BM100/4 and BM101/4 Analogue Insulation and Continuity Testers · Analogue Insulation and...

3
BM100/4 and BM101/4 Analogue Insulation and Continuity Testers DESCRIPTION The Megger ® ‚ BM100/4 and BM101/4 Insulation and Continuity Testers provide an insulation test voltage of 500 V d.c. The instruments have two continuity measuring ranges: 0 to 2 and 0 to 200 . The BM100/4 has an automatic voltage indicating facility that warns, before a test is executed, if the instrument has been inadvertently connected to an energised supply. This warning is given by a reading on a 0 to 600 V a.c. scale on the meter; this scale also monitors the discharging voltage following tests on a capacitive circuit. The BM101/4 does not have the voltage indicating facility, but instead has an additional resistance range of 0 to 1 M. A single rotary switch selects each range, and has a position for checking the condition of the internal 9 V replaceable battery. A push-button is pressed to execute a test, and upon release, the automatic discharge circuit is connected across the instrument’s terminals and therefore across the item under test. Test leads must only be removed when the capacitive circuits have discharged. Readings are shown on an analogue meter; this has a fast response. It has a white-on-black scale and an orange “dayglow” pointer for clear, easy reading in any lighting conditions. The tough ABS plastic case incorporates shrouded safety terminal sockets and test leads with right- angled connectors to prevent them being accidentally pulled out of the instrument. There is a shatter-proof polycarbonate window for protection of the meter. A fold away support stand allows the user to stand the instrument up rather than holding it in the hand. All instruments are tough and robust, well able to withstand the treatment they are likely to receive in everyday use or while being carried in an electrician’s toolbag. APPLICATIONS The BM100/4 and BM101/4 are intended for insulation and continuity testing during installation, servicing or maintenance work. In particular, they are suited to domestic and industrial wiring systems being tested to the IEE wiring regulations. They may be used for testing other items of electrical equipment (e.g., transformers, motors, generators, etc.). The instruments have been designed to conform to the IEC 1010-1 safety specification, and to performance standard VDE 0413 Part 1. Optional test leads with fused prods are available for the BM100/4. It is essential (to comply with HSE Guidance Note GS 38) that these be used when checking (by performing a voltage test) that equipment has been isolated from the supply, especially in high energy situations. Also available as optional accessories are 4 mm right- angled adaptors (black and red) enabling use of leads with straight connectors. A third optional accessory is a synthetic test and carry case. Suitable for testing to the IEE Wiring Regulations Complies with the requirements of BS 7671, HD 384 and IEC 364 Combined insulation and continuity testing Insulation testing at 500 V d.c. to the VDE 0413 Part 1 BM100/3 and BM101/4 Analogue Insulation and Continuity Testers

Transcript of BM100/4 and BM101/4 Analogue Insulation and Continuity Testers · Analogue Insulation and...

Page 1: BM100/4 and BM101/4 Analogue Insulation and Continuity Testers · Analogue Insulation and Continuity Testers DESCRIPTION The Megger®‚ BM100/4 and BM101/4 Insulation and ... Insulation

BM100/4 and BM101/4 Analogue Insulation and ContinuityTesters

DESCRIPTION

The Megger®‚ BM100/4 and BM101/4 Insulation andContinuity Testers provide an insulation test voltage of500 V d.c.

The instruments have two continuity measuring ranges: 0 to 2 Ω and 0 to 200 Ω. The BM100/4 has an automaticvoltage indicating facility that warns, before a test isexecuted, if the instrument has been inadvertentlyconnected to an energised supply. This warning is givenby a reading on a 0 to 600 V a.c. scale on the meter; thisscale also monitors the discharging voltage following testson a capacitive circuit. The BM101/4 does not have thevoltage indicating facility, but instead has an additionalresistance range of 0 to 1 MΩ.

A single rotary switch selects each range, and has aposition for checking the condition of the internal 9 Vreplaceable battery. A push-button is pressed to execute atest, and upon release, the automatic discharge circuit isconnected across the instrument’s terminals and thereforeacross the item under test. Test leads must only beremoved when the capacitive circuits have discharged.

Readings are shown on an analogue meter; this has a fastresponse. It has a white-on-black scale and an orange “dayglow” pointer for clear, easy reading in any lightingconditions. The tough ABS plastic case incorporatesshrouded safety terminal sockets and test leads with right-angled connectors to prevent them being accidentallypulled out of the instrument. There is a shatter-proofpolycarbonate window for protection of the meter. A fold

away support stand allows the user to stand theinstrument up rather than holding it in the hand.

All instruments are tough and robust, well able towithstand the treatment they are likely to receive ineveryday use or while being carried in an electrician’stoolbag.

APPLICATIONS

The BM100/4 and BM101/4 are intended for insulation andcontinuity testing during installation, servicing ormaintenance work. In particular, they are suited todomestic and industrial wiring systems being tested to theIEE wiring regulations. They may be used for testing otheritems of electrical equipment (e.g., transformers, motors,generators, etc.).

The instruments have been designed to conform to theIEC 1010-1 safety specification, and to performancestandard VDE 0413 Part 1.

Optional test leads with fused prods are available for theBM100/4. It is essential (to comply with HSE GuidanceNote GS 38) that these be used when checking (byperforming a voltage test) that equipment has beenisolated from the supply, especially in high energysituations.

Also available as optional accessories are 4 mm right-angled adaptors (black and red) enabling use of leads withstraight connectors. A third optional accessory is asynthetic test and carry case.

