Reactive Power Controller ProCon / DynamiC€¦ · Page 2 = Key 1 = Key 2 = Key 3 Reactive Power...

56
Peak value Fix stages Password Capacitive Required capacitive power Cosinus ϕ Inductive Automatic mode Harmonics Manual mode Target cos(phi1) Target cos(phi2) Lowest value Capacitive stage active Alarm output active Expanded programming Number of stages Stage ratio Power of 1st stage Learning of configuration CT ratio cap cosϕ Qc ind 1 2 3 4 5 6 7 8 9 10 11 12 Error ϕ1 ϕ2 learn 1:1... Prog Maschinenfabrik Reinhausen GmbH - Power Quality Management | Wiebestraße 46 | 10553 Berlin / Germany Tel.: +49 30 330915-0 | Fax : +49 30 330915-25 | email: [email protected] | Internet: http://www.reinhausen.com Reactive Power Controller Operating instructions Brief instructions see last page ProCon / DynamiC Dok Nr. 1.020.079.1 Serie II Key 3 Key 2 Key 1

Transcript of Reactive Power Controller ProCon / DynamiC€¦ · Page 2 = Key 1 = Key 2 = Key 3 Reactive Power...

  • Peak valueFix stagesPasswordCapacitiveRequired capacitive powerCosinus ϕInductiveAutomatic modeHarmonicsManual modeTarget cos(phi1)Target cos(phi2)

    Lowest valueCapacitive stage activeAlarm output active

    Expanded programmingNumber of stagesStage ratioPower of 1st stageLearning of configurationCT ratio

    capcosϕϕϕϕϕ Qcind

    1 2 3 4 5 6 7 8 9 10 11 12 Error

    ϕϕϕϕϕ1 ϕϕϕϕϕ2 learn 1:1... Prog

    Maschinenfabrik Reinhausen GmbH - Power Quality Management | Wiebestraße 46 | 10553 Berlin / Germany

    Tel.: +49 30 330915-0 | Fax : +49 30 330915-25 | email: [email protected] | Internet: http://www.reinhausen.com

    Reactive Power Controller

    Operating instructions

    Brief instructions see last page

    ProCon / DynamiC

    Dok

    Nr.

    1.0

    20.0

    79.1

    S

    erie

    II

    Key 3

    Key 2

    Key 1

  • Page 2 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Expanded programming 25Fix stages 25Discharge time 26Disconnection pause 26Power station service 27Stage power 28Choke degree 28Voltage transformer ratio 29Harmonic thresholds 30Switching frequency 31Alarm output 32

    Alarm call 32Give a receipt for alarms 32Lower voltage (1) 33Overvoltage (2) 33Underscoring of the measurement current (3) 33Exceeding of measuring current (4) 33Insufficient capacitor output (5) 33Supply of real power (6) 33Harmonic thresholds (7) 33Overtemperature (8) 33

    Averaging time for the mean value cos(phi) 34Averaging time of reactive power 34Ventilator control 35Ventilation control 35

    Upper temperature limit 35Lower temperature limit 35Switching output 35

    Overtemperature disconnection 37Upper temperature limit 37Lower temperature limit 37Pause time 37

    Indication in manual mode 38Password 39Program password 39Enter password 39Change password 39Contrast 40Reset programming 41Connection configuration 42

    Correction angle 42Software release 43

    Serial number 43Serial interface (Option) 44

    Device address 44Transmission protocol 44Baud rate 45Modbus RTU 45Profibus DP V0 45Table Modbus 46Table Profibus 47

    Contents

    Receipt Control 4Meaning of the symbols 4

    Hints for usage 4Product description 5

    Intended use 5Data protection 5Hints for maintenance 5

    Repairing and calibration 5Front foil 5Waste management 5

    Funktional description 6Measurement 6Switching of capacitor stages 6Switching outputs 6Net return 6

    Hints for installation 8Mounting place 8Measurement and supply voltage 8

    Sum current measurement 9Current measurement 9

    Installation and putting into service 10Measurement and supply voltage 10Current measurement 11Real power 11Switching outputs 12

    Transistor outputs 12Target-cos(phi) changeover 13Alarm output 13Check alarm output 13

    RS485 Interface (Option) 14Transmission protocols 14Bus structure 14Shielding 14Cable length 14Terminal resistors 14

    Removal of errors 15Service 16

    Display and use 17Automatic mode 17Manual mode 17Key functions 18

    Standard programming 19Target cos(phi) 19Current transformer ratio 20Learning of the configuration 21Stage power 22Stage ratio 22Switching outputs 23Delete peak and lowest values 24

  • Page 3= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Display overview 48Measured value indications 48Display in standard programming 50Display in expanded programming 51

    Configuration data 53Setting range 53Manufacturer's presetting 53

    Technical data 54Ambient conditions 54Inputs and outputs 54Measurement 54Measurement accuracy 54Back Side 55Side view 55

    Short manual 56

    Issue Note30.06.1999 First edition21.07.1999 Indication cos(phi)=0.00; Switching of

    fixed stages.12.08.1999 Measurement accuracy, switching

    frequency.30.08.1999 Page 30, table of correction angle

    changed.31.08.1999 Fuses and connection diagrams have been

    corrected.12.11.1999 Switching in manual mode23.03.2000 Maximum and minimum storage all 15

    minutes.21.09.2000 Functional expansion.19.01.2001 Technical data and brief instructions

    added.20.03.2001 Generator mode = oFF.04.04.2001 RS485 interface.22.10.2001 Serial interface does not work at 50Hz

    switching frequency.28.01.2002 Connection diagrams alarm output.12.08.2002 Address list Modbus expanded by

    harmonics U/I.22.08.2002 Description of password programming.23.09.2002 Measurement and supply voltage L-N.

    All rights reserved. No part of this manual may be re-produced or duplicated without the written permissionof the author. Any contraventions are punishable andwill be prosecuted with all legal means.

    No liability can be taken for the faultless condition ofthe manual or damage caused by the use of it. As fail-ures cannot be avoided completely, we shall be verygrateful for any advice. We will try to remove any fail-ures as soon as possible. The mentioned software andhardware descriptions are registered trademarks in themost cases and are subjected to the regulations by law.All registered trademarks are property of the correspond-ing companies and are fully recognized by us.

  • Page 4 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Receipt ControlIn order to ensure a perfect and safe use of the device, aproper transport, expert storage, erection and mountingand careful usage and maintenance are required. Whenit may be supposed, that a safe operation is no longerpossible, the device has to be put out of service and beprotected against unintentional putting into service.

    A safe operation can no longer be assumed, when thedevice• shows visible damage,• does not work in spite of intact net supply,• has been exposed to disadvantageous conditions for alonger time (e.g. storage out of the allowed climatewithout adaption to the room climate, dew etc.) or trans-port use (e.g. falling from great height, even withoutvisible damage).

    Please test the contents of delivery for completion, be-fore starting the installation of the device. All deliveredoptions are listed on the delivery papers.In the attached description doc. no.: 1.020.030.x all de-livery types and options for the reactive power control-ler DynamiC are listed.

    Hints for usageSafe and failure free operation can only be granted,when the device is operated according to this manual!

    This device may be put into service and used by quali-fied personnel according to the safety regulations andinstructions only. Please mind the additional legal andsafety regulations for the respective application.

    Qualified personnel are persons, familiar with erection, mounting,putting into service and usage of the product and having the quali-fications such as:

    • education or instruction / entitlement to switch, re-lease, ground or characterize current circuits and de-vices according to the standards of safety techniques.

    • education or instruction in the care and usage of suit-able safety equipment according to the standards ofsafety techniques.

    Warning of dangerous electrical voltage.

    This symbol shall warn you of possible dangers, which can occur during maintenance, putting into serviceand while usage.

    Protective wire connection

    ��

    Meaning of the symbols

    Attention!This manual also describes options andtypes, which were not delivered and there-fore, do not belong to the contents of deliv-ery.

  • Page 5= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Product descriptionIntended useThe reactive power controller DynamicC together withexternal capacitor stages, serves for step by step con-trolling of the phase shift angle cos(phi) in 50/60Hzlow voltage networks. Depending on the type of thereactive power controllers DynamiC , contactors or semiconductor switches can be controlled directly.Additionally, the following electrical quantities are meas-ured and indicated:- Voltage L2-L3,- Current in L1,- Frequency,- Sum real power (Consumption/supply),- Sum reactive power (ind./cap.),- uneven current harmonic waves 1. - 19. in %,- uneven voltage harmonic waves 1. - 19. in %.The harmonic contents are related to the rated voltageor rated current.

    The connection is carried out on the back side via touchproof spring power terminals.Measurement and supply voltage are taken from themeasurement voltage and must be connected to thebuilding installation via a separation (switch or powerswitch) and an overcurrent protection (6,3A).The current measurement is carried out via a ../5A or../1A current transformer in one outer conductor.

    The relay outputs are suitable for contactor control, thetransistor outputs are provided for the control of fastswitching thyristor modules, switching at zero crossing.

    Hints for maintenanceBefore delivery the device is tested in various safetychecks and marked with a seal. If the device is opened,these checks must be repeated.There is no guarantee for devices, which are openedout of the manufacturing works.

    Repairing and calibrationRepairing and calibration work can be carried out in themanufacturing works only.

    Front foilThe cleaning of the front foil must be done with a softcloth using a common cleansing agent. Acid or acidicagents may not be used for cleaning.

    Waste managementThe device can be disposed as electronical waste ac-cording to the legal regulations and recycled.

    Data protectionThe data protection is carried out in a none volatilememory (EEPROM).Changed programming data are saved immediately.

