EARTH ELECTRODE / EARTH LOOP RESISTANCE CONTINUITY OF PE CONDUCTORS / CONDUCTIVE PARTS Nominal Differntial current IN (mA) 10 30 100 300 500 1000 R earth () max. (Uc<50 V) 5000 1666 500 166 100 50 R earth () max. (Uc<25 V) 2500 833 250 83 50 25 1 2 INSULATION RESISTANCE LINE / NEUTRAL TO PE Limits: Where no RCD, select limit from the FUSE characteristics, test by Z loop. Where RCD: VERIFICATION ON LOW-VOLTAGE ELECTRICAL INSTALLATIONS: IEC 60364-6 PROTECTION BY AUTOMATIC DISCONNECTION OF THE SUPPLY 4 REPORTS AND CERTIFICATES ON LOW-VOLTAGE ELECTRICAL INSTALLATIONS: IEC 60364 5 TN system - Two clamps - clamps arround main N/PE cable TT system - Two wire - test from the socket N to PE IT system - Three wire - test leads to rods in triangle Lightning system & Earth loops - test each loop IEC 60364-6 61.3.6.2., B.3., equipment: IEC 61557- 5 Limits: 2 above ground 10 whole system 10 underground per leg or 8% of Specific Earth Resistance L1 L2 L3 PE TN N L1 L2 L3 PE N TT IEC 60364-6 61.3.2., equipment: IEC 61557- 4 Parameters: ± 200 mA both directions, all exposed conductive parts to MPE and in between where distance < 2.5 m. Limits: or 2 Ω max. (where RCD built-in) R U c I pfc 50V 200A 0,25 Ω (where Fuse C20A built-in) IEC 60364-6 61.3.3., equipment: IEC 61557-2 Parameters: 500 V DC 250 V DC for PELV/SELV Limits on Circuits: R min > 1 MR min > 0.5 Mfor PELV/SELV Floor and wall resistance/impedance R > 50 k(insulated) Semiconductive coatings 1 M< R > 1 GProtection against static electricity (EN 61340-5-1) Leakage Current - alternative method for testing and tracing insulation problems without disconnection Parameters: TRMS Low range measurement Limits: 1 mA/kW or 3.5 mA max. per app. 5 mA max. where heating app. 1/3 x Idn where RCD protected circuits. Leakage < 100 mA for fire protection. Fuse: Z loop L-PE / Z line L-L, L-N IEC 60364-6 61.3.6.3., 61.3.11., equipment: IEC 61557- 3 Parameters / Limits are characteristics of particular built-in Fuse, designed for trip-out time of: 0.1 s (Explosive), 0.2s (3Phase Circuits), 0.4 s (1Phase systems) or 5 s (fixed connections). Measured values of Impedances from the end of the circuit must be lower than Zs from the table. In (A) Tip B Tip C TiP G Ia=5x In (A) Zs=( ) (0,2 s) Ia=10x In(A) Zs=( ) (0,2 s) In (A) Zs=( ) (0,4 s) 2 10 22 20 11 16 13,7 4 20 11 40 5,5 32 6,8 6 30 7,3 60 3,65 47 4,6 10 50 4,4 100 2,2 82 2,6 16 80 2,8 160 1,4 110 2,0 20 100 2,2 200 1,1 147 1,4 RCD: Trip out time, Trip out Current IEC 60364-6 61.3.6.1., 61.3.7., equipment: IEC 61557- 6 More Parameters/Limits could be found in Metrel Handbooks and inside Eurotest/Smartec testers. RCD RCD trip out at differential Id (ms) 1/2 x IN 1 x I N 2 x I N 5 x I N General No trip t< 300 t< 150 t< 40 Selective No trip 130 x t < 500 60 x t < 200 50 x t < 150 RCD Slope range (from-to) 0,5 ÷ 1.0 x l N AC A 0,35 ÷ 1.4 x l N B 0,5 ÷ 2.0 x l N L1 L2 L3 PE N TT 3 www.metrel.si ANG Code: 20 752 423 Ver 1.0. Poster_Verification on Low-voltage electrical installations_ANG_Ver 1.0._20 752 423.indd 1 7.7.2015 7:45:03

Transcript of vErification on loW-voltagE ElEctrical installations: iEc 60364-6 · 2017. 7. 18. · IEC 60364-6...

  • Earth ElEctrodE / Earth loop rEsistancE

    continuity of pE conductors / conductivE parts

    nominal differntial current i∆n (ma) 10 30 100 300 500 1000

    r earth (Ω) max. (uc 0.5 mΩ for PELV/SELV floor and wall resistance/impedance r > 50 kΩ (insulated) semiconductive coatings 1 mΩ < r > 1 gΩ Protection against static electricity (EN 61340-5-1)

    leakage current - alternative method for testing and tracing insulation problems without disconnection parameters: trms Low range measurement limits: 1 ma/kW or 3.5 ma max. per app. 5 ma max. where heating app. 1/3 x idn where RCD protected circuits. Leakage < 100 ma for fire protection.

    fuse: Z loop l-pE / Z line l-l, l-n iEc 60364-6 61.3.6.3., 61.3.11., equipment: iEc 61557- 3

    parameters / limits are characteristics of particular built-in Fuse, designed for trip-out time of:

    0.1 s (Explosive), 0.2s (3Phase Circuits), 0.4 s (1Phase systems) or 5 s (fixed connections).

    Measured values of Impedances from the end of the circuit must be lower than Zs from the table.

    In (A)

    tip b tip c tip gIa=5x In (A)

    Zs=(Ω) (0,2 s)

    Ia=10x In(A)

    Zs=(Ω) (0,2 s)

    In(A)

    Zs=(Ω) (0,4 s)

    2 10 22 20 11 16 13,74 20 11 40 5,5 32 6,86 30 7,3 60 3,65 47 4,6

    10 50 4,4 100 2,2 82 2,616 80 2,8 160 1,4 110 2,020 100 2,2 200 1,1 147 1,4

    rcd: trip out time, trip out current iEc 60364-6 61.3.6.1., 61.3.7., equipment: iEc 61557- 6

    More Parameters/Limits could be found in Metrel Handbooks and inside Eurotest/Smartec testers.

    RCDrcd trip out at differential id (ms)

    1/2 x I∆N 1 x I∆N 2 x I∆N 5 x I∆N

    General No trip t∆ < 300 t∆ < 150 t∆ < 40

    Selective No trip 130 x t ∆ < 500 60 x t∆ < 200 50 x t∆ < 150

    RCD slope range (from-to)

    0,5 ÷ 1.0 x l∆N AC

    A 0,35 ÷ 1.4 x l∆N

    B 0,5 ÷ 2.0 x l∆N