Suitable for testing to the IEE WiringRegulations

Complies with the requirements of BS 7671, HD 384 and IEC 364

Combined insulation and continuitytesting

Insulation testing at 500 V d.c. to theVDE 0413 Part 1

BM100/3 and BM101/4Analogue Insulation and Continuity Testers

Page 2: BM100/4 and BM101/4 Analogue Insulation and Continuity Testers · Analogue Insulation and Continuity Testers DESCRIPTION The Megger®‚ BM100/4 and BM101/4 Insulation and ... Insulation

FEATURES AND BENEFITS

Suitable for testing to the IEE wiring regulations

Complies with BS 7671, HD 384 and IEC 364

Combined insulation and continuity testing

Insulation testing at 500 V d.c. to the VDE 0413 Part 1

specification

Designed under the IEC 1010-1 safety specification

Shrouded safety terminals with right-angled test lead

connectors

Automatic discharge of capacitive circuits after test

Lightweight, tough and robust

SPECIFICATION

BM100/4 BM101/4Insulation Test Voltage Ranges

500 V d.c. 500 V d.c.

Insulation Resistance Range

0 to 200 MΩ 0 to 200 MΩ

Resistance Range

— 0 to 1 MΩ

Continuity Ranges

(i) 0 to 200 Ω 0 to 200 Ω

(ii) 0 to 2 Ω 0 to 2 Ω

Voltage Range

0 to 600 V a.c. —

Terminal Voltage D.C.(nominal on open circuit)

Insulation Resistance Range

<600 V <600 V

(>500V at 0,5 MΩ) (>500V at 0,5 MΩ)

Resistance Range

— 53 V

Continuity Ranges

(i) 0,76 V 0,76 V

(ii) 4,7 V 4,7 V

Terminal Current(nominal on short circuit)

Insulation Resistance Range

1,6 mA 1,6 mA

Resistance Range

— 325 µA

Continuity Ranges

(i) 12,3 mA 12,3 mA

(ii) 210 mA 210 mA

Typical scale (not full size) BM100/4 (BM101/4 similar)

GENERAL

Accuracy (at 20° C)

±2,5% of scale length on all ranges [i.e., ±1,9 mm (0,075 in.) oninsulation resistance range]

Class 1,5 (as VDE 0413 Part 1) for insulation resistance rangemarked by a white band, Class 3 for other ranges

Movement

250 µA full scale deflection

Discharge

Automatic discharge of capacitive circuits via an internal resistor(<500 kΩ) when TEST pushbutton is released following aninsulation test

Voltmeter Input Impedance

BM100/4 only: 330 kΩ

Temperature RangeOperation: –5 to +40°C

Temperature Coefficient

±0,1% per °C

HumidityOperation: 90% RH max. at 20°C

80% RH max. at 35°C

Storage: 95% RH max. at 35°C

Typical terminal voltage characteristic

Fuses500 mA, 250 V ceramic HBC type F,20 x 5 mm, IEC 127/1

2 ampere, 500 V ceramic HBC type F, 32 x 6 mm, 50 kA breakingcapacity

Power SupplySingle 9 volt battery, IEC 6 LR61 type

Current Consumption:

110 mA max. on insulation range, 40 mA max. on resistance range, 220 mA max. on 2 Ω range

BM100/3 and BM101/4Analogue Insulation and Continuity Testers

Page 3: BM100/4 and BM101/4 Analogue Insulation and Continuity Testers · Analogue Insulation and Continuity Testers DESCRIPTION The Megger®‚ BM100/4 and BM101/4 Insulation and ... Insulation

ORDERING INFORMATIONItem (Qty) Order No.

Insulation and Continuity Tester BM100/4

Insulation and Continuity Tester BM101/4

Included Accessories

Zip-up carry case 6420-075

Test leads including prods and clips (1 set) 6220-434

Operating instruction book 6172-048

Note: When measuring or detecting voltage, the advice

given in Health and Safety Executive Guidance Note GS 38

must be followed, particularly in regard to the use of test

leads with fused prods.

Optional Accessories

Synthetic test and carry case 6420-030

Test lead sets

2 leads, 2 clips, 2 probes 6220-434

Test leads with fused prods, FPK4 —

unsuitable for continuity measurements: comply

with Health and Safety Executive Guidance Note

GS 38 (1 set) 6111-287

UK Archcliffe Road, DoverCT17 9EN England T (0) 1 304 502101 F (0) 1 304 207342

UNITED STATES 4271 Bronze Way, Dallas, TX75237-1017 USAT 1 800 723 2861 T 1 214 330 3203 F 1 214 337 3038

OTHER TECHNICAL SALES OFFICESValley Forge USA, TorontoCANADA, Mumbai INDIA, Le Raincy FRANCE, CherrybrookAUSTRALIA, Guadalajara SPAINand The Kingdom of BAHRAIN.

ISO STATEMENT

Registered to ISO 9001:1994 Reg no. Q 09250

Registered to ISO 14001 Reg no. EMS 61597

BM100/4_BM101/4_DS_en_V03www.megger.comMegger is a re g i s t e red trademark

BM100/3 and BM101/4Analogue Insulation and Continuity Testers

Battery LifeMore than 1800 5 second operations on 2 Ω range

SafetyThe instruments will, in general, meet the requirements of the IEC1010-1 (1990) safety specification. Safety Class II

Flash test to 4 kV peak impulse

The instruments have been designed for use on high energysystems with phase-to-earth voltages not exceeding 300 V a.c. andwith phase-to-phase voltages not exceeding 500 V a.c.

Dimensions175 H x 95 W x 57 D mm

(6,9 H x 3,75 W x 2,25 D in. approx)

Weight485 g (1 lb approx)