Page 1: REG-D PAN D

a-eberleT013D202A00 Issue 08/2006

(REG-D, PAN-D)

Voltage Control System

* in wall-mounting housing* in panel-mounting housing* as plug-in module

Characteristics of the voltageregulation system• Large backlit LCD (128 x 128) with all Important information (tap-change position, voltage, etc.)• Measuring functions (U, I, P, Q, S, cos ϕ, ϕ, I sin ϕ, f )• Recorder functions (multichannel line recorder)• Statistics functions (total number of switching operations, switching operations per tap)• Event recorder (log book)• Transformer-monitoring functions for recording of the hot-spot temperature and lifetime consumption• 14 (16) freely programmable binary inputs• 7 freely programmable binary outputs• Freely programmable analogue inputs or outputs (mA)• PT 100 direct input• Input for tap-change potentiometer (200 Ω ... 20 kΩ total resistance)• Control of triple-wound transformers• Control of phase-shifting transformers

REGSys™

ApplicationBoth simple and demanding measurement, control and regu-lation tasks can be carried out using the new RegSys™ volt-age-control system.The REG-D™ voltage regulator (basic device), PAN-D and PAN-A1/A2 voltage monitoring units as well as interface mo-dules with binary inputs and outputs and analogue inputs and outputs are used as an optimal solution for these varied tasks.

Every REG-D™ regulator can be used as a regulator and at the same time as a transformer monitor, measurement transducer, recorder, statistical unit and ParaGramer. All important network measurement quantities are displayed in measurement trans-ducer mode. Changes in the regulated voltage and additional selectable measurement quantities are recorded in recorder mode. The statistical unit for the tap-changer position offers a clear display of all switching operations of the tap-changer. The ParaGramer provides a complete busbar simulation.It is particularly useful for the parallel connection of several transformers.

The REG-DA regulator features a world innovation as it can be equipped with a high-capacity transformer-monitoring func-tion in accordance with CEI IEC 354 (VDE 0536). This function allows the operator to call up information about the hot-spot temperature and the lifetime consumption of the transformer at any time. If required, the regulator can activate up to six cool-ing levels. The oil temperature can either be recorded directly (PT 100) or via a mA input.

The connection of multiple independent voltage control sys-tems in a network via a bus line enables a central monitoring of the transformers and a mutual exchange of data over large distances via various transfer methods. In particular, the parallel connections of several transformers can be very easily imple-mented this way.

The PAN-D voltage-monitoring unit is used for redundant volt-age monitoring.Both the tap-changer and the regulator can be monitored with the aid of monitoring units.The PAN-D unit supplies a range of signals which enable secure

and concise operation of a transformer.These are output via LEDs and relay contacts and include the following: voltage limits <U1, >U2, <<U3, >>U4, tap-changer in operation lamp and the signals “Regulator fault” and “Tap-Changer fault”, etc.

Application-specifi c tasks can also be implemented via freely programmable inputs and outputs.REGSys™ is able to communicate with a central control unit via all common protocols.

The following protocols are available:• IEC 60870 - 5 - 101 / 103 / 104• IEC 61850• LON• DNP 3.0• Profi bus DP• MODBUS RTU• SPABUS

The PAN-D monitoring unit can be usedas an additional safety device.

GB

A. Eberle GmbH & Co. KG

Technical Data

Page 2: REG-D PAN D

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

RS232

RS232

RS485

Status

E-LANRS485

1

2

3

4

5

6 7

8

9

10

11

12

13

COM 1

COM 2

COM 3

µP

LCD

LED

RAM

ROM

CLOCK

Casedifferentiation

REG-D™Program

Boundary conditions

Parallel operationon one(several)busbar(s)

∆I sin ϕ Identical transformers, identical or differenttap changes

∆I sin ϕ (S) Transformers with different performances, different or equaltap changes

Masterslave

Identical transformers, identical tap changes

Free infeed ∆ cos ϕ Any transformers,any tap changes

Emergency pro-gram during bus error

∆ cos ϕ Any transformers,any tap changes for the ∆I sin ϕ and ∆I sin ϕ (S) programs

Description

Functions of the REG-DTM regulator

1 2x current and 2x voltage transformers 2 Analogue mA inputs, Pt 100 3 Binary inputs 4 Input for tap-changer display (tap-change potentiometer) 5 Power supply 6 Display and processing unit 7 Analogue outputs (optional) 8 Binary outputs 9 E-LAN connection (2 x RS485 with repeater function) 10 COM 1, RS232 11 COM 2, RS232 12 COM 3, RS485 (optional) 13 Status signal (life contact)

Regulator modeThe actual value and a fi xed or load-dependent setpoint value are compared in the regulator. The comparison determines the correcting variable for the tap-changer of the transformer, dependent on the regulative deviation. The parameters of the regulator can be optimally adjusted according to the dynamic time behaviour of the network voltage in order to obtain high control performance at a low number of switching operations.

Parallel connection of transformersEvery regulator can be used with other regulators from the REGSys™ family to regulate up to 10 transformers connected in parallel without additional components.

Various processes are available to control the transformers and they are listed in Table 1 according to those that operate in parallel on a busbar and those that are simply freely switched in parallel.An essential factor in this context is that no additional com-ponents are required as all function units required for parallel operation are accommodated within the regulators.

Table 1 Parallel operation of transformers

• Limit value monitoring for all measurement quantities• 4 freely programmable set-point values• Rated values of U and I can be programmed• Implementation of control tasks through ability to freely program• RS485 peripheral bus (COM3) for additional interface modules (ANA-D, BIN-D)• ParaGramer function for the display and automation of any parallel connections with up to ten transformers• WinREG parameterisation software for parameterisation, programming and visualisation as well as for a PC-based archiving and evaluation of the recorder data• REGSim™ simulation software for the simulation of any parallel operation, network and load situations

Technical Data REG-D™

A. Eberle GmbH & Co. KG 2

Page 3: REG-D PAN D

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

Measurement transducer modeThe values of all relevant variables of an equally or arbitrarily loa-ded three-conductor three-phase supply network are calculated and displayed on the basis of the sampling values.In addition, a selection of up to seven measurement values can be output as a DC signal via the analogue outputs.

Furthermore, measurement values which are transferred to the regulator as mA signals from external sources can be displayed. displayed

Recorder modeThe change in the voltage over time and a second selectable measurement quantity are continuously shown on the display in the form of a line chart. The time grid for the recording is adjustable. The present tap position, time and date are recor-ded in addition to the measurement quantity. Therefore, it is possible to display the present voltage and the time-correlated tap position at any time. The average storage time for voltages and tap changes is approximately six weeks.The stored values can be displayed by using the keyboard or the WinREG operating software.

Statistics modeIn the statistics mode, all switching operations of the tap-chan-ger are registered. A differentiation is made between switching operations under load and switching operations without load.