  • Page 6 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Switching of capacitor stagesDynamiC calculates the required reactive power toreach the set target-cos(phi) from the current from oneouter conductor and the voltage between two outer con-ductors. If the cos(phi) deviates from target cos(phi),external capacitor stages or transistor outputs areswitched on or off.In automatic mode the capacitor stages are switched inor off, when the required reactive power is higher orequal to the smallest stage power.If the power of the first capacitor stage is three times ashigh as the measured real power, all capacitor stagesare switched off.

    Switching outputsDepending on the variety of DynamiC , relay ortransistor outputs serve as switching outputs.The relay outputs are suitable for controlling contactorsand the transistor outputs can switch thyristor modules,that switch in zero crossing of voltage.For relay outputs the time between two connections ordisconnections is set to two seconds. Transistor outputshave no limitation of the switching period.

    Net returnAfter net return, the set discharge time runs for therelay outputs. The transistor outputs do not mention thedischarge time.

    Funktional descriptionMeasurementThe measurement is suited for 3 phase systems with orwithout neutral conductor for frequencies of 50Hz or60Hz. The electronical measurement system records anddigitalizes the effective values of voltage between L2and L3 (L-N Option) and the current in L1.In each second several snap check measurements arecarried out. As the current is only measured in oneouter conductor, and the voltage only between two outerconductors, the measured values, which are related toall three outer conductors, are exact for equal loadedouter conductors only.The following electrical quantities are calculated:

    Current and current harmonicsVoltage and voltage harmonicsReal power, sumApparent power,sumReactive power, sumReactive power for each stageReactive current for each stageCos(phi),Net frequency.

    The following information can be indicated:Number of switchings of each stage,total connection time of each stage andthe inner temperature.

    DynamiC measures the frequency of the measurementand supply voltage and shows the average over 10 sec-onds.

  • Page 7= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Diagr.: Connection example, power factor controller with measurement and supply voltage L2-L3,12 relais outputs,target cos(phi) changeover and alarm output.

    DynamiC

    Diagr.: Connection example, power factor controller with measurement and supply voltage L-N,12 relais outputs,target cos(phi) changeover and alarm output.

  • Page 8 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Hints for installationMounting placeThe reactive power controller DynamiC is suited formounting and operation in reactive power compensationsystems.

    The connection is carried out on the back side via touchproof spring power terminals.

    Measurement and supply voltageThe measurement is suited for 3 phase systems with orwithout neutral conductor. Measurement and supplyvoltage are taken from the measurement voltage andmust be connected to the building installation via aseparation (switch or power switch) and an overcurrentprotection (2A...10A).

    The reactive power controller measures and supervisesthe voltage between two outer conductors. If one ofthose two fails, the reactive power controller gets nomore measurement and operating voltage, and switcheson the capacitive stages after net return according tothe programmed times.If the third outer conductor is missing, this will not berecognized by the reactive power controller. If the con-tactors are supplied by this outer conductor, the contac-tors can attract simultaneously and without considera-tion of the discharge time after net return.Falsch

    False

    EinspeisungSupply

    VerbraucherConsumer

    EVU-MessungElectricity-Meter

    DynamiC

    EinspeisungSupply

    VerbraucherConsumer

    EVU-MessungElectricity-Meter

    DynamiCFalschFalse

    EinspeisungSupply

    EVU-MessungElectricity-Meter

    DynamiC

    FalschFalse

    VerbraucherConsumer

    RichtigCorrect

    EinspeisungSupply

    VerbraucherConsumer

    EVU-MessungElectricity-Meter

    DynamiC

    Attention!The operating voltage for the contactorsshould be taken from an outer conductor con-nected to the reactive power controller.

    Abb.: Anschluss der Mess- und Hilfsspannung zwischenL2-L3 und der Strommessung über Stromwandlers.

    DynamiC

    MessungMeasurement

    0,01 .. 5A

    L/Lsiehe Typenschild

    see type label

    ../5(1)AL1L2L3

    PE

    k l

    2 .. 10A

    VerbraucherConsumer

    k l L2 L3

  • Page 9= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Diagr. Measurement with Amperemeter in series

    Diagr. Measurement via sum current transformers

    Current measurementThe current measurement is carried out via ../5A or ../1A current transformers.If the current must be measured with an Amperemeteradditionally to DynamiC , it must be connected inseries.

    Sum current measurementIf DynamiC is connected to a sum current transformer,the total transformation ratio must be programmed.

    Attention!For unequal load of the outer conductors, thecurrent should be measured in the outer con-ductor, which is loaded most heavily.

    Verbraucher 1Consumer 1

    Verbraucher 2Consumer 2

    Einspeisung 1Supply 1

    Einspeisung 2Supply 2

    DynamiC

    L l

    k K

    l L

    K k

    AK AL BK BL

    k l

    k l

    VerbraucherConsumer

    DynamiC

    EinspeisungSupply

    L l

    K k

    Ak

    l

    �Abb.: Anschluss der Mess- und Hilfsspannung zwischenL1-N und der Strommessung über Stromwandlers.

    DynamiC

  • Page 10 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Installation and putting into serviceMeasurement and supply voltageThe controller DynamiC can be delivered in two con-nection varieties for the measurement and supplyvoltage.In the version measurement L-L, the measurement andsupply voltage must be taken from two outer conduc-tors. In version measurement L-N, the measurementand supply voltage must be taken between outer con-ductor L and neutral N.

    Before connection, please ensure, that the local net con-ditions match the data on type plate. The range of themeasurement and supply voltage is given by the typeplate and is connected via a fuse (2…10A, time lag type)

    Diagr.: Connection of measurement and supply voltage(L2-L3) and current transformer.

    DynamiC

    MessungMeasurement

    0,01 .. 5A

    L/Lsiehe Typenschild

    see type label

    ../5(1)AL1L2L3

    PE

    k l

    2 .. 10A

    VerbraucherConsumer

    k l L2 L3

    Diagr.: Connection of measurement and supply voltage(L1-N) and current transformer.

    If the measurement and supply voltage is within theallowed range, DynamiC indicates the voltage on theterminal.While measuring via voltage transformers, the voltagetransformer ratio must be programmed.

    Attention!The measurement and supply voltage mustcome from the low voltage net, which is su-pervised.

    The connected measurement and supply voltage maynot exceed the voltage, mentioned on type plate formore than 10% or underscore for more than 15%.To ensure, that the connected measurement and supplyvoltage is within the allowed range, please check thevoltage at the terminal with a voltmeter.

    Attention!Voltage, which is out of the indicated rangeon type plate can destroy the instrument.

    � Attention!The operating voltage for the contactors shouldbe received from an outer conductor connectedto the controller.

    DynamiC

  • Page 11= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Current measurementThe current transformer is connected to the clamps kand l (/5A or /1A) from the outer conductor L1.Please ensure during the installation of the current trans-former, that the current transformer is passed by theconsumer current but not by the compensation current.The current can be measured by an Amperemeter tocompare it with the current indicated by DynamiC tocheck. Please note, that the factory's presettings of thecurrent transformer ratio is set to 10 and must be adaptedto the existing current transformer.If you should short-circuit the current transformer, theindicated value on DynamiC must decrease to 0A.

    Examples for the setting of the current transformerExample 1Current transformer 200A/5ASet DynamiC to 40

    Example 2Current transformer 500A/1ASet DynamiC to 500

    Example 3Sum current transformer 1000A+1000A/1ASet DynamiC to 2000

    Attention!For unequal load of the outer conductors, thecurrent should be measured in the outer con-ductor, which is loaded most heavily.

    Real powerIf current and voltage are connected to DynamiC ac-cording to the connection diagram, a positive real poweris displayed in case of real power consumption. Realpower with a negative sign in the indication points tothe supply of real power or an error of connection.Possible error:- Voltage and current are measured in the wrong outerconductor.- The current transformer clamps (k-l) are exchanged.

    Attention!None earthed current transformer clamps canbe live.

  • Page 12 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Switching outputsThe reactive power controller DynamiC can beequipped with up to 12 switching outputs. Theswitching outputs can be equipped either with relay ortransistor outputs. If a device is equipped with relay ortransistor outputs it is not shown on display. Theequipment can be seen in the connection diagram onthe back of DynamiC .

    Relay outputsCapacitor contactors can be connected to the relay out-puts according to the connection example "Relay out-puts".

    Transistor outputsSemi conductor switches, switching at zero crossing,must be connected to the transistor outputs of the reac-tive power controller.The transistor outputs switch the voltage of an externald.c. net supply to the semiconductor switches.

    Check switching outputsPlease switch in the capacitor stages in manual mode:The inductive reactive power is decreased by the powerof the respective capacitor stage.Please switch off the capacitor stages in manual mode:The inductive reactive power is increased by the powerof the respective capacitor stage.

    Possibility of errors:The outputs do not switch

    - Relay output defective.- Transistor output defective.

    The change of the reactive power is faulty- The current is measured incorrectly.- A wrong current transformer ratio is set.- The current is measured in the wrong outerconductor.- The voltage is measured in the wrong outerconductors.- The current transformer clamps k-l are exchanged.

    The reactive power does not change- The current transformer is installed at the wrongplace.- Switching outputs faulty.- The wrong control voltage is connected to theswitching outputs.

    Diagr.: Connection example "Transistor outputs"

    Attention !For devices with relay or transistor outputs,there are different control voltages appliedto the switching outputs.

