Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller...

46
Total Cost of Ownership Chilled Water Systems April 17, 2008

Transcript of Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller...

Page 1: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Total Cost of Ownership Chilled Water Systems

April 17, 2008

Page 2: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Todd Brown

Business Development Manager - Chillers

Page 3: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

AGENDA

• Low Flow

• Primary-Secondary vs Variable Primary Flow

• Chillers in Series-Series Counterflow

• Chiller-Tower Optimization

Page 4: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Goal:Goal:Minimize Minimize Capital & OperatingCapital & Operating CostsCosts

Without Sacrificing:Without Sacrificing:RReliability, Efficiency, & Comforteliability, Efficiency, & Comfort

Optimizing Chilled Water Performance

Page 5: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

• Good for Business...

– Offers lower first cost and lower operating cost.

• Good for the Environment:

– Reduced utility generated greenhouse gas emissions.

High Performance Chilled Water Systems:

Page 6: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Base Design: 450 Tons• Design

wet bulb: 78 F(25.5C)• Entering condenser

water temperature (ECWT): 85 F(29.4C)

• Evaporator and condenser temperature differences: 10 F (5.6C)

• Coil, valve and chilled water piping pressure drop: 80 ft

• Condenser water piping pressure drop: 30 ft

• Pump efficiency: 75%

• Pump motorefficiency: 93%

Example: Low Flow/ High Delta T

Page 7: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

example chilled water plant …

Chiller (2.4, 3.0 gpm/ton)

• Consumption:256 kW (0.569 kW/ton)

• Evaporatorpressure drop: 21.0 ft

• Condenserpressure drop: 21.3 ft

Page 8: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

example chilled water plant …

Cooling Tower (3.0 gpm/ton)

• Power rating:30 hp

• Tower static head:10.0 ft

Page 9: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

example chilled water plant …

Design Formulas

DP2/DP1 = (Flow2/Flow1)

kW = 0.746 x hpmotor efficiency

hp = gpm x PD3960 x pump efficiency

1.85

gpm œ rpmHead œ (gpm)²Power œ (gpm)³

Page 10: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

example chilled water plant …

Chilled Water Pump (2.4 gpm/ton)

• System conditions …

– System head: 80 ft– Bundle head: 21.0 ft– Flow rate: 1080 gpm

• Pump power …

– 36.7 hp– 29.5 kW

Page 11: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

• System conditions …

– System head: 26.0 ft

– Bundle head: 21.3 ft

– Tower static: 10.0 ft

– Flow rate: 1350 gpm

• Pump power …

– 26.0 hp

– 20.8 kW

example chilled water plant …

Condenser Water Pump (3.0 gpm/ton)

Page 12: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

example chilled water plant …

System Energy Consumption

• With 2.4, 3.0 gpm/ton flows …(0.043, 0.054 L/S/KW)

2.4/3.0Chiller 256.0Chilled Water Pump 29.5Condenser Water Pump 20.8Cooling Tower 24.1

Total kW 330.4

Page 13: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

example chilled water plant …

Low Flow System

Base Case Low Flow……………….

ARI 42, 16dT 44 F, 14dT 44 F, 14dT; 83.3 F 42 F, 16dT

2.4/3.0 1.5/3.0 1.7/2.0 1.7/2.0 1.5/2.0Chiller 256.0 268.0 288.0 269.0 296.0Chilled Water Pump 29.5 16.2 19.0 19.0 16.2Condenser Water Pump 20.8 20.8 11.3 11.3 11.3Cooling Tower 24.1 24.1 16.0 24.1 16.0Total kW 330.4 329.1 334.6 323.4 339.5

Page 14: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

What About Part Load Operation?We’ll use …• Chiller kW values for NPLV

– Derived from the selection program

• Cooling tower kW

– Tower energy at part load based on being linear with speed reduction

And constant kW values for the …

• Chilled water pump• Condenser water pump

Page 15: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Part Load Operation

Page 16: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

you’ve got more …System Design Options

Either …

• Take full energy (operatingcost) savings

Or …

• Reduce piping size and costExperienced designers use pump,piping and tower savings to select aneven more efficient chiller

Page 17: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Decoupled Systems Decoupled Systems moving tomoving to……

Variable Flow SystemsVariable Flow Systems

Page 18: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

58.0°F2571 gpm

44.0°F 2571 gpm

58.0°F

857 gpm(each)

Primary–Secondarydesign

Primary–Secondarydesign

bypass(decoupler)

primarypumpsprimarypumps

secondarypumps

secondarypumps

2571 gpm

44.0°F

44.0°F

44.0°F

58.0°F

58.0°F

58.0°F

857 gpm

857 gpm

857 gpm

Page 19: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

58.0°F2571 gpm

44.0°F 2571 gpm

58.0°F

Variable Primary

design

Variable Primary

design

2571 gpm

44.0°F

44.0°F

44.0°F

58.0°F

58.0°F

58.0°F

857 gpm

857 gpm

857 gpm

ΔP(typical)

Page 20: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

56.0°F1050 gpm

44.0°F 1050 gpm

56.0°F

Variable Primary part loadVariable Primary part load

1050 gpm

44.0°F 56.0°F1050

off

off

ΔP(typical)

Maximum Flow = 1300 gpmMinimum Flow = 244 gpmSelection Flow = 857 gpm

Page 21: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

56.0°F1050 gpm

44.0°F 1050 gpm

56.0°F

Variable Primary part loadVariable Primary part load

1050 gpm

44.0°F 56.0°F525

525

off

ΔP(typical)