Additionally, a record is kept for every single tap in tabular form. How many tap changes have been carried out during which time period and how often each tap has been selected can be checked using these data. This information can be used to optimise the regulator settings.The saved statistics values can be selected using the keyboard or loaded and printed using WinREG.

ParaGramer modeThe PARAGRAMER is a support tool for the automatic pre-paration of parallel connections and the online display of the switching statuses.The artifi cial word PARAGRAMER is a combination of the two terms parallel and one-line diagram.The PARAGRAMER shows the switching status of the individual transformers in a one-line diagram.The function is activated by feeding each regulator with a com-plete busbar replica (position of circuit breakers, disconnectors, bus ties and bus couplings).Based on the switching states of all regulators involved in the parallel connection, the system autonomously detects which transformer is to work with which other transformer(s) in parallel connection on a busbar.Busbars that are connected via bus coupling(s) are treated as one single busbar by the system.

As shown in the graphic, both transformers T1 and T3 are working on busbar “a”, whereas transformer T2 is feeding into busbar “b”.

Technical Data REG-D™

3 A. Eberle GmbH & Co. KG

Page 4: REG-D PAN D

AUTOlocal

remote ESC MENU

PAN-D

COM1

a-eberle

Betrieb

Störung

< U1

> U2

U« 3

Auslösung

Phasenfall

Lauflampe

Leistungsschalter

StörungStufenschalter

StörungRegler

U» 4

NOT-AUSStufenschalter

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

RS232

Status

E-LANRS485

1

2

3

4 5

6

7

8

COM1

µP

LED

RAM

ROM

Transformer monitoring mode TMMThe essential characteristic quantities of the transformer are monitored in the monitoring mode. The oil temperature can also be recorded in addition to the tap-changer statistics. In accordance with IEC 354 (VDE 0536/3.77), the hot-spot tem-perature is determined on the basis of the oil temperature and the winding current and subsequently extrapolated to determine the residual lifetime of the transformer.Fans can be set to one of six levels and an oil pump can be used to regulate the temperature. Furthermore, the oil levels can be monitored and the operating hours of the fans and the pumps can be counted.

PAN-D Voltage Monitoring UnitThe PAN-D monitoring unit is assigned to a regulator and can be switched to this regulator via bus (E-LAN).

The PAN-D monitoring unit is parameterized either directly via the unit interface or via the keyboard and display of the regu-

Functions of the PAN-D monitoring unit

1 Voltage transformer 2 Binary inputs 3 Power supply 4 Display and processing unit 5 Binary outputs 6 E-LAN connection (2 x RS485 with repeater) 7 COM 1, RS232 8 Status signal (life contact)

lator. The PAN-D unit can function without a bus connection in normal operation and works as a totally independent and additional monitoring unit.

The regulator can be optionally supplied with a PT100 module or a mA input for measuring the oil temperature.In total, three connection points are available. This means that several temperatures can be recorded via mA inputs or the PT 100 if required.The possible combinations can be found in Feature Group “E” in the ordering information.

Technical Data REG-D™

A. Eberle GmbH & Co. KG 4

Page 5: REG-D PAN D

AC current inputs (IE) only for REG-DTM

Measurement current In 1 A / 5 A (hardware and software selectable)Curve shape SinusoidalFrequency range 16....50....60....65 HzInternal consumption ≤ 0.5 VAOverload capacity 10 A continuous 100 In for 1 sec (max. 300 A) 30 In for 10 sec 500 A for 5 ms

Technical Characteristics*) Data is valid for both REG-DTM and PAN-D

Regulations and standards *)IEC 1010/ EN61010 (VDE 0411)CAN / CSA - C 22.2 No. 1010.1 - 92VDE 0110IEC 255 - 4EN 55011 : 1991EN 50082 - 2 : 1995IEC 688 - 1IEC 529EN 50178 / VDE 0160 / 11.94VDE0106 part 100

AC voltage input (UE) *)

Measurement voltage UE 60 ... 140 V (software selectable)Curve shape SinusoidalFrequency range 16....50....60....65 Hz

Internal consumption ≤ U2 / 100 kΩOverload capacity 300 V continuous Resistance input for

tap-change potentiometer

If the tap-changer position is supplied as a resistance value (tap-change potentiometer), then an appropriate module can also be connected (see Feature Group “E” or Accessories).In this case the resistance measurement transducer is no longer required.Resistance ranges from 200 Ohm to 20 kOhm can be converted into tap changes.The specifi ed resistances correspond to the total resistance in the resistance chain.The number of Ohms per tap-change (e.g. 10 Ohm/tap-change) can be specifi ed using the keyboard.

Resistance measurement is normally carried out for a 3-con-ductor circuit. If a 4-conductor measurement circuit is required, this can also be confi gured.The resistance-measurement equipment consists of a program-mable current source to feed the measurement resistance and a voltage-measurement device to measure the voltage at the resistance.The measurement result is output with a resolution of 12 bits and a refresh rate of approx. 10 Hz (0.1 s).

The measurement device has a broken-wire detection sys-tem. The parameters are input in an application menu using the keyboard.

Temperature input PT 100

Number Up to three PT 100 in- puts are possibleConnection 3-conductor circuitCurrent through sensor <8 mALine compensation No compensation requiredTransmission behaviour Linear

Analogue inputs (AI) only for REG-DTM

Number See ordering informationInput range X1...X2 -20 mA...0...20 mA X1 and X2 programmableControl limit ± 1.2 X2Voltage drop ≤ 1.5 VElectrical isolation OptocouplerCommon mode rejection > 80 dbSeries mode rejection > 60 db / order of magnitude from 10 HzOverload capacity ≤ 50 mA continuousError limit 0.5 %

The inputs can be continuously short-circuited or operated open. All inputs are galvanically isolated from all other circuits.

Analogue outputs (AO) only for REG-DTM

Number See ordering informationOutput range Y1...Y2 -20 mA...0...20 mA Y1 and Y2 programmableElectrical isolation OptocouplerLoad range 0 ≤ R ≤ 8 V / Y2Alternating component < 0.5 % from Y2

The outputs can be continuously short-circuited or operated open. All output connections are galvanically isolated from all other circuits.

