Test Report Resistance to wind load Test report No.: 2015-0004-002_en_01 Basis EN 13561:2004-09+A1:2008-10 External blinds – Performance requirements including safety EN 13561:2015-05 Shutters and external venetian blinds – Performance requirements including safety *)and corresponding national versions e.g. ΕΛΟΤ EN ΕΝ 1932 : 2013-06 External blinds and shutters – Resistance to wind loads – Method of testing an performance criteria Representation Instruction for use The results obtained can be used by the manufacturer for preparing the Declaration of Performance in accordance with the Construction Products Regulation 305/2011/EU. The provisions of the applicable product standard have to be observed. Validity There is no time limit. When using this document the up-to-dateness of above basis and the conformity of the product have to be observed. The report contains a total of 9 pages Owner Koukourelis Christos (TENTOEXPRESS) 19th km Thessaloniki – Moudanion (Kardia) 57001 Thermi Greece Product Folding pergola System Designation SunRain System Manufacturer TENTOEXPRESS Guide (Length Width Height) 7,000 mm / 60 mm / 132 mm (43005) Counterweight Small (43003), wide (43004) Distance between counterweight 500 mm Axle (length// thickness) 5,000 mm / 75 mm / 2,5 mm (43010) Overall dimensions (W x H) 5,000 mm x 7,000 mm Mechanism Motorized Special features -/- Results Resistance to wind loads according to EN 13561-2004-09+A1:2008-10 W5,000 x H7,000 Class: 3 Non-harmonized version at the time of testing – Resistance to wind loads according to EN 13561-2015-05 W5.000 x H7,000 Class: 6 PLANECO Mon. EPE 26. November 2018 Dr. Georgios Moustakidis General Manager

Transcript of 2015-0004-002 en 01 - tentoexpress.gr · Test Report Page 2 of 9 Resistance to wind load Test...

Page 1: 2015-0004-002 en 01 - tentoexpress.gr · Test Report Page 2 of 9 Resistance to wind load Test Report No. 2015-0004-002_en_01 dated 26. November 2018 Client Koukourelis Christos (TENTOEXPRESS)

Test Report Resistance to wind load

Test report No. : 2015-0004-002_en_01

Basis

EN 13561:2004-09+A1:2008-10

External blinds – Performance

requirements including safety

EN 13561:2015-05

Shutters and external venetian

blinds – Performance

requirements including safety

*)and corresponding national versions e.g. ΕΛΟΤ EN

ΕΝ 1932 : 2013-06

External blinds and shutters –

Resistance to wind loads –

Method of testing an

performance criteria

Representation

Instruction for use

The results obtained can be used by the manufacturer for preparing the Declaration of Performance in accordance with the Construction Products Regulation 305/2011/EU. The provisions of the applicable product standard have to be observed.

Validity

There is no time limit.

When using this document the up-to-dateness of above basis and the conformity of the product have to be observed. The report contains a total of 9 pages

Owner Koukourelis Christos

(TENTOEXPRESS)

19th km Thessaloniki – Moudanion (Kardia)

57001 Thermi

Greece

Product Folding pergola

System Designation SunRain System

Manufacturer TENTOEXPRESS

Guide

(Length Width Height) 7,000 mm / 60 mm / 132 mm (43005)

Counterweight Small (43003), wide (43004)

Distance between

counterweight 500 mm

Axle (length/∅/ thickness) 5,000 mm / 75 mm / 2,5 mm (43010)

Overall dimensions

(W x H) 5,000 mm x 7,000 mm

Mechanism Motorized

Special features -/-

Results

Resistance to wind loads according to EN 13561-2004-09+A1:2008-10

W5,000 x H7,000 Class: 3

Non-harmonized version at the time of testing –

Resistance to wind loads according to EN 13561-2015-05

W5.000 x H7,000 Class: 6

PLANECO Mon. EPE 26. November 2018

Dr. Georgios Moustakidis

General Manager

Page 2: 2015-0004-002 en 01 - tentoexpress.gr · Test Report Page 2 of 9 Resistance to wind load Test Report No. 2015-0004-002_en_01 dated 26. November 2018 Client Koukourelis Christos (TENTOEXPRESS)

Test Report Page 2 of 9

Resistance to wind load

Test Report No. 2015-0004-002_en_01 dated 26. November 2018

Client Koukourelis Christos (TENTOEXPRESS)

1. Object

1.1. Description of test specimen

Manufacturer/ System Producer Tentoexpress

SunRain System

Test specimen

Description Folding Tento Pergola

Dimensions of specimen [mm] 5,000 x 7,000

Guide

Designation / type / item no 43005

Material / Manufacturer Aluminium / ELVIAL

Number of guides 2

Dimensions (length/width/high) [mm] 7,000 x 60 x 132

Movement of the guide shoe (above – below) Below

Counterweight small

Designation / type / item no 43003

Material / Manufacturer Aluminium / ELVIAL

Dimensions (length/width/high) [mm] 5,000 x 42 x 65

Distance of counterweights [mm] 550

Guide shoe small

Designation / type / item no 1007

Material / Manufacturer Polyamide

Dimensions (length/width) [mm] 29 x 51

Counterweight wide

Designation / type / item no 43004

Material / Manufacturer Aluminium / ELVIAL

Dimensions (length/width/high) [mm] 5,000 x 65 x 103

Distance of counterweights [mm] 550

Guide shoe wide

Designation / type / item no 1008

Material / Manufacturer Polyamide

Dimensions (length/width) [mm] 29 x 90

Page 3: 2015-0004-002 en 01 - tentoexpress.gr · Test Report Page 2 of 9 Resistance to wind load Test Report No. 2015-0004-002_en_01 dated 26. November 2018 Client Koukourelis Christos (TENTOEXPRESS)

