Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com Rectiverter Outdoor system Up to 6 kVA AC & up to 21 kW 48 VDC output Doc CTEJ0834.DS3 – rev1 KEY FEATURES 230VAC SINGLE PHASE INPUT 230 VAC THREE PHASE (Δ) INPUT 400 VAC THREE PHASE (Y) INPUT SINGLE PHASE OUTPUT 48 VDC INPUT/OUTPUT MAX 6 KVA AC OUTPUT MAX 21 KW DC OUTPUT 1 POLE AC DISTRIBUTION OPTION 2 POLE AC DISTRIBUTION OPTION -48 VDC DISTRIBUTION OPTION BUILT IN TRANSFER TECHNOLOGY 150% OVERLOAD CAPABILITY, 15S 600% QUICK TRIP CURRENT, 20MS HOT PLUGGABLE SMARTPACK 2 CONTROLLER SMARTPACK S CONTROLLER OPERATES IN PARALELL WITH FLATPACK2 RECTIFIERS GLOBAL COMPLIANCE PATENTED HE TECHNOLOGY Rectiverter Outdoor system 6 kVA AC + 12,8-21 kW DC The Rectiverter outdoor system combines both AC and DC feed into one common unit. Simultaneously it provides AC backup power for 230 VAC loads, and 48 VDC power for DC loads and battery charging. The total DC output can be configured up to 21 kW DC load where the limitation for AC load is set to max 6 kVA. Together with our Type 3 cabinet platform it’s designed for a variety of applications and can be tailored to fit your specific needs, with a protection class of IP55. APPLICATIONS TELECOM-MOBILE/WIRELESS LTE/4G/WiMAX Distributed antenna system Broadband Radio base stations/cell sites RAILWAY & METRO INFRASTRUCTURE Control & protection Signaling GSM-R Safety Systems POWER UTILITIES Control & protection SCADA system MODULAR ARCHITECTURE RECTIVERTER MODULE The 3 port converter simultaneously provides power for AC and DC loads. During mains outage the Rectiverter 48/1200 HE feeds AC loads using energy stored in the battery. The modular architecture, industry-leading efficiency, compact size, innovative design and comprehensive monitoring and control features provide significant benefits over the current industry standard. Rectiverter Module

Transcript of Rectiverter Outdoor system 6 kVA AC + 12,8-21 kW DC · Max output power DC 12,8 kW Power factor 0,8...

Page 1: Rectiverter Outdoor system 6 kVA AC + 12,8-21 kW DC · Max output power DC 12,8 kW Power factor 0,8 Frequency 50Hz, 60 Hz OTHER SPECIFICATIONS 1 pole AC distribuition 4 pc, 6-10 A,

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com

Rectiverter Outdoor systemUp to 6 kVA AC & up to 21 kW 48 VDC outputDoc CTEJ0834.DS3 – rev1

KEY FEATURES 230VAC SINGLE PHASE INPUT 230 VAC THREE PHASE (Δ) INPUT 400 VAC THREE PHASE (Y) INPUT SINGLE PHASE OUTPUT 48 VDC INPUT/OUTPUT MAX 6 KVA AC OUTPUT MAX 21 KW DC OUTPUT 1 POLE AC DISTRIBUTION OPTION 2 POLE AC DISTRIBUTION OPTION -48 VDC DISTRIBUTION OPTION BUILT IN TRANSFER TECHNOLOGY 150% OVERLOAD CAPABILITY, 15S 600% QUICK TRIP CURRENT, 20MS HOT PLUGGABLE SMARTPACK 2 CONTROLLER SMARTPACK S CONTROLLER OPERATES IN PARALELL WITH

FLATPACK2 RECTIFIERS GLOBAL COMPLIANCE PATENTED HE TECHNOLOGY

Rectiverter Outdoor system6 kVA AC + 12,8-21 kW DCThe Rectiverter outdoor system combines both AC and DC feed into onecommon unit. Simultaneously it provides AC backup power for 230 VACloads, and 48 VDC power for DC loads and battery charging.

The total DC output can be configured up to 21 kW DC load where thelimitation for AC load is set to max 6 kVA.Together with our Type 3 cabinet platform it’s designed for a variety ofapplications and can be tailored to fit your specific needs, with a protectionclass of IP55.

APPLICATIONS

TELECOM-MOBILE/WIRELESS

LTE/4G/WiMAX Distributed antenna system Broadband Radio base stations/cell sites

RAILWAY & METRO INFRASTRUCTURE

Control & protection Signaling GSM-R Safety Systems

POWER UTILITIES

Control & protection SCADA system

MODULAR ARCHITECTURERECTIVERTER MODULEThe 3 port converter simultaneouslyprovides power for AC and DC loads.During mains outage the Rectiverter48/1200 HE feeds AC loads using energystored in the battery.

The modular architecture, industry-leadingefficiency, compact size, innovative designand comprehensive monitoring and controlfeatures provide significant benefits overthe current industry standard.