Technical Data REG-D™

5 A. Eberle GmbH & Co. KG

Page 6: REG-D PAN D

Limit value monitoring *)Limit values ProgrammableResponse time ProgrammableAlarm display Programmable LEDs

Measurement quantitiesVoltages TRMS U12, (U23, U31 )(≤ 0.25 %)Current TRMS I1 (I2 ; I3) (≤ 0.25 %)Active power P (≤ 0.5 %)Reactive power Q (≤ 0.5 %)Apparent power S (≤ 0.5 %)Power factor cos ϕ (≤ 0.5 %)Reactive current I · sin ϕ (≤ 1 %)Frequency f (≤ 0.05 %)

Reference conditions *)Reference temperature 23 °C ± 1 KInput quantity UE = 60 ... 140 V IE = 0 ... 1A / 0 ... 5 AFrequency 50 Hz...60 HzCurve shape Sine, form factor 1.1107Auxiliary voltage H = Hn ± 1%Load (only for features E91...E900) Rn = 5 V / Y2 ± 1%Other IEC 688 - part 1

Binary inputs (BI) *)

Feature D1Inputs E1 ... E8Control signals Ust Within the 48 V...250 V AC/DC rangeCurve shape, permissible Rectangular, sinusoidalH level ≥ 48 VL level < 10 VSignal frequency DC ... 50 HzSwitching delay Selectable from 1..999 sInput resistance 108 kΩElectrical isolation Optocoupler; all inputs are galvanically isolated from each other

Inputs E9 ... E16Control signals Ust Within the AC/DC range 10 V...50 VCurve shape, permissible Rectangular, sinusoidalH level ≥ 10 VL level < 5 VSignal frequency DC ... 50 HzInput resistance 6.8 kΩElectrical isolation Optocoupler; all inputs are galvanically isolated from each other.

Feature D2Inputs E1 ... E16Control signals Ust Within the 48 V...250 V AC/DC rangeCurve shape, permissible Rectangular, sinusoidalH level ≥ 48 VL level < 10 VSignal frequency DC ... 50 HzSwitching delay Selectable from 1..999sInput resistance 108 kΩElectrical isolation Optocoupler; all inputs are galvanically isolated from each other.

Feature D3Inputs E1 ... E16

Control signals Ust Within the AC/DC range 10 V...50 VCurve shape, permissible Rectangular, sinusoidalH level ≥ 10 VL level < 5 VSignal frequency DC ... 50 HzInput resistance 6.8 kΩElectrical isolation Optocoupler; all inputs are galvanically isolated from each other.

Binary outputs (BO) *)

Status Relays 1 ... 9, PAN-D Relays 7 ... 14Max. switching frequency ≤ 1 HzElectrical isolation Isolated from all device- internal potentialsContact load AC: 250 V, 5 A (cosϕ = 1.0) AC: 250 V, 3 A (cosϕ = 0.4) DC: 220 V, 150 W switching capacityNo. of switching operations ≥ 5·105 electrical

Example circuit diagram of a binary input

Technical Data REG-D™

A. Eberle GmbH & Co. KG 6

Page 7: REG-D PAN D

III II

Input circuits of the current and voltage transformers Auxiliary voltage

Control circuits, analogueinputs, analogue outputsCOM´s, E-LAN

50 V 150 V 230 V

E-LAN,COM 1...COM 3,analogue inputs,analogue outputs,inputs 10...50 V

Voltage input,current input

Auxiliary voltage,binary inputs,relay outputs,status

Test voltages Mount.*

Uh* COMs* BO* BI*BI*

50 VAI AO UE* IE

Mounting rack Mount.* - 2.2 0.35 1.35 1.35 0.35 0.35 0.35 1.35 1.35

Auxiliary voltage Uh* 2.2 - 3.7 2.9 2.9 3.7 3.7 3.7 2.6 2.6

COMs COMs* 0.35 3.7 - 2.3 2.3 0.5 0.5 0.5 2.8 2.8

Binary outputs BO* 1.35 2.9 2.3 - 2.0 2.3 2.3 2.3 2.6 2.6

Binary inputs (250 V) BI* 1.35 2.9 2.3 2.0 - 2.3 2.3 2.3 2.6 2.6

Binary inputs (50 V) BI 50V* 0.35 3.7 0.5 2.3 2.3 - 0.5 0.5 2.8 2.8

Analogue inputs AI 0.35 3.7 0.5 2.3 2.3 0.5 - 0.5 2.8 2.8

Analoge outputs AO 0.35 3.7 0.5 2.3 2.3 0.5 0.5 - 2.8 2.8

Input voltage UE* 1.35 2.6 2.8 2.6 2.6 2.8 2.8 2.8 - 2.2

Input current IE 1.35 2.6 2.8 2.6 2.6 2.8 2.8 2.8 2.2 -

Feature H0 H1 H2

AC (internal) 75 V...185 V - -

AC - 85...264 V 18 ...72 V

DC 88...280 V 18 ...72 V

Power cons. ≤ 15 VA ≤ 15 VA ≤ 10 Watt

Frequency 45...400 Hz 45...400 Hz -

Microfuse T2 250 V T2 250 V T2 250 V

Electrical safety *)Safety class IDegree of pollution 2Overvoltage category II, III

Operating voltages

Immunity to Electrostatic dischargesinterference according to EN 61000-4-2:1995 Air discharge: 8 kV Contact discharge: 8 kV Electromagnetic fi elds according to ENV 50140:1993 and/or ENV 50204:1995 80 - 1000 MHz: 10 V/m 900 ± 5 MHz: 10 V/m pulse- modulated Fast transient interferences (bursts) according to EN 61000-4-4:1995 Supply voltage: AC 230 V: 2 kV; Data cables: 1 kV Conducted interferences according to ENV 50141:1993 0.15 - 80 MHz: 10 Veff 50 Hz-magnetic fi elds acc. to EN 61000-4-8:1993 30 A/m

Emitted Group 1 limit class Ainterference according to EN 55011:1991

Transmission behaviour *)Error limit 0.05% / 0.5 % / 1% All error data compared to Y2 (see “Measurement Quantities”)Measurement cycle time ≤ 10 msSampling rate ≤ 1 kHz

Note: All test voltages are AC voltages in kV, which may be applied for 1 minute. COM1, COM2, COM3 are tested against each other with 0.5 kV. * Also valid for PAN-D

Power supply *)

The following applies to all features:Voltage dips lasting < 80 ms cause neither loss of data nor malfunction.

