Page 2/2