Slide 1 of 25 Proprietary / Duplication Prohibited Scientech User Group Meeting Contact Us AMS Technology Center, 9119 Cross Park Drive, Knoxville, TN 37923 USA P. 865-691-1756/ [email protected] General Overview and Introduction to EMC Concepts August 11, 2015 Electromagnetic Compatibility (EMC) Basics PRESENTED BY Chad Kiger AMS Corporation EMC Engineering Manager

Transcript of Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf ·...

Page 1: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 1 of 25

Proprietary / Duplication Prohibited

Scientech User Group Meeting

Contact Us AMS Technology Center, 9119 Cross Park Drive, Knoxville, TN 37923 USA

P. 865-691-1756/ [email protected]

General Overview and Introduction to EMC Concepts

August 11, 2015

Electromagnetic Compatibility (EMC) Basics

PRESENTED BY Chad Kiger

AMS Corporation EMC Engineering Manager

Page 2: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 2 of 25

Proprietary / Duplication Prohibited

EMC can be Simplified if you treat it like a Program

• EMC does not begin and end with qualification testing – Think of planting a seed in a garden

• It takes an EMC program - Understand EMC - Know the Requirements - System Design - Construction and Wiring - Qualification Planning and Testing - System Installation - Future Maintenance and Troubleshooting

Page 3: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 3 of 25

Proprietary / Duplication Prohibited

EMC is comprised of two parts

• Emissions – How much electromagnetic energy a device generates

• Immunity – How much electromagnetic energy a device can withstand

Page 4: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 4 of 25

Proprietary / Duplication Prohibited

Myth 1: Noise Takes Path of Least Resistance

SIGNAL GENERATOR

Coaxial Cable – 10.5 feet; 153 mΩ

Copper Wire – 3 inches; 3 mΩ

50 Ω Terminator

Page 5: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 5 of 25

Proprietary / Duplication Prohibited

Where does Current Flow?

Cable Length – 10.5 feet; 153 mΩ Short section – 3 inches; 3 mΩ

Page 6: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 6 of 25

Proprietary / Duplication Prohibited

Video: Resistance vs. Impedance

Page 7: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 7 of 25

Proprietary / Duplication Prohibited

Myth 2: Noise can be drained to earth/ground

Ground Leads from 120VAC Input Power Ground Leads from

DC Power Supply

Ground Lead to Earth

Page 8: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 8 of 25

Proprietary / Duplication Prohibited

Where does the Current Go?

No current flows to Ground Grid Connection

AC Ground from Input Power

AC Ground from DC power supply

AC Ground to Ground Grid

Page 9: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 9 of 25

Proprietary / Duplication Prohibited

Know the Requirements

• Nuclear Regulatory Commission (NRC) – Regulatory Guide 1.180 Revisions 0, 1 (2 under development)

• Electric Power Research Institute (EPRI) – Topical Report TR-102323 Revisions 0,1,2,3,4

• International Electrotechnical Committee (IEC) – IEC 62003 Revision 0, Revision 1 Under Development

• Military Standards – MIL-STD461 E,F

• International Standards – IEC 61000 – CISPR

• Federal Communications Commission (FCC) • Institute of Electrical and Electronic Engineers (IEEE) • American National Standards Institute (ANSI)

Page 10: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 10 of 25

Proprietary / Duplication Prohibited

Applicable EMC Tests from EPRI

MIL-STD-461E Commercial Standard

Low-Frequency Conducted CS101 IEC EN 61000 Part 4 Section 13 And 16

High-Frequency Conducted CS114 IEC EN 61000 Part 4 Section 6

Low-Frequency Radiated RS101 IEC EN 61000 Part 4 Sections 8, 9 and 10

High-Frequency Radiated RS103 IEC EN 61000 Part 4 Section 3

Surge CS116 IEC EN 61000 Part 4 Section 5 and 12 or IEEE C62.41-1991

Electrically-Fast Transient CS115 IEC EN 61000 Part 4 Section 4 or IEEE C62.41-1991

Electrostatic Discharge N/A IEC EN 61000 Part 4 Section 2

Susceptibility Tests

MIL-STD-461E Commercial Standard

Low-Frequency Conducted CE101 None

High-Frequency Conducted CE102 IEC EN 61000-6-4 or FCC 47 CFR Part 15

Low-Frequency Radiated RE101 None

High-Frequency Radiated RE102 IEC EN 61000-6-4 or FCC 47 CFR Part 15

Emissions Tests

Page 11: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 11 of 25

Proprietary / Duplication Prohibited

Differences Among Testing Guidance

High Frequency Radiated Emissions – MIL-STD-461E RE102

Page 12: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 12 of 25

Proprietary / Duplication Prohibited

What tests are critical?