Climatic stability *)Temperature range Function (housing) -10 °C...+50 °C Function (plug-in module) -10 °C...+60 °C Transport und storage -25 °C...+65° C

Data storageDevice settings Serial EEPROM with ≥ 1000 k read/write cyclesRAM data Li battery laser-welded(recorder function Feature S1)

Display only for REG-DTM

LCD display 128 x 128 graphics-capableLighting Programmable switch on/off

Technical Data REG-D™

7 A. Eberle GmbH & Co. KG

Page 8: REG-D PAN D

123456

d b z d b z

1

2

3

4

2

16

20

24

28

32

22

26

30

d b z d b z d b z

5

62

32

2

32

2

32

2

32

12356

d b z d b z2

16

20

24

28

32

22

26

30

d b z d b z d b z2

32

2

32

2

32

2

32

CP

- 4

7.6220.3220.3240.6445.72

15.24

CP

- 1

CP

- 2

CP

- 3

CP

- 6

CP

- 5

7.6220.3220.3240.6445.72

CP

- 1

CP

- 2

CP

- 3

CP

- 6

CP

- 5

Socket connector 1 2 3 4 5 6

Guide n - - - - n+26

Screws n n+4 n+8 n+11 n+16 n+25

Mechanical design *)Plug-in moduleFront panel Plastic, RAL 7035 grey on aluminium supportHeight 3 U (132.5 mm)Width 28 T (142.2 mm)Circuit board 160 mm x 100 mmWeight ≤ 1.5 kgDegree of protection Plug-in module IP 00 Socket connector IP 00Mounting Acc. to DIN 41494 part 5Plug-in connectors DIN 41612

Position of the REG-D™ socket connectors

Position of the REG-D™ blade connectors

Position of the PAN-D socket connectors

Position of the PAN-D blade connectors

Installation in the mounting rackThe mounting rack has 84 sections and therefore 84 “n” place numbers. A specifi c place number is the reference point for the installation of the guide and the connection elements on the rear of the mounting rack.

Place numbers

Technical Data REG-D™

A. Eberle GmbH & Co. KG 8

Page 9: REG-D PAN D

Socket connector 1; (binary outputs BO)

Raise (2 contact pairs)1 NC contact and 1 NO contact

R1PolePole

b2b4

NCNO

z2z4

Lower (2 contact pairs)1 NC contact + 1 NO contact

R2PolePole

b8b10

NC NO

z8z10

Freely programmable R3 Pole b14 NO z14

Freely programmable R4 Pole b16 NO z16

Freely programmable R5 Pole b20 NO z20

Manual/Automatic(Switch)

Pole b22 Automatic z22

Manual b24

Status Pole b26 NO/NC z24

Binary outputs (BO)4 relaysFreely programmable

GND R6...9 z28

NO R6 b30 NO R8 z30

NO R7 b32 NO R9 z32

Socket connector 2; (binary inputs BI) Features D1...D3

Raise E1 + b2 - z2

Lower E2 + b4 - z4

Standstill E3 + b6 - z6

High-speed switching E4 + b8 - z8

Manual / Automatic E5 + b10 - z10

Manual E6 + b12 - z12

Freely programmable E7 + b14 - z14

Freely programmable E8 + b16 - z16

BCD 1 E9 + b18 - z18

BCD 2 E10 + b20 - z20

BCD 4 E11 + b22 - z22

BCD 8 E12 + b24 - z24

BCD 10 E13 + b26 - z26

BCD 20 E14 + b28 - z28

BCD - E15 + b30 - z30

Freely programmable E16 + b32 - z32

Socket connector 3; (input voltage, auxiliary voltage)

Input voltage L 20 L 22 L 24

Auxiliary voltage L(+) 28 N(-) 30 GND 32

Socket connector 4; (Input for alternating current)

Input current IE1 k 5 l 6

Input current IE2 k 3 l 4

Socket connector 6; (analogue inputs / outputs; inter-faces)

Analogue module 11.1 + b2 1.2 + z2

1.1 - b4 1.2 - z4

E-LAN

Left EA + b6 Right EA + z6

Left EA - b8 Right EA - z8

Left E + b10 Right E + z10

Left E - b12 Right E - z12

Analogue module 22.1 + b14 2.2 + z14

2.1 - b16 2.2 - z16

COM 2

TxD b20 RTS z20

RxD b22 CTS z22

GND b24 +12 V z24

Analogue module 33.1 + b26 3.2 + z26

3.1 - b28 3.3 - z28

COM 3Tx + b30 Rx + z30

TX - b32 Rx - z32

Socket connector 1; (binary outputs 230V)

TrippingCircuit breaker

R1PolePole

b2b4

NONO

z2z4

EMERGENCY OFFTap-changer drive

R2PolePole

b8b10

NONO

z8z10

Raise R3 Pole b14 NO z14

Lower R4 Pole b16 NO z16

Freely programmable R5 Pole b20 NO z20

Freely programmable R6 Pole b22 NO z22

StatusPole b22

Fault b24 Operation z22

Socket connector 2; (binary inputs BI)

Tap-changer in operation E1 + b2 - z2

Freely programmable E2 + b4 - z4

Freely programmable E3 + b6 - z6

Freely programmable E4 + b8 - z8

Freely programmable E5 + b10 - z10

Freely programmable E6 + b12 - z12

Freely programmable E7 + b14 - z14

Freely programmable E8 + b16 - z16

Contact assignment for REG-DTM

Note:All of the inputs are freely programmable, with the exception of the inputs E5 and E6. Table 2 shows an example for assig-ment.

CB-5 can be supplied either with a protocol card (XW1) or an additional binary input or output card if required.

Contact assignment for PAN-DTM

Technical Data REG-D™

9 A. Eberle GmbH & Co. KG

Page 10: REG-D PAN D

E-LAN (L)

Raise

Lower

MANUALAUTO

Freely programmable

Freely programmable

Freely programmable

Open during faultStatus Closed during fault

BCD 10

(-)

BCD 8BCD 4BCD 2BCD 1

BCD 20VZ

GND

Socket connector 6; (analogue inputs / outputs; inter-faces)

Tap-changerfault

Pole b2 NO contact z2

NC contact b4

Regulatorfault

Pole b6 NO contact z6

NC contact b8

<U1Pole b10 NO contact z10

NC contact b12

>U2Pole b14 NO contact z14

NC contact b16

«U3Pole b18 NO contact z18

NC contact b20

»U4Pole b22 NO contact z22

NC contact b24

High-speed swit-ching

Pole b26 NO contact z26

NC contact b28

Freely program-mable

Pole b30 NO contact z30

NC contact b32

Socket connector 3; (input voltage, auxiliary voltage)

Input voltage L1 20 L2 22 L3 24

Auxiliary voltage L(+) 28 N(-) 30 GND 32

Socket connector 6; (interfaces)

E-LAN

Left EA + b6 Right EA + z6

Left EA - b8 Right EA - z8

Left E + b10 Right E + z10

Left E - b12 Right E - z12

Nr.

I **

1Auxiliary voltage UH AC / DC

234

Input voltage UE567 k

Current input8 l9

10

II *

*

11 Input 1 Raise12 Input 2 Lower13 Input 3 Standstill14 Input 4 High-speed switching15 Input 5 AUTO (M / A)16 Input 6 MANUAL17 Input 7 Freely programmable18 Input 8 Freely programmable19 Ground for input terminals 11...1820212223 EA+24 EA-25 E+26 E-

III *

*

27

R128293031

R232333435

R33637

R43839

R5404142

IV *

*

434445464748495051 Freely programmable R9

52 Freely programmable R8

53 Freely programmable R7

54 Freely programmable R6

55565758

Housing *)REGSys™ is also very fl exible with regards to its housing sys-tem. The following are just some of the housing option available. The standard versions are those described by features B05 and B07.Since the number of inputs, outputs, COMs, etc. in a B01 re-gulator plug-in module (basic module for all regulation systems in the housing!) is much larger than the number of terminals available on the housing, the pin assignment can be individually suited for all other housing types.