    15-30VDC

    F0,2ADynamiC

    1

    2

    3

    C1

    Diagr.:Connection example "Relay outputs"

    Attention!The relai and transistor outputs are live.�

    DynamiC

    C1

    1

    2..1

    0A

    max. 250V

    2

    3

    Attention!If a switching frequency of 50Hz is programmedfor the transistor outputs, the serial interfacedoes not work!

  • Page 13= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Target-cos(phi) changeoverVia the input target-cos(phi) changeover it can bechanged over between target-cos(phi1) and target-cos(phi2).If there is no voltage at the input, the target-cos(phi1)is active. If there is a 85 bis 265V AC connected to theinput, the target-cos(phi2) is active.

    In the standard display (please see example), apart fromthe active channels and the actual cos(phi) also the ac-tive target-cos(phi) is indicated.

    Target-cos(phi1) is active.

    cosϕϕϕϕϕind

    1 2 3

    ϕ1ϕ1ϕ1ϕ1ϕ1

    Actual cos(phi) meanvalue

    Target-cos(phi2) is active.

    cosϕϕϕϕϕind

    1 2 3

    ϕ2ϕ2ϕ2ϕ2ϕ2

    Actual cos(phi) meanvalue

    Diagr.: Connection diagram target-cos(phi) changeover

    85 - 265V AC15

    16ϕ1

    ϕ2

    DynamiC

    Alarm outputThe alarm relay attracts in undisturbed operation, andthe contact of the alarm output is closed. If a distur-bance occurs, the alarm relay releases and the contact isopened. Various events can be assigned to the alarmoutput via OR-logic interconnections. Each event is as-signed to an alarm number, an alarm delay and alarmduration.

    Check alarm outputIf there is no alarm, the alarm relay attracts immedi-ately. In order to trigger off an alarm, the threshold forovertemperature can be set to zero, for instance, andthe alarm relay releases immediately.

    Diagr.: Connection diagram alarm output

    13

    14

    T6,

    3A

    max. 250V

    Error

    Prog

  • Page 14 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    RS485 Interface (Option)Transmission protocolsTwo transmission protocols are available for the connec-tion to an existing field bus system:

    0 - Modbus RTU (Slave) and1 - Profibus DP V0 (Slave) .

    With Modbus protocol you can have access to the data oftable 1, and with Profibus protocol you can have accessto the data of table 2.

    Bus structureAll devices are connected in bus structure (line). In onesegment up to 32 participiants can be assembled. At theend and the beginning of each segment, the cable mustbe terminated by resistors. In DynamiC you can activatethese resistors with two plug-ins.For more than 32 participiants you must use a repeater(line amplifier) to connect the single segments.

    ShieldingFor connections via RS485 interface, you need a pro-tected and twisted cable. To achieve a sufficient protec-tion result, the shielding must be connected at both endsextensively to the housing or parts of the cabinet.

    Cable specificationsThe maximum cable length depends on cable type andtransmission speed. We recommend cable type A.

    Cable parameter Type A Typ B

    Impedance 135-165Ohm 100-130Ohm(f = 3-20MHz) (f > 100kHz)

    Capacity < 30pF/m < 60pF/mResistance < 110 Ohm/km -Diameter >= 0,34mm2 >= 0,22mm2

    (AWG22) (AWG24)

    Cable lengthThe following table shows the maximum cable length inmeters (m) for various transmission speed.

    Baud rate (kbit/s)Cable type 9.6 19.2 93.75 187.5 500 1500

    Type A 1200 1200 1200 1000 400 200Type B 1200 1200 1200 600 200 70

    Terminal resistorsIf DynamiC is connected to the end of the bus cable,the bus cable must be terminated at this point withresistors. The required resistors are integrated within theDynamiC and are activated in position ON.

    Diagr. Connection RS485 interface

    10200740

    392R 221R 392R

    23

    22

    21

    A

    B

    +5V

    OFFON

    GND

    GND

    Termination

    DynamiC

  • Page 15= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Removal of errors

    Possible cause

    - Wrong measurement and supply voltageconnected.- Prefuse (10A time-lag type) has triggered.

    - Current measurement in the wrong outerconductor.- Wrong current transformer ratio.- Current out of measuring range.- Current transformer clamps are bridged.- One current transformer line is interrupted.- A current measuring device is connectedparallely.- Wrong voltage transformer ratio.

    - Uneven load of the outer conductors.- Wrong voltage transformer ratio.

    - Voltage and/or current are measured incor-rectly.- Voltage and current are measured in thewrong outer conductors.

    - Voltage and/or current are measured incor-rectly.- The current transformer connection (k-l) isexchanged.

    The measuring current is smaller but 10mA.The measuring voltage is interrupted.The current transformer clamps are bridged.

    - Voltage is measured incorrectly.- Current is measured incorrectly.- Real power is measured incorrectly.

    The current transformer is installed after themeasurement of the energy supplier.

    Current and voltage are connected in-cor-rectly.

    The capacitor current is not detected by thecurrent transformer.Capacitive stages are faulty.

    The measurement and operating voltage isexceeded by more than 10%.

    Current measurement in wrong phase.L1 and L3 are exchanged.

    The device is defective.

    Remedy

    Please check measurement and sup-ply voltage.

    Please check current measurement.

    Please check voltage measurement.

    Please check current and voltagemeasurement.

    Please check current and voltagemeasurement.

    Please check current measurement.

    Please check current and voltagemeasurement.

    Check and correct connection.(Please see hints for installation)

    Check and correct connection.(Please see hints for installation)

    Check and correct mounting posi-tion of the current transformer.Check capacitive stages.

    Check measurement and operatingvoltage.

    Check measurement and operatingvoltage.

    Send the device to the manufacturerwith an exact description of the error.

    Description of the error

    No indication.

    Currenttoo little / too high.

    VoltageL2-L3 too little / too high.

    Real powertoo little / too high.

    Real power supply/con-sumption exchanged.

    Cos(phi) = 0.00

    Cos(phi)too high / too little.

    Cos(phi) does not change,although all capacitorstages were switched in.

    Cos(phi) is indicated ca-pacitive on DynamiC , but,nevertheless, the reactivepower meter measures reac-tive power.DynamiC only connectsstages, but does not dis-connect.

    The outputs can only bedisconnected.

    DynamiC shows a cos(phi)of 0,2 - 0,4 capacitive.

    It does not work.

  • Page 16 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    ServiceIf certain questions appear, which are not mentioned inthis handbook, please call us directly.To be able to support you, we require the followinginformation:

    - Device description (see type plate),- Serial number (see type plate),- Software Release,- Measurement and supply voltage and- Exact description of the error.

    Maschinenfabrik Reinhausen GmbHPower Quality ManagementWiebestraße 46, 10553 Berlin, GermanyTel.: +49 30 33 09 15-0Fax: +49 30 33 09 15-25e-mail:[email protected]@reinhausen.comInternet: http:\\www.reinhausen.com

  • Page 17= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2 learn 1:1... Prog

    Display and useIn the front side of DynamiC there is a digitalindication and three keys, with which you can questiondata and program the device.If you are in automatical mode, you can change be-tween the operating modes using key 1:

    automatic mode,manual mode,standard programming andexpanded programming

    automatic modemanual modestandard programmingexpanded programming

    In standard programming often needed settings are car-ried out such as current transformer ratio or the numberof stages.In expanded programming those settings are carried out,which are used not as often, such as discharge time orchoke degree.

    To reach the expanded programming from automaticmode, leaf through the standard programming using key1 until the symbol "Prog" appears. Confirm selectionwith key 2, and you are in expanded programming.

    Automatic modeAutomatic mode is marked by the symbol .In automatic mode, there is:- the switching condition of capacitive stages,- the actual value of cos(phi) indicated,- Connection and disconnection of capacitive stages,- all 15 minutes saving of

    peak and lowest values,number of switchings of the capacitor stages andthe switching times of capacitor stages.

    - Indication of measured values using key 2 and 3.

    There are three possibilities to reach automatic mode:- after net return,- pressing key 1 for about 2 seconds,- pressing no key in programming mode for 1

    Automatic mode

    cosϕϕϕϕϕind

    1 2 3

    ϕ1ϕ1ϕ1ϕ1ϕ1

    Actual value cos(phi)

    Manual modeIn manual mode, you can switch in capacitor stagesusing key 3, and switch off capacitor stages using key2. The time between two switchings is only limited bythe programmed discharge time. If one stage shall beconnected in manual mode and a discharge time is run-ning, the number and capacitor stage is flashing.If no capacitors are switched in manual mode, anautomatical jumpback to automatical mode is carriedout after 15 minutes.

    Manual modeReactive power

    Connected stages

    k VArind

    1 2 3 4 5

  • Page 18 = Key 1 = Key 2 = Key 3

    Reactive Power ControllerC

    hang

    e m

    ode

    Lea

    fP

    rogr

    amm

    ing

    Expanded programming

    Automatic mode Manual mode

    Standard programming

    Password

    Meas. values

    Meas. values

    Meas. values

    Meas. values

    ProgrammingMenue

    2 seconds

    shor

    tlo

    ng

    long short

    short

    ProgrammingMenue

    ProgrammingMenue

    ProgrammingMenue

    Confirm selection

    Select number Select number

    short value *10long value /10

    short number +1long number -1

    short number +1long number -1

    short value *10long value /10

    ProgrammingMenues

    hort

    Key functions

    Prog

    ProgrammingMenue

    ProgrammingMenue

    shor

    tlo

    ng

    ProgrammingMenue

    Prog Prog

    2 seconds

  • Page 19= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2 learn 1:1... Prog

    Target cos(phi)In automatic modeDynamiC tries to reachthe set target powerfactor by switching inor off the capacitorstages.It is possible to set a target-cos(phi1) and a target-cos(phi2). Devices without target-cos(phi) changeoveralways use the target-cos(phi1). Devices with an inputfor target-cos(phi) changeover switch to target-cos(phi2),whenever the input is active.Range 0.80cap. - 1.00 - 0.80ind.

