Bus 2 DFW
3
description
250 km. Bus 2 DFW. 500 km. Bus 6 COAL. 300 km. Bus 7 WIND. 400 km. Bus 3 UT. Bus 1 HOU. 150 km. 300 km. Bus 4 SA. No Wind (Good Wind). 400 km. Summer Peak, 3 kW per person, 20 million people, 60 GW Winter Peak, 80% of Summer Peak Spring/Fall Peak, 50% of Summer Peak - PowerPoint PPT Presentation
Transcript of Bus 2 DFW
Bus 2DFW
Bus 5VAL
300 km
250 km
150 km
300 km
400 km
500 km
400 km
Bus 3UT
Bus 1HOU
Bus 7WIND
Bus 4SA
• Summer Peak, 3 kW per person, 20 million people, 60 GW
• Winter Peak, 80% of Summer Peak• Spring/Fall Peak, 50% of Summer Peak
• Nightime, 50% of Daily Peak• Approx 5% losses
No Wind(Good Wind)
Bus 6COAL
BUSLOAD % OF
TOTAL
GEN% OF
TOTAL
1, HOU 30% 45%
2, DFW 25% 15% ( 10%)
3, UT 5% 5%
4, SA 20% 10%
5, VAL 10% 5%
6, COAL 5% 15% ( 5%)
7, WIND 5% 5% ( 20%)Positive-sequence line constants for each 345kV circuit:• R = 0.06 Ω/km per conductor
• L = 1 µH/m• C = 12 pF/m • Rating = 800 A per conductor