Note: Further housing types can be found in the brochure “Designs”.

Material PlasticDegree of protection IP 65 Weight ≤ 1.5 kgDimensions See Figure 8 Connection elements Feature B02 2.8 x 0.8 6.3 x 0.8 Fast-on Features B03, B05, B06 Phoenix B07, B91, B92 Screw/clamp terminals

Pin assignment for types B05, B06 and B07**) See Figures 12 to 16 for position of the terminal strip

Technical Data REG-D™

A. Eberle GmbH & Co. KG 10

Page 11: REG-D PAN D

28 TE

3 H

E

128.

5

12173.5

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

138

280

224

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 422 3 4 5 6 7 8 9 101

310

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

%

CAL

MODE

<U1 >U2OVR

COM2

A:REG-D 12:34:00Regler-Modus MANUELL

1. Sollwert 100.0 % 100.0 V

zul. Regelabw. 2.0 %

Stufenstellung 12

Istwert 101.0 V

-10 % 0 +10 %

a-eberle

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

343536373839404142

33323130292827

1

2

3

4

5

6

7

8

9

10

1514131211

181920

1716

212223242526

505152535455565758

49484746454443

progr.

progr.

progr. Hand/Auto

H

A

GND

R6

R7

R8

R9

Schnell-

Still-

BCD 1

(-)

BCD 2

BCD 4

BCD 10

BCD 8

BCD 20

VZ

1A/5Ak

l

U AC/DCH

Hand

Auto(A/H)

E1...E12

progr.

(-)

Status

EA+

EA-

E+

E-

E-L

AN

(L)

StatusNO

NC

U E

schaltung

setzung

progr.

I E1

höher

tiefer

144

288

52 287

REG-D™ / PAN-D plug-in module 28 TE - Feature B01

Panel mounting housing 49 TE - Features B06/B91

Control panel cutout: 280.5 +0.2 mm x 138.3 +0.2 mm

View of fi xing incontrol panel

Wall mounting housing 49 TE - Feature B91

Note:The housing can be supplied with addi-tional equipment as well as application-specifi c pin assignment according to agreement

Technical Data REG-D™

11 A. Eberle GmbH & Co. KG

Page 12: REG-D PAN D

3 H

E

84 TE

245 mm

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

a-eberlea-eberle

144

192

28752

343536373839404142

33323130292827

505152535455565758

49484746454443

1

2

3

4

5

6

7

8

9

10

1A/5Ak

l

U AC/DCH

1514131211

181920

1716

212223242526

Hand

Auto(A/H)

Schnell-

Still-

E1...E12

progr.

(-)

Status

progr.

progr.

EA+

EA-

E+

E-

E-L

AN

(L)

StatusNO

NC

U E

schaltung

setzung

progr.

progr.

I E1

höher

tiefer

A:REG-D 12:34:00Regler-Modus MANUELL

1. Sollwert 100.0 % 100.0 V

zul. Regelabw. 2.0 %

Stufenstellung 12

Istwert 101.0 V

-10 % 0 +10 %

a-eberle

COM2

BCD 1

(-)

BCD 2

BCD 4

BCD 10

BCD 8

BCD 20

VZ

Hand/Auto

H

A

GND

R6

R7

R8

R9

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

138

280

224

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 422 3 4 5 6 7 8 9 101

310

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

COM2

Note:The housing can be supplied with additional equipment as well as application-specifi c pin assignment according to agreement

Control panel cutout: 184.5 +0.2 mm x 138.3 +0.2 mm

View of fi xing incontrol panel

Panel mounting housing 30 TE - Feature B05(Panel mounting housing as standard)

Wall mounting housing 49 TE - Feature B07(Wall mounting housing as standard)

Mounting rack 84 TE - Feature B92

Note:The housing can be supplied with addi-tional equipment as well as application-specifi c pin assignment according to agreement

Technical Data REG-D™

A. Eberle GmbH & Co. KG 12

Page 13: REG-D PAN D

Mounting rack 84 TE Rear view with terminals - Feature B92

Fibre-optic cable output asST or FSMA connection

Technical Data REG-D™

13 A. Eberle GmbH & Co. KG

Page 14: REG-D PAN D

CPR-D a-eberle

COM1

Status

Reset

EOR-D a-eberle

COM1

Status

Reset

EOR-D a-eberle

COM1

Status

Reset

EOR-D a-eberle

COM1

Status

Reset

EOR-D a-eberle

COM1

Status

Reset

PQI-D a-eberle

COM1

Status

Reset

ANA-D

a-eberle

BIN-D

a-eberle

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

MMU-D a-eberle

COM1

Status

Reset

AUTOlocal

remote ESC MENU

PAN-D

COM1

a-eberle

Betrieb

Störung

< U1

> U2

U« 3

Auslösung

Phasenfall

Lauflampe

Lei stu ng sschal ter

StörungStu fensch alter

StörungReg ler

U» 4

NOT-AUSStu fensch alter

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-DP

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

REG/ST

a-eberle

REG-F

a-eberle

REG-S

a-eberle

REGSys™ - Overview

RS232

RS485

LWLWinREG

Windows 95Windows 98Windows NTWindows 2000Windows XP

Ethernet IEC 61850

IEC 60850-5-101/103/104MODBUS, SPABUS,LONMark, DNP 3.00

BCD-CODE (Tap position)

COM3

BIN-D ANA-D

COM1RS232

REG-BO

Remote control unit

BCD-CODE

REG-DPPAN-D REG-ST

REG-F(X)REG-S

MMU-DREG-D

REG-D

CPR-D EOR-D

E-LAN

REG-BO

REG-PC

PQI-D

RS232

E-LAN< 5

km

E-LANE-LAN

E-LANRS485

RS485

REGSim™

AUTOlocal

remote ESC MENU

F5

F4

F3

F2

F1Status

< U

> U

> I

REG-D

COM1

a-eberle

Display

X = 81,15y = 76,95

B = 67,818 mmH = 67,818 mm

Network / parallel connectionThe networking of several regulators to a system is particularly required with transformers connected in parallel. The ∆I sinϕ, ∆I sinϕ (S) and Master-Slave parallel connection programs can only be implemented by the system bus (E-LAN). This enables the individual group members of a parallel connection to com-municate with each other easily without the need for additional components.The stations do not need to be connected for the operation of a parallel connection which works in accordance with the ∆ cosϕ procedure. Due to the large distances, such a connection is not normally possible anyway

Serial interfacesRS232 interfaces

Connection elements COM1 Sub Min D on the front of the device, pin assignment as on PC COM2 Pin connection Terminal strip (Circuit board VI)

Connection possibilities PC, terminal, modem, PLC

Number of data bits/ protocol Parity 8, even, off, oddTransfer rate bit / s 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200 76800, 115200

HANDSHAKE RTS / CTS or XON / XOFF

RS485 interfaceEvery REG-D™ regulator is provided with a double E-LAN interface as standard. It provides the bus connection of in-dividual regulators and monitoring units to a form a voltage control system.