    The active target-cos(phi) is indicated in the measuredvalue indication for the actual-cos(phi).Example:

    cosϕϕϕϕϕind

    ϕ1ϕ1ϕ1ϕ1ϕ1

    cosϕϕϕϕϕind

    ϕ1ϕ1ϕ1ϕ1ϕ1

    ProgrammingPress key for about 2seconds to select auto-matic mode.

    Press key 1 to leaf tomanual mode until in-dication target cos(phi).

    Select the number to bechanged using key 2.The selected numberflashes.Change the selectednumber by pressingkey 3.

    Target-cos(phi1) is active.

    ϕ1ϕ1ϕ1ϕ1ϕ1

    Standard programmingIn the standard programming, the settings needed fre-quently are carried out, such as:- target-cos(phi1),- target-cos(phi2),- current transformer ratio,- learning of configuration,- power of the first capacitive stage,- stage ratio,- number of stages,- delete peak values (no indication).

    Standard-Programming

    Automatic mode

    cosϕϕϕϕϕind

    1 2 3

    ϕ1ϕ1ϕ1ϕ1ϕ1

    Automatic mode

    Manual mode

    Target cos(phi1)

    Press key 1 for about 2 seconds. You return to auto-matic mode, and the changes are saved immediately.

    In delivery condition no password is programmed. Thechange from automatic mode into standard program-ming is carried out without password protection.If a password is programmed by the user, the changefrom automatic mode to standard programming is car-ried out only after password clearance.Change from automatic mode to standard programmingand back:

    Password

    2 seconds

    short

    StandardProgramming

    Automatic mode

    cosϕϕϕϕϕind

    1 2 3

  • Page 20 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    ϕϕϕϕϕ1 ϕϕϕϕϕ2 learn 1:1... Prog

    Current transformer ratioAt the measuring in-put of the currentmeasure-ment either /5A or /1A currenttransformers can beconnected. In order to get a correct current and powerindication, the current transformer ratio of the connectedcurrent transformer must be set to DynamiC . If thecurrent is measured via a sum current transformer, thetotal current transformer ratio must be set.

    Example 1: Current transformer 500A/5AThe current transformer ratio is now calculated to

    500A : 5A = 100A ratio of 100 must be set on the device.

    Example 2: Current transformer 200A/1AThe current transformer ratio is calculated to

    200A : 1A = 200A ratio of 200 must be set on the device.

    Example 3: Sum current transformerTransformer 1 200/5ATransformer 2 400/5ASum current transformer 5+5/5AThe current transformer ratio is calculated to

    (200A + 400A) : 5A 600A : 5A = 120

    CT ratioAutomatic mode

    ProgrammingExample: Current transformer ratio 1000

    Select indication forcurrent transformer ra-tio using key 1.The automatic symboldisappears.

    Select the digit to bechanged. The selecteddigit is flashing.Change the selecteddigit pressing key 3.

    Current transformer ratios of more but 1000 are indi-cated with a decimal point automatically.Example: Current transformer ratio = 1200

    1200 = 1.200kIndication on display "1.200k"

    k

  • Page 21= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Learning of the configurationAfter installation of thecontroller there is thepossibility to learn andsave the configurationwith the function"learn".

    Important requirements are:- The discharge time for capacitors is set to 60 seconds,when the device is delivered. For capacitors with longerdischarge times, the discharge time must be checkedand changed before using the "learn" function.- The current transformer must be flown through byconsumer and compensation current.- The measurement and supply voltage may not be takenfrom phase to N.- The compensation system must be ready for opera-tion.

    The learning function of the controller is devided intotwo steps:Step 1 - Learning of the connection configurationHere the correction angle between current transformerand measurement and supply voltage is detected.Step 2 - Learning of the capacitor stagesHere the number of outputs and the stage power ofeach stage is detected.The following requirements are neccessary:- The switching of a capacitor stage must cause a changeof current of at least 50mA at current input.- The stage power of the stage to be learned must bebigger than 1% of the measuring range of the control-ler.

    Attention!After learning, the saved configurations must be checked,if they are plausible.

    Attention!After learning, the saved configurations must bechecked, if they are plausible.

    The following actions can be carried out:oFF - No learning. 1 - Step 1, learning of the connection configura-tion. 2 - Step 2, learning of capacitor stages. 3 - Step 1 + 2, learning of the connection

    configuration and capacitor stages.

    learn

    Prog

    Start learningGo to symbol learn us-ing key 1.Select action (oFF, 1,2, 3) with key 3.Start learning with key1.The symbol learn flashes. The controller learns.During the learning the capacitor stages are switchedfor several times. The learning can only be interruptedby switching off the power factor controller.The duration of the learning procedure depends on thenet conditions, the number of capacitor stages and theset discharge time for the capacitors.

    When the learning procedure is finished, the detectedcorrection angle, in theexample 270°, is indi-cated.The learned character-istics are saved.

    After 60 seconds the controller changes to automaticmode. Pressing key 1 for 2 seconds, you reach auto-matic mode at once.

    learn

  • Page 22 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2 learn 1:1... Prog

    ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2 learn 1:1... Prog

    Stage ratioThe stage ratio statesthe ratio of the stagepower of the variouscapacitor stages. Thepower of the first ca-pacitor stage serves as a reference. The stage ratio isprogrammable for each stage up to the fifth stage.

    Setting range : 0 - 9In the display only the stage ratio for the capacitorstages 2, 3, 4 and 5 are indicated. The stage ratio forthe first capacitor stage is always 1.

    Example 2The stage ratio is programmed to 1:2:0:2:2:2.... In the4-digit display only the part "2:0:2:2" is indicated.

    Example 1The stage ratio is programmed to 1:2:4:8:8:8..., and inthe four digit-display, only the part "2:4:8:8" is indi-cated.

    Stage powerThe stage power is thepower of a capacitorstage. In the standardprogramming the stagepower can only be pro-grammed for the first stage. In the expanded program-ming you can set the stage power for each capacitorstage. If you only enter the stage power for the firstcapacitor stage, the other stages are fixed by the stageratio. The stage power of each capacitor stage can becalculated from the first stage and the correspondingstage ratio.

    Ratio 0var - 9999kvar

    Example 1Power of the first capacitor stage = 10kvarStage ratio = 1:1:1:1:1....All following stages have the power: 10kvar

    Example 2Power of the first capacitor stage = 20kvarStage ratio = 1:2:4:8:8....The stages have the power:

    1. Stage = 20kvar2. Stage = 40kvar3. Stage = 80kvar4. Stage = 160kvar5. Stage = 160kvaretc.

    1:1...

    Please select the indi-cation for stage powerusing key 1.The automatic symboldisappears.

    Select the digit to bechanged using key 2.The selected digit isflashing.Change the digit bypressing key 3.

    Example: Programming stage power

    Stage powerAutomatic

    k VAr

    If all numbers are flashing, the decimal point of the setnumber is moved.

    Please select the indi-cation of the stage ra-tio using key 1.The automatic symboldisappears.

    Please select the digitto be changed usingkey 2. The selecteddigit is flashing.Change the selecteddigit by pressing key 3.

    Example: Programming stage ratio

    1:1...

    Stage ratioAutomatic

    If the first capacitor stage has a power of 10kvar, thefollowing stages have the power:

    1. Stage = 10kvar2. Stage = 20kvar3. Stage = 0kvar4. Stage = 20kvar5. Stage = 20kvaretc.

    1 . 2 . 4 . 8 . 8 . 8....

    Indicated on display.

    1. capacitor stage5. capacitor stage

    1 . 2 . 0 . 2 . 2 . 2....Indicated on display.

    1. capacitor stage5. capacitor stage

    k VAr

  • Page 23= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2 learn 1:1... Prog

    ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2ϕ1 ϕ2 learn 1:1... Prog

    The switching outputs can be equipped with either re-lay or transistor outputs.If a device is equipped with relay or transistor outputsit cannot be read on display. The equipment can onlybe seen on the back side of DynamiC in the connectionexample.

    Example 2: DynamiC with 3 transistor outputsPlease check, if 3 transistor outputs are programmed.The programming and indication of the switching out-puts is carried out in the menu standard programming.

    Please go to the indi-cation of the number ofstages.The automatic symboldisappears.

    Only two stages areprogrammed!Select the digit to bechanged using key 2.The selected digit isflashing.Change the selecteddigit using key 3.

    DynamiC is available in three varieties regarding theswitching outputs.1. Only relay outputs2. Only transistor outputs3. Relay and transistor outputs mixed

    In the menus of the standard programming, only thevariations 1 and 2 can be programmed.In mixed operation the switching outputs with smallernumbers are always the relay outputs.The relay outputs in mixed operation are programmedin the menu of standard programming, and the transis-tor outputs are programmed in the menu of expandedprogramming. The programming of the transistor out-puts is carried out indirectly via the stage power of theswitching outputs. For transistor outputs, to which nosemiconductor switch is connected, a capacitor powerof 0kvar is set.

    Please select the indi-cation of the switchingoutputs using key 1.The automatic symboldisappears.

    Please select the digitto be changed usingkey 2. The selecteddigit is flashing.Change the selecteddigit by pressing key 3.