Rectiverter Module

Page 2: Rectiverter Outdoor system 6 kVA AC + 12,8-21 kW DC · Max output power DC 12,8 kW Power factor 0,8 Frequency 50Hz, 60 Hz OTHER SPECIFICATIONS 1 pole AC distribuition 4 pc, 6-10 A,

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com

Rectiverter Outdoor systemDoc CTEJ0834.DS3 – rev1

MODEL 6 KVA+12,8 KW DCPart number CTEJ0834.4000

INPUT DATAVoltage range AC (3 phase Y) 320-475 VVoltage range DC 40-58 VMaximum current AC (per phase) 28-48 AFrequency 47-53 / 57-63 HzPower factor > 0.99

OUTPUT DATAAdjustable range AC 200-240 VAdjustable range DC 43-58 VMax output power AC 6,0 kVAMax output power DC 12,8 kWPower factor 0,8Frequency 50Hz, 60 Hz

OTHER SPECIFICATIONS1 pole AC distribuition 4 pc, 6-10 A, C-48 VDC distribution 14 pc, 10-63 A, CBattery breaker (plug-in) 2 pc, 100 A, D

LVLD 1 pc, 150 A

Specifications are subject to change without notice

SINGLE LINE 6KVA+12,8 KW DC

FRONT VIEW 6KVA+12,8 KW DC

Rectiverter 6 kVA+12,8 kW single phase outdoor system

Page 3: Rectiverter Outdoor system 6 kVA AC + 12,8-21 kW DC · Max output power DC 12,8 kW Power factor 0,8 Frequency 50Hz, 60 Hz OTHER SPECIFICATIONS 1 pole AC distribuition 4 pc, 6-10 A,

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com

Rectiverter Outdoor systemDoc CTEJ0834.DS3 – rev1

MODEL 6 KVA+16,8 KW DCPart number CTEJ0834.4001

INPUT DATAVoltage range AC (3 phase Y) 320-475 VVoltage range DC 40-58 VMaximum current AC (per phase) 28-48 AFrequency 47-53 / 57-63 HzPower factor > 0.99

OUTPUT DATAAdjustable range AC 200-240 VAdjustable range DC 43-58 VMax output power AC 6,0 kVAMax output power DC 16,8 kWPower factor 0,8Frequency 50Hz, 60 Hz

OTHER SPECIFICATIONS1 pole AC distribuition 4 pc, 6-10 A, C-48 VDC distribution 12 pc, 10-63 A, CBattery breaker (plug-in) 2 pc, 200 A, D

LVLD 1 pc, 150 A

Specifications are subject to change without notice

SINGLE LINE 6KVA+16,8 KW DCRectiverter 16,8 kW+6 kVA single phase outdoor system

FRONT VIEW 6KVA+16,8 KW DC

Page 4: Rectiverter Outdoor system 6 kVA AC + 12,8-21 kW DC · Max output power DC 12,8 kW Power factor 0,8 Frequency 50Hz, 60 Hz OTHER SPECIFICATIONS 1 pole AC distribuition 4 pc, 6-10 A,

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com

Rectiverter Outdoor systemDoc CTEJ0834.DS3 – rev1

FLEXIBLE AC INPUT 6KVA + 16 KW DCPart number CTE20834R1.4000

INPUT DATAVoltage range AC Flexibel AC inputVoltage range DC 40-58 VMaximum current AC (per phase) 35 AFrequency 47-53 / 57-63 HzPower factor > 0.99

OUTPUT DATAAdjustable range AC 200-240 VAdjustable range DC 43-58 VMax output power AC 6,0 kVAMax output power DC 16,0 kWPower factor 0,8Frequency 50Hz, 60 Hz

OTHER SPECIFICATIONS1 pole AC distribuition 4 pc, 6-10 A, C-48 VDC distribution 14 pc, 10-63 A, CBattery breaker (plug-in) 2 pc, 200 A, D

LVLD 1 pc, 150 A

Specifications are subject to change without notice

FRONT VIEW FLEXIBLE AC INPUT 6KVA+16 KW DC

SINGLE LINE FLEXIBLE AC INPUT 6KVA+16 KW DC

Rectiverter 16,0 kW+6 kVA single phase outdoor system

Page 5: Rectiverter Outdoor system 6 kVA AC + 12,8-21 kW DC · Max output power DC 12,8 kW Power factor 0,8 Frequency 50Hz, 60 Hz OTHER SPECIFICATIONS 1 pole AC distribuition 4 pc, 6-10 A,

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com

Rectiverter Outdoor systemDoc CTEJ0834.DS3 – rev1

FLEXIBLE AC INPUT 6 KVA + 21 KW DCPart number CTE30834R1.4000

INPUT DATAVoltage range AC Flexibel inputVoltage range DC 40-58 VMaximum current AC (per phase) 58 AFrequency 47-53 / 57-63 HzPower factor > 0.99

OUTPUT DATAAdjustable range AC 200-240 VAdjustable range DC 43-58 VMax output power AC 6,0 kVAMax output power DC 21,0 kWPower factor 0,8Frequency 50Hz, 60 Hz