Test Report Page 3 of 9

Resistance to wind load

Test Report No. 2015-0004-002_en_01 dated 26. November 2018

Client Koukourelis Christos (TENTOEXPRESS)

Axle

Designation / type / item no 43010

Material / Manufacturer Aluminium / ELVIAL

Dimensions (length / diameter ∅ / thickness) [mm] 5,000 x 75 x 2,5

Mounting system

Designation / type / item no Aluminium tubes / 43011

Material / Manufacturer Aluminium / ELVIAL

Number 2

Fabric

Designation / type / item no PVC Block-out

Material / Manufacturer Dikcson / RVE

Weight [gr/m2] 850

Width x height [mm] 5,000 x 7,000

Mechanism / Mode of Operation

Mode of operation Motorized

The description is based on information provided by the client and inspection of the test specimen at the test rig (item designations /

numbers as well as material specifications were provided by the client).

1.2. Sampling

The below sampling data were provided to PLANECO:

Sampling by: TENTOEXPRESS

Verification: A sampling report has not been provided to PLANECO.

Delivered on: 16.10.2015

Specimen No.: 2015-009-001

2. Procedure

2.1. Basis

EN 13561:2004-09+A1:2008-10 External blinds – Performance requirements including safety

EN 13561:2015-05 Shutters and external venetian blinds – Performance

requirements including safety

EN 1932:2013-06 External blinds and shutters – Resistance to wind loads – Method

of testing and performance criteria

Page 4: 2015-0004-002 en 01 - tentoexpress.gr · Test Report Page 2 of 9 Resistance to wind load Test Report No. 2015-0004-002_en_01 dated 26. November 2018 Client Koukourelis Christos (TENTOEXPRESS)

Test Report Page 4 of 9

Resistance to wind load

Test Report No. 2015-0004-002_en_01 dated 26. November 2018

Client Koukourelis Christos (TENTOEXPRESS)

2.2. Test sequence

Resistance to wind load according to EN 1932:2013-06

EN 13561:2004-09+A1:2008-10, Clause 4.2, the load application process Νο. 1 has been applied in

accordance with EN 1932:2013-06.

For this purpose, the samples were loaded with test weights in accordance with the EN 1932.

Testing was performed with the nominal load and/or the safety load. The relevant test loads

depending on the wind load class was applied ina jolt-free manner for 2 minutes each.

Page 5: 2015-0004-002 en 01 - tentoexpress.gr · Test Report Page 2 of 9 Resistance to wind load Test Report No. 2015-0004-002_en_01 dated 26. November 2018 Client Koukourelis Christos (TENTOEXPRESS)

Test Report Page 5 of 9

Resistance to wind load

Test Report No. 2015-0004-002_en_01 dated 26. November 2018

Client Koukourelis Christos (TENTOEXPRESS)

3. Detailed results

Page 6: 2015-0004-002 en 01 - tentoexpress.gr · Test Report Page 2 of 9 Resistance to wind load Test Report No. 2015-0004-002_en_01 dated 26. November 2018 Client Koukourelis Christos (TENTOEXPRESS)

Test Report Page 6 of 9

Resistance to wind load

Test Report No. 2015-0004-002_en_01 dated 26. November 2018

Client Koukourelis Christos (TENTOEXPRESS)

Page 7: 2015-0004-002 en 01 - tentoexpress.gr · Test Report Page 2 of 9 Resistance to wind load Test Report No. 2015-0004-002_en_01 dated 26. November 2018 Client Koukourelis Christos (TENTOEXPRESS)

Test Report Page 7 of 9

Resistance to wind load

Test Report No. 2015-0004-002_en_01 dated 26. November 2018

Client Koukourelis Christos (TENTOEXPRESS)

4. Evaluation

Based on the test results and according to EN 1932: 2013-09, EN 13561:2004-09+A1:2008-10 and ΕΝ

13561: 2015-08 the test specimen is classified in the wind load category 3 for EN 13561:2004-

09+A1:2008-10 and wind load category 6 for EN 13561: 2015-08. The wind load categories 3 and 6

are the highest achievable category in accordance with EN 13561 in each version.

The difference between the values Η0-Η2 was calculated and found to be <0.4%. [Η0 = initial height,

Η2 = height after application of the nominal wind load plus 50%]. The nominal load was added plus

50%, so that the achieved performance characteristics also apply to pergolas with more than two (2)

guides.

After the nominal load plus 50% and the safety load plus 50%, no wear / damage was detected and

the pergola awning was fully functional.

Page 8: 2015-0004-002 en 01 - tentoexpress.gr · Test Report Page 2 of 9 Resistance to wind load Test Report No. 2015-0004-002_en_01 dated 26. November 2018 Client Koukourelis Christos (TENTOEXPRESS)

Test Report Page 8 of 9

Resistance to wind load

Test Report No. 2015-0004-002_en_01 dated 26. November 2018

Client Koukourelis Christos (TENTOEXPRESS)

Page 9: 2015-0004-002 en 01 - tentoexpress.gr · Test Report Page 2 of 9 Resistance to wind load Test Report No. 2015-0004-002_en_01 dated 26. November 2018 Client Koukourelis Christos (TENTOEXPRESS)

Test Report Page 9 of 9

Resistance to wind load

Test Report No. 2015-0004-002_en_01 dated 26. November 2018

Client Koukourelis Christos (TENTOEXPRESS)