Post on 17-Jun-2020
Status: 30.11.2015
Values in mg/Nm³, Daily Average, 6% O2. * CO figures are indicative yearly average emission levels; hpy: operating hours per year
Fuel Type of
value
Legal
Instrument MW Type NOX SO2
CO*
(existing
≥1500 hpy)
HCl HF Dust Hg (μg/Nm³)
Biomass ELV MCP 1-5 New 500 200 50
Biomass ELV MCP 5-20 New 300 200 30
Biomass ELV MCP 20-50 New 300 200 20
Biomass ELV IED 50-100 New 250 200 20
Biomass ELV IED 100-300 New 200 200 20
Biomass ELV IED ≥300 New 150 150 20
Biomass ELV MCP 1-5 Existing 650 200 50
Biomass ELV MCP 5-20 Existing 650 200 50
Biomass ELV MCP 20-50 Existing 650 200 30
Biomass ELV IED 50-100 Existing 300 200 30
Biomass ELV IED 100-300 Existing 250 200 20
Biomass ELV IED ≥300 Existing 200 200 20
Biomass BATAEL BREF 50-100 New 120-200 30-175 <30-250 1-12 <1 2-10 <1-5
Biomass BATAEL BREF 100-300 New 100-200 <20-85 <30-160 1-12 <1 2-10 <1-5
Biomass BATAEL BREF ≥300 New 65-150 <20-70 <30-80 1-12 <1 2-10 <1-5
Biomass BATAEL BREF 50-100 Existing 120-275 30-215 <30-250
(≥500 hpy) 1-35 <1.5 2-22 <1-5
Biomass BATAEL BREF 100-300 Existing 100-220 <20-175 <30-160 1-12 <1 2-18 <1-5
Biomass BATAEL BREF ≥300 Existing 95-165 <20-85 <30-80 1-12 <1 2-16 <1-5
Coal ELV MCP 1-5 New 500 400 50
Coal ELV MCP 5-20 New 300 400 30
Coal ELV MCP 20-50 New 300 400 20
Coal ELV IED 50-100 New 300
(400 PL) 400 20
Coal ELV IED 100-300 New 200 200 20
Coal ELV IED ≥300 New 150
(200 PL)
150
(200 FB) 10
Coal ELV MCP 1-5 Existing 650 1100 50
Coal ELV MCP 5-20 Existing 650 1100 50
Coal ELV MCP 20-50 Existing 650 400 30
Coal ELV IED 50-100 Existing 300
(450 PL) 400 30
Coal ELV IED 100-300 Existing 200 250 25
Coal ELV IED ≥300 Existing 200 200 20
Coal BATAEL BREF 50-100 New 155-200 170-220 <30-140 1-6 <1-3 4-16 Coal: <1-3;
Lignite: <1-5
Coal BATAEL BREF 100-300 New 80-130 135-200 <30-140 1-3 <1-2 3-15 Coal: <1-3;
Lignite: <1-5
Coal BATAEL BREF ≥300 FBC New 80-125 25-110 <30-100 1-3 <1-2 3-10 Coal: <1-2;
Lignite: <1-4
Coal BATAEL BREF ≥300 PC New 80-125 25-110 <5-100 1-3 <1-2 3-10 Coal: <1-2;
Lignite: <1-4
Coal BATAEL BREF 50-100 Existing 165-330 170-400 <30-140 2-10 <1-6 4-22 Coal: <1-9;
Lignite: <1-10
Coal BATAEL BREF 100-300 Existing 155-210 135-220 <30-140 1-5 <1-3 4-22 Coal: <1-9;
Lignite: <1-10
Coal BATAEL BREF ≥300 FBC Existing 140-165 50-220 <30-100 1-5 <1-3 3-11 Coal: <1-4;
Lignite: <1-7
Coal BATAEL BREF ≥300 PC Existing <85-165 25-165 <5-100 1-5 <1-3 3-11 Coal: <1-4;
Lignite: <1-7
2
As of 30.11.2015. Notes for the values on this sheet:
These are the general legally-binding values. Many exceptions exist and are not listed here. Refer to the
Reference pages below. Bear in mind that local permitting authorities may always ask stricter emission
levels than those described here.
New and Existing:
MCP
Article 3 (6):
“‘existing combustion plant’ means a combustion plant put into operation before 20 December 2018 or for
which a permit was granted before 19 December 2017 pursuant to national legislation provided that the
plant is put into operation no later than 20 December 2018;”. All subsequent plants are considered “new”.
IED
Article 30.2 defines “existing” plants. “All permits for installations containing combustion plants which
have been granted a permit before 7 January 2013, or the operators of which have submitted a complete
application for a permit before that date, provided that such plants are put into operation no later than 7
January 2014, shall include conditions ensuring that emissions into air from these plants do not exceed the
emission limit values set out in Part 1 of Annex V.” All subsequent plants are considered “new”.
LCP BREF
Definition of a new LCP is “A combustion plant first permitted at the installation following the publication
of these BAT conclusions or a complete replacement of a combustion plant on the existing foundations
following the publication of these BAT conclusions” The BAT Conclusions being still unpublished, the “new”
date is still unknown (although expected to be early 2017). All other plants are considered existing, but
many exemptions exist to the values in the EPPSA table.
BATAEL notes:
FBC: FBC boiler combusting coal and/or lignite and lignite-fired pulverised coal boiler
PC: coal-fired PC boiler
FB: in case of circulating or pressurised fluidised bed combustion
PL: Pulverised Lignite Combustion
3
References
Contents References LCP BREF .................................................................................................................... 4
Coal ......................................................................................................................................... 4
Biomass ................................................................................................................................... 7
References IED .......................................................................................................................... 10
References MCPD ...................................................................................................................... 14
4
References LCP BREF
Coal
5
6
7
Biomass
8
9
10
References IED
11
12
13
14
References MCPD
15
16
Note:
The Benchmark values were proposed by the European Commission in its 2013 initial proposal.
They were removed by the Codecision procedure (Parliament and Council). These figures have no
legally-binding value, but they were officially published by the European Commission, and as
such may be evoked in regions with high pollution.