    Example 1: DynamiC with 12 relay outputs10 of the 12 existing outputs shall be engaged.The programming and indication of the switching out-puts is carried out in the menu standard programming.

    Switching outputsAutomatic

    Switching outputsAutomatic

    Switching outputs

    Variety 1 2 3 4 5 6 7 8 9 10 11 12

    3R R R R3T T T T6R R R R R R R6T T T T T T T6R6T R R R R R R T T T T T T12R R R R R R R R R R R R R12T T T T T T T T T T T T T

    T= Transistor outputsR= Relay outputs

    Diagr. Varieties of the switching outputs

    Switching outputs

    The reactive powercontroller DynamiCcan be equipped withup to 12 switchingoutputs.

    Switching outputs

  • Page 24 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Prog

    Example 3: DynamiC 6R6T with 6 transistor outputsand 6 relay outputsTwo transistor outputs and 6 relay outputs shall be pro-grammed.The programming of the relay outputs is carried out inthe menu standard programming, and the programmingof the transistor outputs is carried out in the menu ex-panded programming.

    1. step: Programming of the relay outputs.In standard program-ming you move to theindication of thenumber of stages usingkey 1. 6 stages are pro-grammed, so no change is required.

    2. step: Programming of the transistor outputs.The programming of the transistor outputs is carriedout in the expandedprogramming.Please move to the ex-panded programmingusing key 1. Now presskey 2.In the expanded pro-gramming appears themenu point "Fixstages".

    Prog

    Prog

    Using key 3, you reachthe indication stagepower.

    Here the stage (7) is se-lected by pressing key2. Please confirm withkey1. One digit for thestage power is flashing.

    k VAr

    1

    Prog

    If this stage is engaged, the required stage power mustbe programmed by pressing the keys 2 and 3.Select the digit to be changed using key 2. The selecteddigit is flashing. Now change the digit using key 3.If all ciphers are flashing, the shown digit can be multi-plied by 10 using key 3. Also the dimension of the unitcan be changed.

    Delete peak and lowest valuesPeak and lowest valuesof various measuredvalues are saved every15 minutes.The peak values andlowest values can only be deleted altogether.The following values are not deleted:

    Peak temperature value,Switching time of the capacitor stages andNumber of switchings per stage.

    Example: Delete peak values

    Move to indication forpeak and lowest valuesby pressing key 1.The automatic symboldisappears.

    Select delete with key 3.Text "on" is flashing.With key 1 you moveto the expanded pro-gramming and activatedeletion.

    VAr

    7

    flashing

    Automatic

  • Page 25= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Prog

    Fix stagesThe first three capaci-tor stages can be fixedswitched in alterna-tively. Fix stages aremarked by a line be-low the number of the capacitor stage.Fix stages cannot be included in the controlling. Never-theless they are considered in the stage ratio, so that inthe stage ratio in the most disadvantageous case (threefix stages) in the standard programming only two stageratios are available. To get a better solution of the stagepower, the capacitor power must be set for every singlestage in the expanded programming .

    Prog

    1. capacitor stage (Fix stage)2. capacitor stage (Fix stage)3. capacitor stage (Fix stage)

    controllable capacitor stages

    Example 1: Indication of stage ratio

    Example: Programming of fix stagesPlease select the fixstages by using key 1.The first three stagenumbers are flashing.

    1 2 3

    Prog

    cosϕϕϕϕϕind

    1 2 3 5 6 12

    ϕ2 ϕ2 ϕ2 ϕ2 ϕ2

    The fix stages 1, 2 and3 are switched in

    Target-cos(phi2) is active.

    Capacitor stages 5,6 and 12are switched in

    The actual mean cos(phi) is 0.96ind.

    Example 2:Indication of fix stages in automatic mode

    Indicated on display

    Expanded programmingIn the expanded pro-gramming those set-tings are carried out,which are requiredvery rarely.With key 3 you can change between the indications.With key 1 the selected indication can be chosen forchanging.

    The following settings and readings can be carried out inexpanded programming:

    Fix stages,Discharge time,Disconnection pause of relay stages,Power station service,Stage power, 1. - 2. stage,Choke degree,Voltage transformer ratio,Harmonic table,Switching frequency of transistor stages,Alarm calls,Averaging time for reactive power,Averaging time of the mean value cos(phi),Fan control,Overtemperature disconnection,Indication in manual mode,Password,Contrast,Reset of programming,Connection configuration,Software release andSerial number.Power station service,Stage power, 1. - 2. stage,Choke degree,Voltage transformer ratio,Harmonic table,Switching frequency of transistor stages,Alarm calls,Averaging time for reactive power,Averaging time of the mean value cos(phi),Fan control,Overtemperature disconnection,Indication in manual mode,Password,Contrast,Reset of programming,Connection configuration,Software release,Serial number andRS485 interface.

    1 : 2 : 4 : 8 : 8 : 8....

    All three fix stagesare switched on.

    1 2 3

    Prog

    With key 3 you switchin the fix stages.With key 2 you dis-connect the fix stages.Confirm selection withkey 1 and continue with expanded programming usingkey3.

  • Page 26 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Discharge timeThe discharge timemeans the time, whicheach capacitor stagehas got for discharge.

    Setting range : 0 - 1200 seconds

    The discharge time will be started after a net return andafter switching of a capacitor stage.Capacitor stages controlled by transistor outputs mustnot consider the discharge time, as the therewith con-trolled semiconductor switches in the zero crossing ofvoltage.

    Example: Programming discharge timeWith key 3 you can leaf to the discharge time in theexpanded programming. With key 1 you get into pro-gramming mode. In this example a discharge time of60 seconds is indicated.

    Select the digit to bechanged using key 2.The selected digit isflashing.Change digit using key3.

    Pressing key 1 you leave the programming mode andwith key 3 you can continue leafing through the ex-panded programming.

    Disconnection pauseThe disconnectionpause means the timeafter the connection ofa capacitor stage, inwhich it is forbidden todisconnect the next stage.

    Setting range : 0 - 1200 seconds

    The disconnection pause is not valid for capacitor stages,switched via transistor outputs.

    Example: Programming of disconnection pauseWith key 3 you leaf to the disconnection pause in ex-panded programming. Please press key 1. In this exam-ple a disconnection pause of 15 seconds is indicated.

    Select the digit to be changed by using key 2. Theselected digit is flash-ing.Change the selecteddigit using key 3.

    Pressing key 1 you leave the programming mode andwith key 3 you can continue leafing through the ex-panded programming.

    s

    Prog

    s

    Prog

    Prog s

    Prog s

  • Page 27= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Confirm selection withkey 1.Text "on" flashes.Set function "powerstation service" to "oFF" using key 2 and to "on" usingkey 3.Confirm with key 1 and continue with expanded pro-gramming pressing key 3.

    Power station serviceBy setting "power sta-tion service" the reac-tion of the controller atsmall currents is con-trolled.Presetting: Power station service = "oFF"

    Power station service= "oFF"If no or a very small current is flowing through thecurrent transformer, all connected capacitor stages areswitched off one after the other.

    Power station service = "on"If delivery (power station service) and consumption ispossible, connected stages must remain connected tothe net, even if no current is measured.

    ProgrammingExample: Power station serviceGo to power station service in expanded programmingusing key 3.

    If real power is generated in a certain application, thefollowing situations can arise:Case a.The generated real power is smaller than the demand.Additionally real power is delivered by the energy sup-plier.

    Case b.The generated real power is bigger than the demand.Real power is supplied.

    Case c.The generated real power corresponds to the demand.

    In all cases the required reactive power is supplied bythe energy supplier, or even better, by a compensationsystem.The following situation can come into being. The neededreal power is completely generated (case c.) by the gen-erator, and the reactive power is completely suppliedby a compensation system.There is no current flowing through the current trans-former. If the power station service, by mistake, is on"oFF", the capacitor stages are disconnected. Then areactive current is flowing again through the currenttransformer. The controller detects a need for compen-sation, and connectes the stages again. The reactive cur-rent is compensated. Again, no current is flowing.The problem is, that the number of switchings is in-creased.For power station service, especially in case c, the powerstation service should be set to "on".

    Diagr.: Connection example power station service

    reactive powerBlindleistung

    real powerWirkleistung

    L1

    DynamiC

    M G

    reactive power compensation systemBlindleistungs-Kompensationsanlage

    consumerVerbraucher

    generatorGenerator

    L2L3

    k l

    1020

    0610

    Prog

    Prog

  • Page 28 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Choke degreeThe choke degree mustbe set for choked orcombined choked com-pensation systems. Thechoke degree is neededfor the exact determination of the capacitor current.With the choke degree you lay down the switching or-der in combined choked compensation systems. Capaci-tor stages with a high choke degree and low chokedegree are switched alternatingly. Capacitor stages witha high choke degree are switched in first.If more but two different choke degrees are set, thecapacitor stages with the middle choke degrees areswitched as unchoked capacitor stages.

    Attention!To reduce the programming expenditure, the program-ming of the first capacitor stage is taken over for all thefollowing capacitor stages. Nevertheless, the choke de-gree can be changed for the following capacitor stagesafterwards.

    The choke degree is given for each capacitor stage inpercent.

    Setting range : 0 - 15%

    Stage powerThe stage power is thecapacitive reactivepower of a capacitorstage. The stage powercan be set in the ex-panded programming for each stage. In the standardprogramming, the stage ratio 0000 is indicated.

    Setting range 0 var - 9999kvar

    Example: Programming stage powerWith key 3 you can leaf to the stage ratio in expandedprogramming. Please press key 1 to confirm. In thisexample, a stage power of 10kvar is indicated for thefirst capacitor stage.