E-LAN (Energy - Local Area Network)Features• 255 bus stations can be addressed• Multimaster structure• Integrated repeater function• Open ring, bus or combination of bus and ring possible possible• Log based on SDLC/HDLC framework• Transfer rates of 62.5 or 125 kbit/s• Telegram length 15.6... 375 kbits/s• Average throughput approx. 100 telegrams / sec at 62.5k

COM3For connection of 15 interface modules (BIN-D, ANA-D) in any combination to any REG-D™ regulator.

REGSimTM simulation softwareREGSim™ was designed as a PC-based program for the simulation of parallel connections of several transformers with any possible combinations of network and load.

The transformers, the network and the load are simulated in a mathematically exact manner to ensure that the REG-D™ regulators operate in the same way in the simulation as they do in the network.The authenticity of the simulation is guaranteed because REGSimTM uses the original algorithm of the REG-D™ regu-lator.All the setting options correspond to those in the real regulator and the simulation “runs” in real time.

Technical Data REG-D™

A. Eberle GmbH & Co. KG 14

Page 15: REG-D PAN D

Undervoltage <U1 0 ... -25 %

Undervoltage >U2 0 ... 25 %

Undervoltage «U3 0 ... -35 %

Undervoltage »U4 0 ... 35 %

Tripping 100 ... 135 V

Switching delay for<U1, >U2, «U3, »U4

The standstill can be set sepa rately

1 ... 999s

Laufl ampe - Maximalzeit 3 ... 40s

Parameter Setting rangePermissible regulative deviation ± 0.1 ... 10%Time factor 0.1 ... 301st setpoint value 60.0 ... 140.0 V2nd setpoint value 60.0 ... 140.0 V3rd setpoint value 60.0 ... 140.0 V4th setpoint value 60.0 ... 140.0 V

Time behaviour

∆U · t = constREG 5A/ELINEARCONST

Current infl uence

Apparent currentActive currentReactive currenLDC

Apparent current / Active currentGradientLimitation

0 ... 40 %0 ... 40 %

LDC(Line Drop Compensation)

R : 0 ... ±30 ΩX : 0 ... ±30 Ω

Undervoltage <U -25 % ... +10 %Overvoltage >U 0 ... 25 %Overcurrent >I 0 ... 210 % (1 A / 5 A)Tripping 60 V ... 160 VHigh-speed forward switching 0 ... -35 %High-speed backwards switching 0 ... 35 %Standstill -75 % ... 0 %Switching delay for<U, >U, <I, tripping,high-speed switchingThe standstill can be set sepa-rately

1 ... 999 s

(High-speed forward switching 2...999 s)

ParametrierungREG-D - Parameters (selection)

WinREG parameterisation andconfi guration softwareWinREG was designed for the parameterisation and program-ming of the system. WinREG can be operated in three different modes.In the Panel mode, up to six regulators can be simultaneously displayed and operated via the mouse.All settings that can be carried out directly on the regulator via the membrane keyboard can also be carried out centrally via WinREG. However, all the regulators need to be connected together via E-LAN to be able to do this.This operating mode provides a considerably simplifi ed and more transparent operation, particularly when the transformers are operated in parallel.If WinREG is used to change all the regulators of the trans-formers that are operating in parallel into the measurement transformer mode, all the circulating reactive currents of the transformers can be displayed on a PC monitor in real time.The Parameter mode allows for an easy parameterisation of the individual components. The individual parameters can be entered, stored for future use or transferred to a station using the clear tabbed structure.The Terminal mode provides the possibility of direct commu-nication with the system.Therefore, the WinREG terminal is far easier to use than traditi-onal terminal programs and considerably simplifi es the system programming. WinREG runs under Windows 95, 98, Windows 2000, NT or Windows XP and is also available in a modem-enabled version.

Recorder ModeTme grid YT 14 s, 1, 5, 10, 30, min / divisionsAll measurement values are stored in seconds, independent of the selected YT time grid (feed speed).The value every second represents the arithmetic average of the previous 10 measurement values generated in intervals of 100 ms.

Memory response Stop or overwrite;at overfl ow FIFO with overwrite (First in First out)

Storage time > 18.7 days in worst case(Voltage plus tap-change) On average > 1 month

Measurement transducer modeMeasurement quantities Voltage Ueff

in the display Current Ieff

Active power P Reactive power Q Apparent power S cosϕ ϕ Circulating reactive current I sinϕ Frequency f

Analogue output Max. 6 mA output (2.5, 5, 10, 20 mA bipolar)

Characteristic curve Linear, with corner

Max. load RAmax RA = 8 V/IAN

RA Load IAN Nominal value of the output current

PAN-D - Parameters

Technical Data REG-D™

15 A. Eberle GmbH & Co. KG

Page 16: REG-D PAN D

OptionM2

Stat

usA

nalo

gue

- cha

nnel

s (O

ptio

n E

9x)

Inpu

t or o

utpu

t

E-LA

NL

E-LA

NR

+M

odul

e 1

L(+)

L(-)

Man

ual /

Auto

.

Automatic

MANUAL

-20 ... 0 ... +20 mA

-20 ... 0 ... +20 mA

-20 ... 0 ... +20 mA

-20 ... 0 ... +20 mA

-20 ... 0 ... +20 mA

-20 ... 0 ... +20 mA

low

er

rais

e

2832

30

3

-+

++

++

--

--

-M

odul

e 2

Mod

ule

3

42

414

16b

zz

bb

1416

2628

2628

zz

bb

zz

2Bin

ary

inpu

ts

+-

++

++

+-

--

--

+-

+-

b 22

44

66

zb

zb

z8

810

1012

12b

zb

zb

zb 14

1416

1618

zb

zz

2020

2222

2424

bz

bz

bz

b 226b

26z28b

RS2

32C

OM

1C

OM

2R

S232

(Opt

ion

R1)

CO

M3

RS4

85

68

1012

2022

2420

2224

3230

3230

bb

bb

zz

zz

68

1012

EA+EA-E+E-

EA+EA-E+E-

Tx+Tx-

Rx+Rx-

bb

zz

TxDRxDGNDRTSCTS

+12V

bb

bz

zz

6

5 6

k l

42 2

1

4108810141416162028 2032 30 32 30 222422

26b24z 1Pol

NC contact /NO contact

bbzzbbzzbzb

MAz b b

BA4

BA3

BA2

GN

D

zz z b b bz z

Binary outputs 230 VBinary outputs230 V

6

61

23

45

78

9

GNDRI

DTRCTSTXDRTSRXDDSRDCD

E1E2

E3E4

E5E6

E7E8

freel

y

18b+-

E9+

-E1

0+

-E1

1+

-E1

2+

-E1

3

28z

+-

E14

30b30z

+-

E15

32b32z

+-

E16

IE1

3 4

k l

4

U L120

L2 L3

32422

R2

R3

R4

R5 R

1

IE2

OptionM2

R9

R8

R7

R6

BA1

µP

LED

CLO

CK

RA

M/R

OM

Display

LCD

Key

boar

d

128 x 128DOTS

Pin

assi

gnm

ent

Sock

et c

onne

ctor

no.

