Mechanical ventilation with heat recovery

technical trainingmartedì 17 gennaio 2012

Page 2: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Mecchanical ventilation heat recovery

2

Ventilation

Ventilation is the process of replacing waste air in any indoor space to provide high air quality for occupants comfort and

wellbeing.

martedì 17 gennaio 2012

Page 3: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Mecchanical ventilation heat recovery

3

BenefitsAir quality

- bacteria and fungi

Reduction of air pollution due to high concentration of:

- chemical substances (radon, smoke, carbone monoxide and dioxide, volatile organic compounds)

- humidity and smelles

Low energy consumption

- ventilation heat losses reductione- wellbeing of walls and structures protected from indoor humidity

The correct ventilations rate ensure:

Indoor comfortControllo delle condizioni microclimatiche rispetto a:

- air temperature

- air humidity

- air movements and speed

martedì 17 gennaio 2012

Page 4: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A 4

Natural ventilation

The ventilation flow rates are not constant but depending on external conditions

In natural ventilation external air flows to an indoor space as a result of pressure difference due to- wind- temperature differences

Mecchanical ventilation heat recovery

martedì 17 gennaio 2012

Page 5: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A 5

Natural ventilation

- NATURAL VENTILATION is based only on userʼs sansations about indoor air quality. External air flows throught windows and doors opened by the users.

- NATURAL CONTROLLED VENTILATION is based on userʼs or mechanical operations according to fixed and controlled criteria

Mecchanical ventilation heat recovery

martedì 17 gennaio 2012

Page 6: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A 6

Natural ventilation

Advantages: - no fan and no energy consumption- little investment

Mecchanical ventilation heat recovery

Drawbacks: - bad control of air change- noises coming from the openings- people feeling cold flows near the openings

martedì 17 gennaio 2012

Page 7: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Mechanical ventilation heat recovery

7

Mechanical ventilation

In this case, the new air is introduced naturally in the spaces thanks to adjustable air-vents situated on the outside walls.

On the other hand, foul air is extracted mechanically (fans). With this extraction, the spaces are on depression and this favours the infiltration of new air.

Simple flow ventilation

martedì 17 gennaio 2012

Page 8: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Mechanical ventilation heat recovery

8

Mechanical ventilation

Simple flow ventilation

Advantages: - symple system and easy to use- extracted air debits are controlled- no ventilation network is nedeed

Drawbacks: - air-vents are source of noises- risk of cold air flow due to air-vents badly set- no heat recovery

martedì 17 gennaio 2012

Page 9: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Mechanical ventilation heat recovery

9

Mechanical ventilation

Double flow ventilation

New air filtered and preheated in winter is mechanically distribuited by a ductwork.

Air is mechanically extracted by another ductwork

The heart of the system is a heat exchanger witch ensures the

thermal energy recovery from extracted air.

martedì 17 gennaio 2012

Page 10: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Mechanical ventilation heat recovery

10

Mechanical ventilation

Double flow ventilationSimple flow ventilation

Advantages: - debits air controlled everyehere- air filtered and treated before distribution- heat recovey from polluted air flow

Drawbacks: - more expensive system- ductworks integrated in the structure- important and frequent maintenance

martedì 17 gennaio 2012

Page 11: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Mechanical ventilation heat recovery

11

The heart of the system: the air to air heat exchanger

The counter flow energy recovery heat exchanger recovers waste heat from

extracted air

Heat recovery

In the countercurrent exchanger two air rates flow in opposite directions to each other: the maximum amount of heat that can

be obtained is higher than with other exchangers.

martedì 17 gennaio 2012

Page 12: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Mechanical ventilation heat recovery

12

Heat recovery

The heart of the system: the air to air heat exchanger

external air

polluted internal air

internal air

preheated air

martedì 17 gennaio 2012

Page 13: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Mechanical ventilation heat recovery

13

ALTAIR HEAT EXCHANGERS

-polypropylene counterflow heat exchanger

-high heat recovery efficiency (up to 95%)

-automatic exchanger defrost function

-automatic by-pass

- easy maintenance operations thanks to the removable panel

martedì 17 gennaio 2012

Page 14: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Mechanical ventilation heat recovery

14

Double flow ventilation with heat recovery

The exchanger recovers heat from extracted air to

warm incoming airAir is extracted from polluted spaces

such as bathrooms and kitchens

Air is distributed in the other spaces

such as bedrooms and livin rooms

martedì 17 gennaio 2012

Page 15: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Individual ventilation units

15

Model Air flowm3/h Microprocessor* Power supply

VFans power

W

Sensible heat recovery efficiency

%Weight

Kg

CP 150 150 CTR 230 43 >92 38

CPX 150 150 CTRX 23043

>92 38

Data referred to the following conditions: Dbt external air -5°C; external R.H. 80%; Dbt environment 20°C; environment R.H. 50%; 50% nominal airflow

Mechanical ventilation units with high efficiency heat recovery.