• Emissions

– CE102 High Frequency Conducted

– RE102 High Frequency Radiated

• Susceptibility

– Electrically Fast Transients (EFT)

– CS114 High Frequency Conducted

– RS103 High Frequency Radiated

Page 13: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 13 of 25

Proprietary / Duplication Prohibited

Surge Suppressors (MOVs)

Power Line Filter

• MOVs are downstream of power line filter

• MOVs are in the middle of the cabinet

• Input and output of MOVs and filters are routed together

• MOVs and Filter have long leads to Ground

• There is no separation of power and signal cabling

Design for EMC

Page 14: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 14 of 25

Proprietary / Duplication Prohibited

Excessive Inverter Emissions

Original Configuration

Cable Rerouting

Page 15: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 15 of 25

Proprietary / Duplication Prohibited

Impact of Cable Rerouting

Inverter

DC AC 120 VAC Out

125 VDC In

Inverter

DC AC 120 VAC Out

125 VDC In

Enclosure Enclosure

Page 16: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 16 of 25

Proprietary / Duplication Prohibited

Follow EMC Best Practices

• Power Line Filters – At the cabinet boundary

• Maintain Twisted – With GND Wire for Power

• Power and Signal Cable Separation – Cross at 90º – Separate Cabinet Entry

• Shield Bonding – Short Leads – EMI Reference

• Ground – Follow Safety Codes – Follow EMI Practices

• Do not tie-wrap cables

Page 17: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 17 of 25

Have a Plan for Qualification Testing

• Cable Type – Impacts emissions and immunity – Shielding can significantly change results

• Cable Length – Standards have specific requirements – Affects effective antenna length

• Equipment Grounding – Impacts noise return path – Dictates shielding performance

• Mode(s) of Operation of the EUT – Steady-state mode of operation – Response time of system

Page 18: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 18 of 25

DO NOT FORGET ACCEPTANCE CRITERIA – Its not contained in the EMC guidance documents

• How much can the Analog I/O deviate? – 4-20mA signal – 0.02%, 2%, 20%

• Can the Digital I/O change state? • How much deviation or ripple on

output of a power supply? • Different acceptance criteria for

different EMC tests? – Surge/EFT vs. other tests

Page 19: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 19 of 25

Proprietary / Duplication Prohibited

• Verify the testing is performed according to the test plan

• System configuration is critical

• Support equipment should not impact the test results

EMC Qualification Testing

Page 20: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 20 of 25

Options for Addressing EMC failures

• Live with it

• Modify the system

• Buy something else

• Pencil-whip it

• Perform EMI/RFI site survey – Existing System/Location

– During Installation

– Post Installation

Page 21: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 21 of 25

Proprietary / Duplication Prohibited

EMC Testing is usually put off until the very end

• EMC Testing performed during FAT testing

• System failed CE102 and RE102 emissions testing

• No time to implement and test EMC recommendations

Page 22: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 22 of 25

Proprietary / Duplication Prohibited

On-site testing showed impact of EMC recommendations and plant installation

• Testing was performed with the system de-energized, energized, and operating – Spent Fuel Pool

– Reactor Building

• “As left” CE102 and RE102 test results would not significantly increase the level of emissions at the point of installation

Fuel Handling Bridge

Monopole Antenna

Spent Fuel Pool Area

Page 23: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 23 of 25

Proprietary / Duplication Prohibited

Plant installation is critical for EMC

• Evaluate configuration differences

• Incorporate qualification testing modifications

• Apply EMC best practices • Assess impact of existing

plant wiring on system performance

Page 24: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire

Slide 24 of 25

Proprietary / Duplication Prohibited

EMC Concerns can be Managed Without Significantly Impacting Schedules, Costs, and Sanity

• Attention to detail during the design phase

• Select the appropriate tests and levels for EMC Qualification testing

• Equipment failures can be managed through mitigation and/or justification

• Understand what to look for during installation and troubleshooting

• EMC is not Rocket Science

Page 25: Scientech User Group Meeting - FAMOSfamos.scientech.us/PDFs/2015_Symposium/EMC_Basics.pdf · Scientech User Group Meeting. ... Coaxial Cable – 10.5 feet; 153 m. Ω. Copper Wire