Maximum Flow = 1300 gpmMinimum Flow = 244 gpmSelection Flow = 857 gpm

44.0°F 56.0°F

Page 22: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

56.0°F1050 gpm

44.0°F 1050 gpm

51.2°F

857 gpm(each)

Primary–Secondarydesign

Primary–Secondarydesign

664 gpm

primarypumpsprimarypumps

secondarypumps

secondarypumps

1714 gpm

44.0°F

44.0°F

51.2°F

51.2°F

857 gpm

857 gpm

off

44.0°F

Page 23: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Lower Capital Cost Variable Primary advantages

• Fewer …

– Pumps

– Motors

– Pump bases

– Starters and wiring

– Fittings and piping

– Controls

• Less labor

Page 24: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

More Available Space

Opportunity to …

– Add other equipment

– Select larger, more efficient chillers

– Improve service access

Page 25: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Simplified Control

• Unfetters chillers from flow-based control

• Operates distribution pumps to transport water

… not to start/stop chillers

Page 26: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Improved Reliability

Provides system with …

– Fewer pumps and accessories

– Fewer chiller recovery options

– Fewer pump recovery options

– Better balance between pumps and chillers online

Page 27: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Chiller Selection Considerations

• Evaporator flow limits

• Rate-of-change tolerance

• Flow “range-ability”

– Difference between selection flow rate and evaporator minimum flow limit

Page 28: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

What are otherWhat are other’’s s saying???saying???

Variable Primary Flow Chilled Water Plant Design …

Page 29: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.
Page 30: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.
Page 31: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

VFP systems:VFP systems:•• Reduces total annual plant energy 3Reduces total annual plant energy 3--8%8%•• Reduces first cost 4Reduces first cost 4--8%8%•• Reduces lifeReduces life--cycle cost 3cycle cost 3--5%*5%*

*Relative to conventional Decoupled chilled-water systems.

Page 32: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

VPF SystemMore information

• “Don’t Ignore Variable Flow,” Waltz, Contracting Business, July 1997

• “Primary-Only vs. Primary-Secondary Variable Flow Systems,”Taylor, ASHRAE Journal, February 2002

• “Comparative Analysis of Variable and Constant Primary-Flow Chilled-Water-Plant Performance,” Bahnfleth and Peyer, HPAC Engineering, April 2001

• “Campus Cooling: Retrofitting Systems,” Kreutzmann, HPAC Engineering, July 2002

Page 33: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

unsuited for

Variable Primary Flow

• Inadequate control capability– Insufficient chiller unloading

– Vintage chiller controls

• Poor financial return(Consider chilled water reset instead)

Page 34: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Parallel VPF Systems Parallel VPF Systems

moving tomoving to……

Series Evaporator Series Evaporator SystemsSystems

Page 35: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

VPF system configurationsSeries-Counter Flow

VFD

57°F

48.96°F

103.82°F 89.6°F

96.63°F

89.6°F103.82°F

96.63°F

48.96°F 41°F

41°F

Page 36: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

�SingleCompressorChiller

103.82° F

Lift62.82° F

41° F

103.82° F

Lift54.86° F

48.96° F

Upstream Chiller96.63° F

Lift55.63° F

41° F

Downstream Chiller Series-Counter flowArrangement

• Upstream chiller: 103.82 - 48.96 = 54.86• Downstream chiller: 96.63 - 41 = 55.63• Average lift: 55.24

(vs. 62.82 for single compressor (12%))

Better chiller efficiency, but high ΔP

VPF system configurationsSeries-Counter Flow

Page 37: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Chiller–Tower Optimization …

Do It Right!

Chiller–Tower Optimization …

Do It Right!

Page 38: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

chiller–tower optimizationThe Question …

• What’s the “right” condenser water temperature?

Page 39: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Or Said Another Way …

050

100150200250300350400

72 73 74 75 76 77 78 79 80 81 82 83 84 85

Chiller kWTower kWTotal kW

kW

Condenser Water Temperature

Page 40: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

chiller–tower optimizationHow Do You Do It?

With real-life controls!

Page 41: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

• MicroTech II and BAS Combination

The optimized method requires auto-adaptive controls. This control logic constantly adjusts the condenser water supply temperature to the value that uses the least amount of power. The controller measures the power requirement for the chiller and cooling tower. The condenser water temperature setpoint then is altered and the power consumption is checked again. If the total power consumption goes down, a similar adjustment is made and the total power is checked again.

How do you do it?

Page 42: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

What’s good for the component …may NOT be good for the system!

Page 43: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

where’s the meter?The Only Possible Response …

On the building!On the building!

Page 44: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

chiller–tower optimizationIn Summary …

• Defines the optimal entering condenser temperature

• Optimal control is the right thing to do …AND it saves money

• Savings are real and can be quantified• The control strategy is available NOW!

Page 45: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

FirstFirstCostCost

OperatingOperatingCostCost

Exploit technology!Exploit technology!•• Low flowLow flow•• Low temperatureLow temperature•• High efficiencyHigh efficiency•• ControlsControlsLeverage:Leverage:•• Optimized ControlsOptimized Controls•• Variable Primary FlowVariable Primary Flow•• Series EvaporatorsSeries Evaporators

Lowest Total Cost of Ownership

Page 46: Total Cost of Ownership Chilled Water · PDF file · 2016-06-24Better chiller efficiency, but high ΔP VPF system configurations Series-Counter Flow. ... Lowest Total Cost of Ownership.

Questions or Comments?