EE 434 POWER SYSTEM PROTECTION LECTURE 16: OVERCURRENT COORDINATION Ernesto VazquezMartinez, ECERF

description

Theory of protection coordination using overcurrent relays

Transcript of Overcurrent Coordination

Page 1: Overcurrent Coordination

EE 434 POWER SYSTEM PROTECTIONLECTURE 16: OVERCURRENT COORDINATION 

Ernesto Vazquez‐Martinez, ECERF

Page 2: Overcurrent Coordination

OC radial system protection

∆Τ

d

d

T

I

∆Τ∆Τ

Page 3: Overcurrent Coordination

Minimum fault condition

Minimum generation for a minimum fault current (I = 0.866 I3, or I‐G).

Relay Fault

MIN

PICK‐UP Protectionzone

FAULTMAX

Page 4: Overcurrent Coordination

Example using One‐Liner

R2R1

10MVAp.f.0.95

167.3A

8MVAp.f.0.95

133.8A

j0.1j0.2j0.15

34.5kV

Page 5: Overcurrent Coordination

Fault conditions

Page 6: Overcurrent Coordination

Initial coordination

0.05s

0.04s

Page 7: Overcurrent Coordination

Final coordination 1

T 0.29s

Page 8: Overcurrent Coordination

Final coordination 2

T 0.42s

Page 9: Overcurrent Coordination

Minimum fault condition

Page 10: Overcurrent Coordination

Coordination criteria

Page 11: Overcurrent Coordination

Initial coordination

Page 12: Overcurrent Coordination

Final coordination

Page 13: Overcurrent Coordination

Sensibility for MFC

The loads are taken of service. Use the positive sequence currents.

Ks=(1859/240) / 4 = 1.93 > 1.5

Page 14: Overcurrent Coordination

EE 434 POWER SYSTEM PROTECTIONLECTURE 16: OVERCURRENT COORDINATION 

Ernesto Vazquez‐Martinez, ECERF