    Select the digit to bechanged using key 2.The selected digit isflashing.Change the selected digit using key 3.

    Pressing key 1 you leave the programming mode andwith key 3 you can continue leafing through the ex-panded programming.

    Example: Programming choke degreePlease leaf to the choke degree in the expanded pro-gramming using key 3. In this example, for the firststage a choke degree of 5,7% is needed. For the pro-gramming, 6% was selected.

    Pressing key 1 you leave the programming mode andwith key 3 you can continue leafing through the ex-panded programming.

    %

    1

    Prog

    Select the digit to bechanged using key 2.The selected digit isflashing.Change the selecteddigit by pressing key3.

    If the choke degree for the second capacitive stage mustbe programmed, you leaf to the desired capacitor stagepressing key 2.The selected capacitor stage is confirmed by pressingkey 1.

    %

    2

    Prog

    2. capacitor stage

    k VAr

    1

    Prog

    k VAr

    1

    Prog

    1

    Prog

    %

  • Page 29= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Voltage transformer ratioIf the measurement and operating voltage for DynamiCis taken from a voltage transformer, the voltage trans-former ratio can be set. This ratio is build by number 1and number 2 .

    Programming number 1Leaf to number 1 for voltage transformer ratio in ex-panded programming using key 3. Confirm with key 1.In this example,number 1 = 1.

    Select the digit to bechanged by pressingkey 2. The selected digit is flashing.Change the selected digit using key 3.With key 1 you can leave programming mode and withkey 3 you continue expanded programming.

    number 1Voltage transformer ratio =

    number 2

    Attention! If a wrong voltage transformer ratio is set,all voltage as power is indicated incorrectly.

    The setting ranges for the numbers 1 and 2 are:number 1 : 1 - 9.999knumber 2 : 1, 10, 100, 110, 200, 230, 400

    In this example, thepresettings are indi-cated with number 1 = 1 and number 2 = 1.

    Programming number 2Leaf to number 1 for voltage transformer ratio in ex-panded programming using key 3. Change to number 2with key 2. In this ex-ample a value of 1 isindicated for number 2.Confirm selection withkey 1.The value flashes.With key 2 and key 3the needed value canbe selected for number2 from a list of values(1, 10, 100, 110, 200,230, 400).Confirm selection with key 1. The selected value doesnot flash anymore.

    Continue expanded programming with key 3.

    Number 1

    Number 1 is indicated with a decimal point automati-cally, when the value gets bigger than 1000.Example: Voltage transformer ratio = 1200

    1200 = 1.200kIndication "1.200kV"

    Example: Programming voltage transformer ratioA voltage transformer has a primary of 20000V and asecondary of 100V.The result is a ratio of

    20000V = 200

    100VThe measurement and supply voltage mentioned on typeplate of DynamiC must be 100V.To set the ratio of 200, several combinations of number1 and number 2 are possible.

    e.g. number 1 200 = = 200

    number 2 1

    or number 1 2000 = = 200

    number 2 10

    kV

    Prog

    V

    Prog

    Number 2

    V

    Prog

    V

    Prog

    Prog

    V

    V

    Prog

  • Page 30 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Harmonic thresholdsIn order to avoid reso-nance in the net and toprotect capacitors fromoverload, a thresholdrow should be selectedfrom the threshold table. If a harmonic threshold is ex-ceeded, capacitive stages are switched off for the dura-tion of the discharge time.

    Setting range 0 - 10

    In order to avoid too much switchings of capacitorstages, the capacitor stages are only switched on, whenthe harmonic threshold of a lower threshold row is ex-ceeded.If the threshold row is selected for 0, no capacitorstages are switched off. The thresholds of thresholdrow 0 are only taken as the lower threshold row forthreshold row 1.

    Harmonic thresholds in % of nominal voltage

    Threshold row number 1 2 3 4 5 6 7 8 9 10

    3. 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.05. 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.07. 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.09. 1.2 1.2 1.5 1.5 2.0 4.0 4.5 5.0 5.5 6.011. 2.5 3.0 3.0 3.5 4.0 5.0 5.5 6.0 6.5 7.013. 2.0 2.1 2.5 3.0 4.0 5.0 5.5 6.0 6.5 7.015. 1.0 1.2 1.5 1.5 1.8 2.0 2.2 2.5 2.0 2.317. 1.5 1.5 2.0 2.0 2.3 2.0 2.5 3.0 3.5 4.019. 1.0 1.2 1.5 1.5 1.8 2.0 2.2 2.5 3.0 3.5

    Har

    mon

    ic n

    umbe

    r

    Example: Programming threshold rowLeaf to the harmonic table in the expanded program-ming using key 3. Confirm with key 1. In this examplethe threshold row 1 is indicated.

    Select the digit to bechanged by pressingkey 2. The selecteddigit is flashing.Change the selecteddigit by pressing key 3.

    Pressing key 1 you leave the programming mode andwith key 3 you can continue leafing through the ex-panded programming.

    V

    Prog

    V %

    Prog

  • Page 31= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Switching frequencyThe switching fre-quency determines,how often per seconda transistor output maybe switched at maxi-mum.

    Possible switching frequencies are:0,1Hz, (preset)0,2Hz,0,5Hz,1,0Hz,10,0Hz and50,0Hz.

    The delay time between two switchings of transistoroutputs is fixed to a minimum of 70ms, except for"50.0Hz".

    Switching frequency 0,1HzIf a switching frequency of 0,1Hz is set, a transistoroutput is switched in and off within 10 seconds onetime at maximum.

    Switching frequency 10HzIf a switching frequency of 10Hz is set, a transistoroutput is switched in and off 10 times per second atmaximum.

    Schaltfrequenz „50,0Hz“Die Zeit von einer Signaländerung im Netz, bis zumAuslösen einer Schalthandlung am Transistorausgangdes DynamiC , beträgt maximal 20ms. Die Zeit zwischenzwei Schalthandlungen beträgt minimal 50ms. Wird eineSchaltfrequenz von 50Hz für die Transistorausgängeprogrammiert, so ist die serielle Schnittstelle außerFunktion.

    Example: Programming switching frequencyGo to the switching frequency using key 3 in expandedprogramming. Change to programming mode with key1. In this example, a switching frequency of 10,0 Hz isindicated.

    The set frequency isflashing.Now select the neededfrequency with key 2and 3.

    Pressing key 1 you leave the programming mode andwith key 3 you can continue leafing through the ex-panded programming.

    Attention!If a switching frequency of 50Hz is programmedfor the transistor outputs, the serial interface doesnot work!

    Hz

    Prog

    Hz

    Prog

  • Page 32 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Alarm outputIn undisturbed ope-ra-tion, the alarm relay at-tracts, and the contactof the alarm output isclosed. In case of a dis-turbance, the alarm relay releases and the contact isopened. Various events can be assigned to the alarmoutput via or-conjunctions. One alarm number, one alarmdelay and one alarm duration are assigned to each event.The alarm call can be activated or deactivated for eachevent.

    "on"/number = Alarm call is activated."oFF" = Alarm call is deactivated.

    The following events can be assigned to the alarm out-put:

    Alarm callIf one or more alarms occur, DynamiC changes to analarm indication. In the alarm indication, the errors areshown by their number. In the following example, theerrors "lower voltage" and "compensation power"occurred.The time and dimension of the error is not saved.

    Give a receipt for alarmsIf you confirm the alarm message with key 3, you reachthe last measured value indication. The error symbol"Error" remains within the measured value indicationsuntil the errors are not valid anymore.

    1 5 Error

    Low voltage Compensation power

    If other error messages appear after the confirmation ofan error message, the alarm indication appears againwith new error messages. Older errors, which are notvalid anymore, are flashing.

    Example: Programming compensation powerLeaf to the first alarm in the expanded programmingwith key 3. Please leaf to compensation power (5) withkey 2 and confirm with key 1.

    Pressing key 1 you leave the programming mode andwith key 3 you can continue leafing through the ex-panded programming.

    With key 3 the alarm "compensation power" is acti-vated (on), with key 2 the alarm "compensation power"is deactivated (oFF).

    Alarm-number Event Condition 1 Lower voltage oFF/number 2 Overvoltage oFF/number 3 Underscoring of meas.current oFF/number 4 Exceeding of meas. current oFF/number 5 Insufficient capacitor output off/on 6 Supply of real power off/on 7 Harmonic thresholds oFF/number 8 Overtemperature oFF/number

    Example: Alarm message

    VAr

    5 Error

    Prog

    V %

    1 Error

    Prog

    cosϕϕϕϕϕind

    2 3 Error

    ϕ1ϕ1ϕ1ϕ1ϕ1

    Error symbol

  • Page 33= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Lower voltage (1)A lower voltage is recognized, when the measurementand supply voltage is smaller or equal to the rated volt-age given on type plate.If lower voltage occurs, it is recognized after 100mslatest, and the alarm output is active for at least 1 minute.The threshold for lower voltage is programmable in 1%steps in the range of 85% and 99%.

    ExampleSelected threshold : 85%85% of the rated voltage of 400V make 340V.If the voltage of 340V is underscored, the alarm relayreleases.

    Attention!If the measurement and operating voltage falls below85% of the rated voltage, all capacitor stages areswitched off after about 20ms.

    Overvoltage (2)Overvoltage is recognized, when the measurement andsupply voltage is higher or equal to the rated voltagegiven on type plate.If overvoltage occurs, this will be recognized after100ms latest, and the alarm output is active for at least1 minute.The threshold for overvoltage can be programmed inthe range of 96% up to 110% of the rated voltage in1% steps.