ALTAIR CP

martedì 17 gennaio 2012

Page 16: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A 16

Mechanical ventilation units with high efficiency heat recovery.

ALTAIR CP

-150m3/h nominal airflow

-compact size and reduced height

-vertical installation on wall or horizontal on ceiling

-low consumption radial fans with electronic motors

-G4 filters for exhaust air

-F7 low pressure drop filters for fresh air

-plug-n-play connection with electrical panel

-standard microprocessor control CTR*

-advanced microprocessor control CTRX*

Individual ventilation units

martedì 17 gennaio 2012

Page 17: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A 17

Mechanical ventilation units with high efficiency heat recovery.

ALTAIR HR - VR

Model Air flowm3/h

Microprocessor* Power supplyV

Fans powerW

Sensible heat recovery efficiency

%

WeightKg

HR 300 350 CTR 230 71 x 2 >93 52

VR 300 350 CTR 230 71 x 2 >93 48

HR 500 500 CTR 230 200 x 2 >91 52

VR 500 500 CTR 230 200 x 2 >91 48

HRX 300 350 CTRX 230 71 x 2 >93 52

VRX 300 350 CTRX 230 71 x 2 >93 48

HRX 500 500 CTRX 230 200 x 2 >91 52

VRX 500 500 CTRX 230 200 x 2 >91 48

Data referred to the following conditions: Dbt external air -5°C; external R.H. 80%; Dbt environment 20°C; environment R.H. 50%; 50% nominal airflow

Individual ventilation units

martedì 17 gennaio 2012

Page 18: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A 18

Mechanical ventilation units with high efficiency heat recovery.

ALTAIR VR

-two models available: 350m3/h and 500m3/h nominal airflow

-VR version for vertical installation on wall or floor

-HR version for horizontal installation on floor or ceiling

-low consumption radial fans with electronic motors

-G4 filters for exhaust air

-F7 low pressure drop filters for fresh air

-plug-n-play connection with electrical panel

-standard microprocessor control CTR*

-advanced microprocessor control CTRX*

ALTAIR HR

Individual ventilation units

martedì 17 gennaio 2012

Page 19: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A 19

Individual ventilation units

ALTAIR SP

Model Air flowm3/h

Microprocessor* Power supplyV

Fans powerW

Sensible heat recovery efficiency

%

WeightKg

SP 300 350 CTR 230 71 x 2 >92 45

SPX 300 350 CTRX 230 71 x 2 >92 45

SP 500 500 CTR 230 200 x 2 >90 46

SPX 500 500 CTRX 230 200 x 2 >90 46

Data referred to the following conditions: Dbt external air -5°C; external R.H. 80%; Dbt environment 20°C; environment R.H. 50%; 50% nominal airflow

Mechanical ventilation units with high efficiency heat recovery.

Separable ventilating unit and heat recovery module.

martedì 17 gennaio 2012

Page 20: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A 20

Individual ventilation units

ALTAIR SP

Mechanical ventilation units with high efficiency heat recovery.

Separable ventilating unit and heat recovery module.

- two models available: 350m3/h and 500m3/h nominal airflow

- separable ventilating module and heat recovery unit

- casing made of high density PPE and steel

- horizontal installation on floor or ceiling

- low consumption radial fans with electronic motors

- G4 filters for exhaust air

- F7 low pressure drop filters for fresh air

- plug-n-play connection with electrical panel

- standard microprocessor control CTR*

- advanced microprocessor control CTRX*

- inspectionable exchanger and filters

martedì 17 gennaio 2012

Page 21: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Collective Ventilation Units

21

Mechanical Ventilation System for collective dwellings

Renewal of the air in single flats is ensured by a couple of centralised fans located on the roof or on a terrace of the building.

Heat recovery is made by recovery u n i t s l o c a t e d i n t h e s i n g l e apartments.

martedì 17 gennaio 2012

Page 22: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Collective Ventilation Units

22

HELIX

Air ventilating units to be interfaced with heat recovery modules:

- nominal airflow from 2000m3/h to 5600m3/h

- high values of static pressure available to the ducting

- inverter controlled centrifugal blowers

-constant pressure

-double panels casing with rockwall insulation

-differential and average pressure sensors

Mechanical Ventilation System for collective dwellings

martedì 17 gennaio 2012

Page 23: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Collective Ventilation Units

23

ALTAIR XC

- two models available: 100m3/h and 200m3/h nominal airflow

- horizontal installation with beneath access for inspection

-polypropylene counterflow heat exchanger

-high heat recovery efficiency (up to 95%)