Row

Freely configurable

Freely configurable

Freely configurable

Freely configurable

Pin

assi

gnm

ent

Sock

et c

onne

ctor

no.

Row

Pin assignmentSocket connector no.

Freely configurable

Freely configurable

Freely configurable

Freely configurable

Freely configurable

Freely configurable

Freely configurable

Freely configurable

Freely configurable

Freely configurable

Pin assignmentSocket connector no.

Row

Pow

er s

uppl

yA

C o

r DC

D-S

ub p

in s

trip

fron

t sid

e

freel

y

freel

y

REG-D™ block diagram

Technical Data REG-D™

A. Eberle GmbH & Co. KG 16

Page 17: REG-D PAN D

Pow

er s

uppl

yA

C o

r DC

R14

Mel

dung

en

Stat

us

E-LA

NL

E-LA

NR

2832

303

2

Bin

ary

inpu

ts

+-

++

++

+-

--

--

+-

+-

b 22

44

66

zb

zb

z8

810

1012

12b

zb

zb

zb 14

1416

16z

bz

Pin

assi

gnm

ent

Sock

et c

onne

ctor

no.

Row

3230

30

5

RS2

32C

OM

1

2422

2220

1818

1614

1412

68

1012

bb

bb

zz

zz

68

1012

E+E-

EA+EA-E+E-

D-S

ub p

in s

trip

fron

t sid

e

U

203

42

2

14

108

810

1414

1616

2020

2624

22b24b 1

bb

zz

bb

zz

bz

bz

bz

bz

Bin

ary

outp

uts

230

V

2422

61

23

45

78

9

GNDRI

DTRCTSTXDRTSRXDDSRDCD

EMERGENCYOFF

-Tap changerdrive

1010

86

64b

2z2bTap-

changerfault

Regulatorfault

<U1

>U2

« U3

Freely

R12

R11

R10

R9

R8

R7

6b

zb

bz

bb

zb

bz

bb

zb

bz

b

R6

R5

R4

R3

R2

R1

22z

12

34

56

78

EA+EA-

2826

26

R13

bz

b

Trippingof circuitbreaker

Raise

Lower

L(+)

L(-)

Tap-changerin operation

Freelyconfigurable

Freelyconfigurable

Freelyconfigurable

Freelyconfigurable

Freelyconfigurable

Freelyconfigurable

Freelyconfigurable

Des

igna

tion

L1 L2 L3

Pol

malfunktion

in operation

High-speedswitching

» U4

BA4

BA3

BA2

BA1GND28

3230

3230

zz

bb

z

Bin

ary

outp

uts

230

V

µP

LED

CLO

CK

RA

M/R

OM

Display

Key

boar

d

48 ..

. 230

V A

C/D

C

Freelyconfigurable

Freelyconfigurable

Pin

assi

gnm

ent

Sock

et c

onne

ctor

no.

Row

Des

igna

tion

Designation

Pin assignmentSocket connector no.

PAN-D block diagram

Technical Data REG-D™

17 A. Eberle GmbH & Co. KG

Page 18: REG-D PAN D

Feature CODE

REG-D™ PAN-D

REG-D™ voltage regulator, 28TE, 3HE plug-in moduleStandard version, with double E-LAN interface, COM 1, COM 2,16 binary inputs, 10 relay outputs plus status relays andWinREG parameterisation and programming software incl. connection cable

REG-D™

PAN-D monitoring unit, 28TE, 3HE plug-in moduleStandard version, with double E-LAN interface, COM 1, COM 2,8 binary inputs, 14 relay outputs plus status relays

PAN-D

Design 19” plug-in module

Wall-mounting housing (30TE) - without wiringWall-mounting housing (30TE) - with wiring

(Terminals compatible with REG 5A)Wall-mounting housing (30TE) - with wiring

(Terminals compatible with Pantavolt 2)Panel-mounting housing (30TE) with wiringPanel-mounting housing (49TE) with wiring

Wall-mounting housing (49TE) with wiringWall-mounting or panel-mounting housing (30/49TE) on request

19” mounting rack according on request

B01B02B03

-

B05B06B07B91B92

B01B02

-

B03

B05B06B07B91B92

Power supplyFrom monitoring network 80 V ... 110 V ... 185 V AC

External 85 V ... 110 V ... 264 V AC / 88 V ... 220 V ... 280 DCVExternal 18 V ... 60 V ... 72 V DC

H0H1H2

H0H1H2

Input current IEN 1 AIEN 5 A

F1F2

--

Measurement transducer display functions for network quantitiesThree-phase current with equal load

Three-phase current with unequal loadU measurement for overvoltage, U and I measurements for undervoltage

Other uses of the transformer ( 2 x I, 2 x U, e.g. triple-wound transformer)

M1M2M3M9

----

Recorder functions for network quantitiesIncl. evaluation software

WithoutWith

S0S1

--

Parallel operation without fi rmware for parallel operation with fi rmware for parallel operation

K0K1

--

When ordering please note:• Only one code with the same capital letter is possible• If the capital letter is followed by the number 9, additional details in plain text are required• If capital letters are followed by 0, the code can be omitted.