    ExampleSelected threshold : 110%110% of the rated voltage of 400V make 440V.If the voltage of 440V is exceeded, the alarm relayreleases.

    Underscoring of the measurement current (3)The rated current of a measuring input is 5A. If theselected threshold for the measurement current is un-derscored, after 100ms maximum the alarm relay re-leases for at least 1 minute.The threshold for underscoring the measuring currentcan be programmed in the range of 0% up to 28% ofthe rated current in 2% steps.

    ExampleSelected threshold : 10%10% of the rated current of 5A make 0.5A.If the current of 0.5A is underscored and the alarmrelay releases.

    Exceeding of measuring current (4)The current of current measurement input is 5A. Therated current of the current measuring input is 5A. Ifthe preset threshold for the measurement current is ex-ceeded, the alarm relay releases after 100ms latest forat least 1 minute.The threshold for exceeding the measurement currentcan be set in the range of 50% up to 120% of the ratedcurrent in 5% steps.

    Example 1Selected threshold : 95%95% of the rated current 5A make 4.75A.If the current of 4.75A is exceeded, the alarm relayreleases.

    Insufficient capacitor output (5)If the required compensation power is not reached forone hour, the alarm relay releases for at least one minute.

    Supply of real power (6)If more real power is supplied than consumed (powerstation service), the alarm relay releases after 100mslatest for at least 1 minute.

    Harmonic thresholds (7)If a value in the selected harmonic threshold table isexceeded, the alarm relay releases after 100ms latestfor at least 1 minute.

    Overtemperature (8)The reactive power controller is laid out for the operat-ing temperature range between -10°C and +55°C. Theinner temperature of the reactive power controller isabout 2°C higher than the temperature within the cabi-net.If the programmable threshold for the controller innertemperature is exceeded, the alarm relay releases after100ms latest for at least 1 minute.Setting range for the temperature : 0..99°C

    Attention!For inner temperatures of more than 70°C thealarm will always be raised.

  • Page 34 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Averaging time for the mean value cos(phi)DynamiC measuresreal and reactive workwithin the averagingtime and calculates themean value cos(phi).

    Setting range: 0.25h0.50h1.00h2.00h12.00h24.00h (presetting)

    Example: Programming of the averaging time for themean value cos(phi).Go to averaging time for the mean value cos(phi) inexpanded programming with key 3.Confirm selection with key 1.In this example, an av-eraging time of onehour is indicated andflashes.With key 2 and 3 thedesired averaging time can be selected.Press key 1 for confirmation and with key 3 you cancontinue leafing through the expanded programming.

    Averaging time of reactive powerThe measured reactivepower is summarizedwithin the averagingtime and the meanvalue of reactive poweris calculated.

    Setting range: 0,1 Sec.0,5 Sec.1,0 Sec.5,0 Sec.10,0 Sec.30,0 Sec.60,0 Sec. (Presetting)

    VAr s

    Prog

    VAr h

    Prog

    VAr h

    Prog

    Example: Programming of the averaging time for reac-tive power.Go to averaging time for the mean value reactive powerin expanded program-ming with key 3.Confirm selection withkey 1.In this example an av-eraging time of 5 seconds is indicated and flashing.Now the desired averaging time can be selected withkey 2 and key 3.Press key 1 for confirmation and with key 3 you cancontinue leafing through the expanded programming.

    VAr s

    Prog

  • Page 35= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Ventilator controlWith the temperaturefeeler, inserted inDynamiC , and a ven-tilator, a simpleventilator control canbe established.Therefore, an

    upper temperature limit, alower temperature limit and aswitching output

    must be fixed.Please note, that the inner temperature of the DynamiCis about 2°C over the outer temperature.A relay output or the alarm output (option) serves asventilator output.If the switching output 0 is assigned to the ventilatorcontrol, the ventilator control is not active.An upper and lower temperature limit can be set. Thetemperature limits can be set in the range of 0°C and98°C in 1° steps. While programming, you can only setan upper limit, when it is at least 1°C over the lowerlimit.

    Attention! If an output is programmed for ventilatorcontrol, and if it is also programmed for a fix stage oralarm output, the ventilator control has higher priority.

    Prog

    Obere Grenztemperatur

    Attention!If one output has been programmed for ventila-tion control, and additionally, it is programmedas a fix stage or alarm output, the ventilationcontrol has priority.

    Prog

    Upper temperature limit(Ventilation control)

    Prog

    Upper temperature limit(Ventilation control)

    Lower temperature limitIf temperature is belowthe lower limit, theventilation is switchedoff.

    Switching outputOne of the relay out-puts or the alarm out-put can be used asswitching output ofDynamiC .If output 0 is assignedto the ventilation control, the ventilation control is in-activated.

    Prog

    Lower temperature limit(ventilation control)

    Upper temperature limitIf the upper limit is ex-ceeded, the ventilationis switched on.

    Ventilation controlUsing the temperaturesensor, which is in-serted within DynamiC, a simple ventilationcontrol can be built.

    To reach this goal, anUpper temperature limit, aLower temperature limit andA switching output

    must be determined.

    While programming of temperature limits, please mind,that the inner temperature of DynamiC is about 2°Cabove the outer temperature.The temperature limits can be set in the range of 0°Cand 98°C in1°C steps.While programming, it is only possible to set the uppertemperature limit, when it is at least 1°C above thelower limit.

    Prog

    No output selected

  • Page 36 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Prog

    Upper temperature limit

    Prog

    Lower temperature limit

    Example: Assign one output to ventilator controlGo to upper tempe-rature limit in ex-panded programmingusing key 3.Move to selection ofthe output using key 2.Output number 13 means the alarm output. Confirmselection with key 1. The first digit is flashing.Select the digit to be changed with key 2 and changewith key 3.Confirm selection with key 1. No digit is flashing.Carry on in expanded programming with key 3.

    Example: Programming of the lower temperature limitGo to upper tempe-rature limit in ex-panded programmingusing key 3.

    Go to lower limit us-ing key 2.Confirm selection withkey 1. The first numberis flashing.Select number with keytwo and change with key 3.Confirm selection with key 1. No digit is flashing.Carry on in expanded programming with key 3.

    Diagr.: Connection example, reactive power controller with connected ventilator motor

    motor ofventilator

    Prog

    No output selected

  • Page 37= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Example: Programming of the upper temperature limitGo to upper temper-ature limit in expandedprogramming usingkey 3.Confirm selection withkey 1. The first digit is flashing.Select number with key 2 and change with key 3.Confirm selection with key 1. No digit is flashing.Carry on in expanded programming with key 3.

    Example: Programming of the lower temperature limitGo to upper temperature limit in expanded program-ming using key 3.Then move to lower limit with key 2.Confirm selection withkey 1. The first digit isflashing.Select number with key2 and change with key3.Confirm selection with key 1. No digit is flashing.Carry on in expanded programming with key 3.

    Example: Programming of the pause timeGo to upper temperature limit in expanded program-ming using key 3.Go to pause time withkey 2.Confirm selection withkey 1. The first digit isflashing.Select number with key 2 and change with key 3.Confirm selection with key 1. No digit is flashing.Carry on in expanded programming with key 3.

    Overtemperature disconnectionIn cabinets there mightbe an exceeding of theinner cabinet temper-ature, effected bypower dissipation ofcon-nected capacitor stages or too high outer tempera-ture.In that case, also the DynamiC controller is heated up,and the inner temperature feeler detects this rise of tem-perature with a little delay. With the overtemperaturedisconnection, connected stages can be disconnectedin order to decrease the inner temperature and to protectthe capacitors from damage.The following values can be set:

    - upper temperature limit,- lower temperature limit and- pause time.

    Upper temperature limit

    Lower temperature limit

    Disconnection of capacitors

    temperature

    t

    t

    Diagr.: Overtemperature disconnection with hysteresis

    � Attention!If the upper temperature limit is set below thelower temperature limit while editing, the lowerlimit is decreased automatically.

    Upper temperature limitIf the upper temperature limit is exceeded, connectedcapacitors are disconnected.

    Lower temperature limitIf the lower temperature limit is exceeded, no morestages are connected anymore.

    Pause timeIf the lower temperature limit is exceeded, one capaci-tor stage will be disconnected, and the pause time isstarted. After the pause time is over, the next capacitorstage can be disconnected.

    Attention! The overtemperature disconnectionalso disconnects programmed fix stages.�

    sProg

    Prog

    Prog

  • Page 38 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Indication in manual modeWhile switching ca-pacitor stages inmanual mode, eitherthe actual cos(phi) oractual real power canbe indicated.

    CAr = Indication of reactive powerCoS =Indication of cos(phi)

    Prog

    Prog

    Example: Selection of indication in manual modeMove to selection of the indication in manual modewith key 3.Confirm with key 1.The last selected value,CoS or CAr, is flash-ing.With key 3 can bechanged over to CoS and with key 2 to CAr.Confirm selection with key1.The selected text is no longer flashing.Carry on expanded programming using key 3.

  • Page 39= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    PasswordThe settings ofDynamiC can beprotected against unin-tentional change by afour digit user pass-word. This denies the access to the menus:

    - manual mode- standard programming and- expanded programming.

    DynamiC works in automatic mode and only themeasured values can be seen.In delivery condition, no password (“0000”) is pro-grammed, the user has full access to all menus.After programming a password, it is always requestedbefore accessing one of the locked menus. The pass-word can be changed within the expanded program-ming. If (“0000”) is entered as a password, the user hasfull access to all menus.

    If a changed password is not known anymore,the device has to be sent back to the manufactur-ing work.

