Download - Electrical Machines

Transcript
Page 1: Electrical Machines

Electrical Machines

LSEGG216A9080V

Page 2: Electrical Machines

Transformer Transformer OperationOperation

Week 4 Week 4

Page 3: Electrical Machines

Transformer Transformer OperationOperation

V+ CIVILCIVIL

Voltage Current

Magnetic Flux

Page 4: Electrical Machines

Transformer Transformer OperationOperation

Applied Voltage

Induced Voltage

Induced Voltage in Secondary

Resultant Current

V1

V’1V’2

IM

Page 5: Electrical Machines

Induced VoltageInduced Voltage

• Φmax =Maximum instantaneous flux• F = Frequency• N = Number of turns• Bmax = Maximum permissible flux density in Wb• A = CSA of core in m2

fN44.4V max AfNB44.4V max

Page 6: Electrical Machines

Transformer Transformer OperationOperation

V1

IM

Ie

Io

Ie= Iron loss currentIo = No load current

Page 7: Electrical Machines

Transformer Transformer OperationOperation

V1

V’1V’2

Io

I’2

I’1

I1

Page 8: Electrical Machines

Transformer Transformer OperationOperation

V1

V’1V’2

Io

I’2 I’1

I1

Page 9: Electrical Machines

Transformation Transformation RatioRatioMagnetic flux is common coils

fN44.4V max

Therefore the voltage can be varied by changing the number of turns

Page 10: Electrical Machines

Transformation Transformation RatioRatio

V1= N1

N2V2== k = Transformation Ratio

Page 11: Electrical Machines

Transformation Transformation RatioRatio

V1x I1

N1

N2

= V2 x I2

=I1

I2

Page 12: Electrical Machines

Transformation Transformation RatioRatio

V1x I1

VA

V2 x I2

kVAPower In Power Out

Page 13: Electrical Machines

Transformation Transformation RatioRatio

V1x I1 V2 x I2

200

200V 100V

400

K = 2

Page 14: Electrical Machines

Voltage Voltage RegulationRegulation

EI

Voltage Drop Due to RVoltage Drop Due to XL

V

• Resistance• Inductance

Coils have both

Page 15: Electrical Machines

Voltage Voltage RegulationRegulation

EI V

Lagging PF of 45

V less than E

Page 16: Electrical Machines

Voltage Voltage RegulationRegulation

EI

V

Leading PF of 45

V More than than E

Page 17: Electrical Machines

Voltage Voltage RegulationRegulation

100 x VNo Load – V Full Load

VFull Load

R% =

If PF = Unity

100 x I x (R x cos + XL x sin)

VFull Load

R% =

Page 18: Electrical Machines

Transformer Basic Transformer Basic TestsTests• Open Circuit Test• Short Circuit Test• Oil Tests• Electrical Insulation• Polarity• Continuity

Page 19: Electrical Machines

Open Circuit TestOpen Circuit TestUsed to determine Iron Losses

Supply = Rated Voltage

Page 20: Electrical Machines

Open Circuit TestOpen Circuit Test

Wattmeter reading V1

IMIo

Ie

Supply Voltage

Ammeter reading

Page 21: Electrical Machines

Short Circuit TestShort Circuit TestUsed to determine Copper Losses

Supply Adjusted = Rated Secondary Current