Ordering information

Continued on next page

Technical Data REG-D™

A. Eberle GmbH & Co. KG 18

Page 19: REG-D PAN D

Feature CODE

REG-D™ PAN-D

Analogue inputs and outputsNote:Please specify the scale if known!:

Example:Channel 1: -100 ... 0 ... + 100 MW - 20 ... 0 ... + 20 MWChannel 2: 0 ... 80 ... 100 V 4 ... 16 ... 20 mAChannel 3: 1 ... 19 tap-change positions 0 ... 20 mA

Note:A total of 3 modules may be used. Pay atten-tion to the TMM particularly with use of the transformer monitoring module!

withoutwith 2 inputswith 4 inputswith 6 inputs

with 2 outputswith 4 outputswith 6 outputs

with 2 inputs and 2 outputswith 2 inputs and 4 outputswith 4 inputs and 2 outputs

Any combination on requesteach with 2 analogue inputs and outputs

PT 100 direct inputTap-change potentiometer input

E00E91E92E93E94E95E96E97E98E99E900

-----------

Binary inputs (freely programmable)E1...E8: 48..250 V AC/DC, E9...E16: 10 ... 50 V AC/DC (can also be used as a BCD input)

E1...E16: 48 ...250 V AC/DC (can also be used as a BCD input)E1...E16: 10 ...50 V AC/DC (can also be used as a BCD input)

D1D2D3

---

RS485 interface (COM 3)Note:COM 3 is only required for ANA-D and BIN-D!

withoutwith

R0R1

--

Control system connection: Internal or external:without (more in Feature Group “Y”))

with integrated connection (more in Feature Group “XL”)with ext. connection (REG-P/PE/PM) more in Feature Group “Y”)

XW0XW1XW9

---

Integrated protocol interface cardfor control connection of REG-D™ systemfor control connection of multiple systems

Note: XL9 can only be combined with XZ15..XZ19 and XZ91

XL1XL9

--

Type of connection:Copper

RS 232RS 485 only for 2-wire operation

Note: XV13 .. XV 19 can only be selected in combination with B02…B92.In all other case, select the appropriate fi bre optic cable module!

Fibre optic cable with FSMA connectionGlass fi bre (wavelength 800...900 nm, range 2000 m)

Plastic (wavelength 620...680 nm, range 50 m)

Fibre optic cable with ST connectionGlass fi bre (wavelength 800...900 nm, range 2000 m)

Plastic (wavelength 620...680 nm, range 50 m)

XV10XV11

XV13XV15

XV17XV19

--

--

--

Continued on next page

Technical Data REG-D™

19 A. Eberle GmbH & Co. KG

Page 20: REG-D PAN D

Feature CODE

REG-D™ PAN-D

LogIEC60870-5-103 for ABB

IEC60870-5-103 for ArevaIEC60870-5-103 for SAT

IEC60870-5-103 for Siemens (LSA/SAS)IEC60870-5-103 for Sprecher Automation

IEC60870-5-103 for others

IEC60870-5-101 for ABBIEC60870-5-101 for IDSIEC60870-5-101 for SAT

IEC60870-5-101 for Siemens (LSA/SAS)IEC60870-5-101 for others

DNP 3.00

LONMark

MODBUS RTU

XZ10XZ11XZ12XZ13XZ14XZ90

XZ15XZ17XZ18XZ19XZ91

XZ20

XZ21

XZ22XZ23

------

-----

-

-

--

Local/remote switching using the keyboard withoutwith

Y0Y1

--

Status output closes during faultopens during fault

U0U1

--

Operating manual GermanEnglishFrench

SpanishItalian

Russian

G1G2G3G4G5G8

G1G2G3G4G5-

Display text Same as operating manualGermanEnglishFrench

SpanishItalianDutchCzech

Russian

A0A1A2A3A4A5A6A7A8

---------

Technical Data REG-D™

A. Eberle GmbH & Co. KG 20

Page 21: REG-D PAN D

REG-D™ accessories IDENT No.

Socket connector 1 (Electronic connector design F, wire wrap) 582.0197

Socket connector 1 (Electronic connector design F, 2.8 faston) 582.0213.01

Socket connector 2 (Current inputs with leading contacts, 2-pole) 582.0258.10

Socket connector 3 (Hybrid connector designs F24 + H7, wire wrap) 582.0215

Socket connector 3 (Hybrid connector designs F24 + H7, 6.3/2.8 faston)

582.0214

Socket connector 4 Current input with leading contacts, 6-pole 582.0258.20

Blanking plate 14TE 566.0014

Blanking plate 7TE 566.0007

Blanking plate 8TE 566.0008

1 pack of T2 L 250 V microfuses 582.1019

Cable for PC connection (null modem cable) 582.020B

Cable for modem connection 582.2040

Fibre optic cable coupler (E-LAN) 111.9030.10

DCF 77 radio clock 111.9024

USB adapter for null modem cable 111.9046

Modem for REG-Dx/EOR-D/PQI-D/MMU-D (standard version Uh: AC 230 V) 111.9030.02

Modem for PC (industrial version Uh: AC 230 V) 111.9030

Analogue input module (2 inputs) 320.0004

Analogue output module (2 outputs) 320.0003

Input module for tap-change potentiometer total resistance 200 Ohm...2 kOhm 320.0002.01

Input module for tap-change potentiometer total resistance >2 kOhm...20 kOhm 320.0002.03

Input module for PT 100 according to DIN 43760 in 3-conductor circuit. 320.0005

E-LAN Y-connection with booster REG-ST

E-LAN PC adapter with booster REG-PC

E-LAN PC adapter, Y-connection with booster REG-ST3

E-LAN booster (wide-range network) REG-BO

Additonal operating manuals for REG-D™ plus PAN-D GX

Additonal operating manuals for REG-D™ (please state language) GX

Technical Data REG-D™

21 A. Eberle GmbH & Co. KG

Page 22: REG-D PAN D

Additions to REG-D™ IDENT. No.

Transformer monitoring module TMM TMM

Consisting of: Firmware- Update (2.X)Analogue module with two inputs for temp. measurement trans-ducerInput for PT 100 according to DIN 43760 in 3-conductor circuitOperating manual and Windows user interfacevia WinREG

A1A2

Additional analogue input module (2 inputs) 320.0004

Additional analogue output module (2 outputs) 320.0003

Additional input module for PT 100 according to DIN 43760 in 3-conductor circuit 320.0005

Profi bus-DP interface moduleIncl. RS 485 interface and connection cable

Design: can be installed on standard mounting rails (120 x 75 x 27) mm, with ext. 24 V power supplyPlug-in module: 12TE/3HE

Profi -DP

B0B1

TCP/IP Adapter (10MB/s)can be installed on standard mounting rails with power supply for Uh 230 V AC

as 8TE plug-in module, 3HE with power supply:85 V ... 110 V ... 264 V AC / 88 V ... 220 V ... 280 V DC

as 8TE plug-in module, 3HE with power supply:18 V ... 60 V ... 72 V DC

100MB/s TCP/IP adapter)

REG-COMA01

A02

A03

A90

Fibre optic cable module with ST connection (glass or plastic))

with FSMA connection (glass or plastic)

Module 1A90A91

Technical Data REG-D™

A. Eberle GmbH & Co. KG 22

Page 23: REG-D PAN D

Notes: .....................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

................................................................................................................................

Technical Data REG-D™

23 A. Eberle GmbH & Co. KG

Page 24: REG-D PAN D

Technical Data REG-D™

A. Eberle GmbH & Co. KG 24

presented by:A.Eberle GmbH & Co. KG