OTHER SPECIFICATIONS1 pole AC distribuition 4 pc, 2-10 A, C-48 VDC distribution 10 pc, 10-63 A, CBattery breaker (plug-in) 2 pc, 250 A, D

Specifications are subject to change without notice Rectiverter 21,0 kW+6 kVA single phase outdoor system

FRONT VIEW FLEXIBLE AC INPUT 6KVA+21 KW DC

SINGLE LINE FLEXIBLE AC INPUT 6KVA+21KW DC

Page 6: Rectiverter Outdoor system 6 kVA AC + 12,8-21 kW DC · Max output power DC 12,8 kW Power factor 0,8 Frequency 50Hz, 60 Hz OTHER SPECIFICATIONS 1 pole AC distribuition 4 pc, 6-10 A,

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com

Rectiverter Outdoor systemDoc CTEJ0834.DS3 – rev1

Models / ordering information 6kVA+12,8 kW DC 6kVA+16,8kW DC 6kVA+ 16,0 kW DC 6kVA+21,0kW DCPart number CTEJ0834.4000 CTEJ0834.4001 CTE20834R1.4000 CTE30834R1.4000

AC OUTPUT DATAVoltage (default) / (adjustable range) 230 VAC / 200 - 240 VAC

Frequency (default inverter mode) 50 Hz (adaptive)Frequency (set-able inverter mode) 50Hz, 60Hz or last synced 50/60Hz (adaptive)Power maximum (continuous / overload (<15s) ) 4800 W (6000 VA) / 8000 VACurrent maximum (continuous / overload (<15s) ) 26ARMS / 34,8ARMS

Current (maximum) Quick trip (20ms) 120A (6 x nominal)Hold up (Voltage dips) (before switching tobattery) > 5 ms @ 4800W load

THD < 1.5 % at resistive loadOutput features Fuse in L and N, Hot pluggable

DC OUTPUT DATAVoltage (default) / (adjustable range) 53.5 VDC / 43 - 58 VDC

Power (maximum @nominal input) 12,8 kW 1) 16,8 kW 1) 16,0 kW 1) 21,0 kW 1)

Current (maximum @VOUT ≤ 48 VDC) 267 A 1) 350 A 1) 333 A 1) 437 A 1)

Hold up time, maximum output power >10ms; VOUT > 41 VDC

Output features Short circuit proof, Over voltage Shutdown

INPUT DATAAC Mains Input Voltage (3 phase Y) 400 VAC

Surge Protection OVP Class 2AC Current/Phase(at nominal output voltage) (depending on type) 28-58 ARMS

3)

Frequency (default: sync range) 47-53 HzFrequency (set-able: sync range) 47-53 Hz, 57-63 Hz or both (adaptive)Power Factor / THD > 0.99 at 50% load or more / < 3.5%DC Voltage nominal / extended range (nooverload)2) 45 - 58 VDC / 40 - 45 VDC

DC Current (maximum) 128 A / 180A during overload (15s)

Input featuresFuse in L and N, Hot pluggable, Varistor, Hot pluggable

AC input individual screw terminals 10 mm2 for L1, L2, L3, N & PEBattery breaker (plug-in type), LVBD default

LOAD DISTRIBUTION 6kVA+12,8kW DC 6kVA+16,8kW DC 6kVA+16,0 kW DC 6kVA+21,0 kW DCLVLD 150 A -1 pole AC distribution (L connection on MCB) 2*6A, 2*10A C-48 VDC distribution ( priority load ) 2*10A,2*16A,2*32A,2*63A 2*10A, 2*32A,2*63A 2*10A,2*16A,2*32A,2*63A 2*10A,2*16A,3*32A,3*63A-48 VDC distribution (no priority load) 2*10A, 2*32A, 2*63A -

Battery breaker 2*100 A, D (plug-in) 2*200 A, D (plug-in) 2*200 A, D (plug-in) 2*250 A, D (plug-in)

OTHER SPECIFICATIONControl and monitoring (see Smartpack2 datasheet) Smartpack S panel mount Smartpack 2Efficiency >96% (mains mode (AC/AC and AC/DC)), >94% (inverter mode (DC/AC))Operating temperature -40 to +55°C (-40 to +131°F), humidity 5 - 95% RH non-condensingStorage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensingDimensions[WxDxH] / Weight 700 x 823x 1800mm (27,6 x 32,4 x 71”) / 250kg (551 lbs)Protection class IP 55Colour RAL 7035

DESIGN STANDARDSElectrical safety EN 60950-1, EN 62040-1 UPS safetyEMC ETSI EN 300 386 V.1.6.1, FCC CFR 47 Part 15

EN 61000-6-1 /-2/-3/-4

Environment ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)RoHS (2011/65/EU) and WEEE (2002/96/EC) compliant

1) AC load has priority. Maximum available DC output power and current is dependent oninstant AC load and AC input voltage; i.e maximum 10,9 kW/18,9 kW at full AC power andnominal input for 230VAC.2) 40 - 45 VDC: reduced performance - no power boost and increased voltage THD on ACoutput

3) If DC voltage is pulled below 43V the input current may increase above this level

Specifications are subject to change without notice