-G4 filter for exhaust air

-F7 low pressure drop filters for fresh air

High efficiency heat recovery modules

Mechanical Ventilation System for collective dwellings

martedì 17 gennaio 2012

Page 24: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Collective Ventilation Units

24

ALTAIR SP

High efficiency heat recovery modules

-two models available: 350m3/h and 500m3/h nominal airflow

-to be interfaced with HELIX external ventilating unit

-horizontal installation on floor or ceiling

-polypropylene counterflow heat exchanger

-high heat recovery efficiency (up to 95%)

-G4 filter for exhaust air

-F7 low pressure drop filters for fresh air

Mechanical Ventilation System for collective dwellings

martedì 17 gennaio 2012

Page 25: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Electronic microprocessors

25

Standard microprocessor CTR

List of the available functions CTR

Manual selection of the fans speed: OFF + 3 speed levels √

Automatic by-pass management √

Prevention from heat exchanger freezing: speed reduction/stop of the intake fan; max level of the exhaust air fan speed

Simplified visualization of the unit operation mode and of incidental alarms (LED) √

Filters status monitoring by mean of the running time of the unit or by controlling the pressure drop across the filters

Fans status monitoring through tachimetric signal (if available on the fan) or by controlling the pressure difference between the inside and outside of the supply and exhaust air ducts

martedì 17 gennaio 2012

Page 26: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Electronic microprocessors

26

Advanced microprocessor CTRX - main features

Tabella rapida delle funzioni disponibili List of the available functions

CTRX

Manual selection of the fans speed: OFF regulation of the fan speed in a range [MIN-MAX]√

Unbalanced airflow between inlet airflow and exhaust airflow√

Automatic control of the fans speed: CO2 e CO2/VOC, HR sensors with programmable range of PPM or HR (by the user); 3 speed levels or continous speed

Remote control of the fans speed by 0-10VDC signal√

Booster (fans at maximum speed) for a period of time settable by the user√

Booster from a remote contact NC for a fixed range of time. (time range settable by the software)√

Booster from a remote proximity switch NC: PIR strategy √

Unit switch ON/OFF from a remote contact√

Weekly cronoprogrammming√

Prevention from heat exchanger freezing: proportional electric pre-heater√

Prevention from heat exchanger freezing by closing a free voltage switch to allow the user to start a customized strategy√

Managing of electrical post-heating in a proportional way in order to reach the set point value for the average internal temperature Tr and to mantain the intake air temperature Ti in a fixed range (comfort range)

Managing of a water post-heating in a proportional way in order to reach the set point value for the average internal temperature Tr and to mantain the intake air temperature Ti in a fixed range (comfort range) √

Managing of a water post-cooling in a proportional way in order to reach the set point value for the average internal temperature Tr and to mantain the intake air temperature Ti in a fixed range (comfort range)

Simplified visualization of the unit operation mode and of incidental alarms (sinoptic and detailed)√

Remote selection of the unit running mode: closed contact=unit is ON; open contact=unit is OFF or unpowered√

Possible managing of more than 1 similar units (up to 4) with a single control panel (master & slave)√

Possibility to change the language of the remote control panel (Italian, English, French, German, Spanish)√

martedì 17 gennaio 2012

Page 27: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Air distribution system

27

Components and pieces od the distribution ductworks

Insulated plenums for inlet/outlet air

Insulated silencer

Regulation rings for reduction

martedì 17 gennaio 2012

Page 28: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Air distribution system

28

components and pieces od the distribution ductworks

Connections for valves

Half hard duct for air inlet

Half hard duct for air outlet

martedì 17 gennaio 2012

Page 29: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Air distribution system

29

components and pieces od the distribution ductworks

Valves for installation on wall/ceiling

Ventilation grids for inlet/outlet air

martedì 17 gennaio 2012

Page 30: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Air distribution system

30

Ventilation flow rates

Ventilation debits are calculated in accordance with:

- European and national standards about energy efficiency

- European and national standards about indoor air quality

- local hygienic reccomendations

Indoor air quality is ensured by the frequency of turnover of interior air by replacement with outside air.

The number of changes per hour depends on the type of spaces (residential building, office, school ecc.)

For residential applications the frequency is about 0,5-0,7 changes per hour.

martedì 17 gennaio 2012

Page 31: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Reference projects

31

Individual ventilation for apartments in a condominium

ALTAIR CP - Milano

martedì 17 gennaio 2012

Page 32: Μηχανικός εξαερισμός με ανάκτηση θερμότητας

Technical training - part A

Reference projects

32

Thanks for attention

martedì 17 gennaio 2012