    Program passwordIf no password was programmed so far, please proceedas follows:Scroll to expanded pro-gramming by pressingkey 1. The symbol“Prog” is flashing.Confirm selection withkey 2.The menu for program-ming the fix stages ap-pears.

    Scroll to menu pass-word by pressing key3. Confirm selectionwith key 1.The first number of thepassword is flashing.Select the digit, which shall be changed, with key 2.The selected number is flashing.Change number with key 3.If the password has been completed, confirm passwordwith key 1.No digit is flashing now.The new password is active.

    Prog

    Prog

    Enter passwordIf the programming is protected by a password, youmust enter this password to have access to the lockedmenus.Press key 1. The firstdigit is flashing.Select the number,which should bechanged with key 2.The selected number flashes.Change number with key 3.If the password is completed, end input with key 2.If the password was invalid, the request for a passwordappears again.

    If the password wascorrect, you are inmenu “manual mode”of the standard pro-gramming.Scroll to the required programming menus with key 1.

    The programming menus are locked again automati-cally, when no key was pressed over 60 seconds.

    Change passwordTo enter a new password, please change to expandedprogramming by using the old password, which has tobe entered first.Confirm with key 1.The first digit of thepassword is flashing.Now enter the old pass-word.Select the number to be changed by key 2, the selectednumber is flashing.Change the selected number with key 3.If the password is completed, confirm with key 2.If the password was invalid, the request for the pass-word appears again.

    If the password was correct, you are in menu “manualmode” of the standardprogramming.Now you can overwritethe password as de-scribed under “pro-gram password”.

    � Entering the password “0000” releases the lockof the programming menus.

    Prog

    Prog

    Prog

    Prog

  • Page 40 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    ContrastThe preferred view ofthe indication is "frombelow", which means,that the display can beread best in this view.The contrast betweenthe characters and the background is the highest.Little changes of the view can be evened out by thecontrast setting. The contrast of the indication can bechanged by the user.

    Setting range 1 - 12

    To get an optimal contrast for the whole temperaturerange, the contrast of the indication is self adjusting forchanges of the ambient temperature. This correction isnot indicated in the contrast setting.

    Prog

    6

    Example: Programming contrast

    Pressing key 1 you leave the programming mode andwith key 3 you can continue leafing through the ex-panded programming.

    Prog

    6

    Contrast = 6

    Go to the next higherdigit using key 2.

    Go to the next smallerdigit using key 3.

    Prog

    7

    Move to contrast in theexpanded program-ming using key 3.Confirm with key 1.The text "Cont" isflashing.

    Prog

    5

    Contrast = 7

    Contrast = 5

  • Page 41= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Reset programming

    Prog

    Prog

    Example: Programming reset

    Go to reset in the ex-panded programmingusing key 3.

    Confirm with key 1.The password indi-cation appears.Enter password.Select the digit to bechanged using key 2.The selected digit isflashingChange the selecteddigit by pressing key 3.

    If all ciphers are programmed correctly, all ciphers dis-appear in the indication, and the manufacturer's pro-gramming is loaded. DynamiC keeps working in auto-matic mode.

    With the function "Re-set programming" theprogramming carriedout are deleted andoverwritten by themanufacturer's programming. The programming is nowin the same condition as delivered.To avoid unintentional deleting, the four digit reset pass-word must be entered additionally. The reset passwordcan be requested in the manufacturing work.

    Prog

  • Page 42 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Prog

    Voltage between

    Current in L1-L2 L2-L1 L2-L3 L3-L2 L3-L1 L1-L3

    L1 k-l 240° 60° 0° 180° 120° 300°l-k 60° 240° 180° 0° 300° 120°

    L2 k-l 120° 300° 240° 60° 0° 180°l-k 300° 120° 60° 240° 180° 0°

    L3 k-l 0° 180° 120° 300° 240° 60°l-k 180° 0° 300° 120° 60° 240°

    Table 2: Correction angle, measurement L-L

    Example : Programming of the correction angleThe current transformer is installed in L2. "k-l" is notexchanged. The voltage measurement is done accord-ing to connection diagram between L2-L3.

    In that case you can read the angle of 240° in the table"correction angle".

    Voltage between

    Current in L1-L2 L2-L1 L2-L3 L3-L2 L3-L1 L1-L3

    L1 k-l 240° 60° 0° 180° 120° 300°l-k 60° 240° 180° 0° 300° 120°

    L2 k-l 120° 300° 240° 60° 0° 180°l-k 300° 120° 60° 240° 180° 0°

    L3 k-l 0° 180° 120° 300° 240° 60°l-k 180° 0° 300° 120° 60° 240°

    Table: Correction angle

    Confirm selection withkey 1. One digit isflashing.Change the selecteddigit using key 2. Theselected digit is flashing. Change the selected digit us-ing key 3.Leave programming mode with key 1. No digit is flash-ing anymore.With key 3 you continue moving through the expandedprogramming.

    Prog

    Voltage between

    Current in L3-N N-L3 L1-N N-L1 L2-N N-L2

    L1 k-l 240° 60° 0° 180° 120° 300°l-k 60° 240° 180° 0° 300° 120°

    L2 k-l 120° 300° 240° 60° 0° 180°l-k 300° 120° 60° 240° 180° 0°

    L3 k-l 0° 180° 120° 300° 240° 60°l-k 180° 0° 300° 120° 60° 240°

    Table 1: Correction angle, measurement L-N

    Connection configurationDynamiC can be de-livered in twoconnection varieties forthe measurement andsupply voltage.In the version measurement L-L, the measurement andsupply voltage must be taken from two outer conduc-tors. In version measurement L-N, the measurementand supply voltage must be taken between outer con-ductor L and neutral N.

    Correction angleThe controller DynamiC indicates the power factor,real and reactive power correctly, if current and voltagewere connected according to the type plate andconnection diagram. The phase shift between voltageand current must not be corrected, and the correctionangle is 0°.The correction angle can be selected in the range of 0°- 359° in one degree steps.

    If the user cannot connect DynamiC according to theconnection diagram, this can be corrected according tothe correction values of table 1 or 2.Devices for version L-N can be corrected with the cor-rection angles of table 1.Devices for version L-L can be corrected with the cor-rection angles of table 2.

    If the connection fault is not known, the correction an-gle can be determined automatically by using the “learn”function.

  • Page 43= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Software releaseThe software forDynamiC is improvedand ex-panded con-tinuously. The softwarerelease of the device isgiven by a number, the software release. The softwarerelease cannot be changed by the user.

    Serial numberEach device has its own unchangeable 8 digit serialnumber. The serial number is laid down in two pic-tures.

    Prog

    Serial number, part 2

    Prog

    If you are in the in-dication of the softwarerelease, please call thefirst and second part ofthe serial number bypressing key 2.

    Serial number, part 1

    Prog

  • Page 44 = Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Serial interface (Option)Device addressIf several devices areconnected via RS485,a master (PC/PLC) cantell the difference be-tween them by their de-vice addresses. Within one network, each DynamiC musthave its own device address.If Profibus protocol has been chosen, the address can begiven between 0 and 126. If Modbus protocol has beenchosen, the address can be given between 0 and 255.

    The device address can be requested and changed inmenu "advanced programming".

    Example: Change device address.With key 3 you canmove to device addressin expanded program-ming.Confirm selection withkey 1.In this example the device address is indicated as 1.Select the number to be changed by using key 2.The selected digit is flashing.Change digit with key 3.Confirming key 1 for about 2 seconds, the changes aresaved and DynamiC keeps working in automaticmode.

    Transmission protocolFor the connection ofDynamiC t o anex i s t ing f i e ld bussystem are two trans-mi s s ion p ro toco l savailable:

    0 - Modbus RTU (Slave) and1 - Profibus DP V0 (Slave) .

    With Modbus protocol you have access to the data fromtable 1 and with Profibus protocol you have access to thedata of table 2.

    Example: Select transmission protocol.Please move to deviceaddress in expandedprogramming using key3. Now press key 2 fortransmission protocol.Confirm selection with key 1.In this example the transmission protocol is protocol1=Profibus DP. Digit 1 is flashing.Please change over between protocol 1 and 2 by pressingkey 3.Confirming key 1 for about 2 seconds, the changes aresaved and DynamiC keeps working in automaticmode.

    Attention!If a switching frequency of 50Hz is programmedfor the transistor outputs, the serial interface doesnot work!

  • Page 45= Key 1 = Key 2 = Key 3

    Reactive Power Controller

    Modbus RTUTransmission mode

    RTU-Mode with CRC-Check

    Transmission parametersBaud rate : 9.6, 19.2, 38.4, 57.6, 115.2kbpsData bits : 8Parity : noneStop bits : 2

    Realised functionsRead Holding Register, Function 03Preset Single Register, Function 06Preset Multiple Register, Function 16

    Data formatschar : 1 Byte (0 .. 255)word : 2 Byte (-32768 .. +32767)long : 4 Byte (-2 147 483 648 .. +2 147 483 647)

    The sequence of bytes is highbyte before lowbyte.

    Profibus DP V0The DynamiC is a slave device and corresponds to thefieldbus directive PROFIBUS DP V0, DIN E 19245 part3. The PROFIBUS user organization has listed DynamiCwith the following entries:

    Device description : DynamiCIdent-Number : 04B9 HEXGSD : PROF04B9.GSD

    The GSD file is specific for the device. Here the trans-mission parameters and the kind of measured data aredetermined. The GSD file for DynamiC with option"Interface" belongs to the contents of delivery.While creating the program for the PLC (master), theGSD file is implemented into PLC prog