ΜPS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
Transcript of ΜPS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
1/44
Har Hotzvim Industrial Park14 Hartom St., PO Box 45029, Jerusalem 91450, Israel
Tel: +972-2-588-8222 Fax: +972-2-582-8875Email: [email protected] Website: www .gamatronic.com
User Guide and Instruction Manual
PS-SP Series 3:1, 1030 kVA
INPUT: 3X220VAC
OUTPUT: 220VAC,192VDC
WITH BYPASS ISOLATION TRANSFORMER (OPTION)
Release 1.1, January 2009
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
2/44
ii PS 3:1, 1030 kVA, 220 Vac ou t
Gamatronic Electronic Industries Ltd.Har Hotzvim Industrial Park14 Hartom St., PO Box 45029, Jerusalem 91450 IsraelTel: +972-2-588-8222 Fax: +972-2-582-8875Email: [email protected] Website: www.gamatronic.com
The equipment described in this document is not intended for use in connectionwith any application requiring fail-safe performance, unless the applicationdesign includes appropriate redundancy. This exclusion inc ludes the operationof nuclear power facilities, air traffic contro l or navigation systems, weaponscontrol systems, life-support systems, or any other system whose failure couldlead to injury, death, environmental damage or mass destruct ion.
Copyright 2009 by Gamatronic Electronic Industries Ltd. All rights reserved worldwide.
The information contained in this document is proprietary and is subject to all relevant copyright, patent and other lawsprotecting intellectual property, as well as any specific agreement protecting Gamatronic Electronic Industries Ltd.rights in the aforesaid information. Neither this document nor the information contained herein may be published,reproduced or disclosed to third parties, in whole or in part, without the express, prior, written permission ofGamatronic Electronic Industries Ltd. In addition, any use of this document or the information contained herein for anypurposes other than those for which it was disclosed is strictly forbidden.
Gamatronic Electronic Industries Ltd. reserves the right, without prior notice or liability, to make changes in equipmentdesign or specifications.
Information supplied by Gamatronic Electronic Industries Ltd. is believed to be accurate and reliable. However, noresponsibility is assumed by Gamatronic Electronic Industries Ltd. for the use thereof nor for the rights of third partieswhich may be affected in any way by the use thereof.
Any representation(s) in this document concerning performance of Gamatronic Electronic Industries Ltd. product(s) arefor informational purposes only and are not warranties of future performance, either express or implied. GamatronicElectronic Industries Ltd. standard limited warranty, stated in its sales contract or order confirmation form, is the onlywarranty offered by Gamatronic Electronic Industries Ltd. in relation thereto.
This document may contain flaws, omissions or typesetting errors; no warranty is granted nor liability assumed in
relation thereto unless specifically undertaken in Gamatronic Electronic Industries Ltd. sales contract or orderconfirmation. Information contained herein is periodically updated and changes will be incorporated into subsequenteditions. If you have encountered an error, please notify Gamatronic Electronic Industries Ltd. All specifications aresubject to change without prior notice.
mailto:[email protected]://www.gamatronic.com/http://www.gamatronic.com/mailto:[email protected] -
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
3/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t ii i
T BLE OF CONTENTS
1. SAFETY PRECAUTIONS...................................................................................... 1
1.1 Dos .............................................................................................................. 1
1.2 Donts........................................................................................................... 1
2. GENERAL FEATURES ......................................................................................... 22.1 Major Subsystems ...................................................................................... 3
2.1.1 Rectifier/Charger................................................................................. 3
2.1.2 Batteries............................................................................................... 3
2.1.3 Inverter................................................................................................. 3
2.1.4 Static Switch........................................................................................ 3
2.1.5 Control System ................................................................................... 3
2.2 Control Panel .............................................................................................. 4
2.3 Power On Self Tests ................................................................................... 5
2.4 Measurement............................................................................................... 5
2.5 Real-Time..................................................................................................... 6
2.6 Communications......................................................................................... 6
2.7 Event Logs .................................................................................................. 6
2.8 Ease of Use ................................................................................................. 6
2.9 Battery Check.............................................................................................. 6
2.10 Service Mode............................................................................................... 6
2.11 Connections ................................................................................................ 6
2.12 Parallel Operation (Option) ........................................................................ 7
2.12.1Centralized vs. Decentralized Static Switch ..................................... 7
3. CONTROL PANEL & INDICATORS ..................................................................... 9
3.1 Function buttons on the smaller cabinets ............................................. 11
3.2 Information Buttons ................................................................................. 113.3 The Contro l Panel on the Larger Cabinet ............................................... 15
3.3.1 Function But tons on the Larger Cabinet ........................................ 15
3.3.2 Information But tons on the Larger Cabinet ................................... 16
3.4 The LOG, SET, and HELP Buttons for Al l Models ................................. 20
3.4.1 System Fault Diagnost ics ................................................................ 23
3.5 LED Indicators .......................................................................................... 25
3.6 Terminal Connections .............................................................................. 26
4. OPERATING THE PS SERIES UPS ................................................................. 27
4.1 Turning the UPS ON ................................................................................. 27
4.2 Turning the UPS OFF ............................................................................... 27
4.3 Activat ing MAINTENANCE BYPASS (Optional) ..................................... 284.4 Deactivating MAINTENANCE BYPASS (Optional) ................................. 28
4.5 Setting the Real-Time Clock .................................................................... 29
4.6 RS232 Interface......................................................................................... 29
4.7 The Alarm Interface .................................................................................. 30
4.8 Remote Monitor Box (Optional)............................................................... 32
4.8.1 Connecting the Monitor Box to the UPS MS/MP............................ 32
5. TROUBLESHOOTING......................................................................................... 33
6. SITE PREPARATION .......................................................................................... 36
6.1 Site Preparation and Considerations...................................................... 36
6.2 Accessibi li ty .............................................................................................. 36
6.3 Circuit Breakers ........................................................................................ 36
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
4/44
Gamatronic Electronic Industries Ltd.
iv PS 3:1, 1030 kVA, 220 Vac ou t
7. INSTALLATION ................................................................................................... 37
7.1 Installation Procedure............................................................................... 37
8. TECHNICAL SPECIFICATIONS.......................................................................... 39
PS 3:1........................................................................................................... 39
LIST OF FIGURES
Figure 1: UPS Operational Schematic ...................................................................................2Figure 2: Contro l panel on smaller units (PC074).................................................................4Figure 3: Contro l panel on medium-sized units (PC075).....................................................4Figure 4: Contro l panel on the larger units (PC085).............................................................5Figure 5: Special parallel communication cable...................................................................7Figure 6: Cabling for centralized ST.SW. configuration ......................................................8Figure 7: Cabling for decentralized ST.SW. configuration ..................................................8Figure 8: PC074 console .........................................................................................................9Figure 9: PC075 console .........................................................................................................9Figure 10: PC085 console .....................................................................................................10Figure 11: Control panel on the larger cabinet ...................................................................15Figure 12: LOG Messages Structure....................................................................................20Figure 13: Act ive Current Sharing ........................................................................................24Figure 14: Voltage Correction ...............................................................................................24Figure 15: LED indicators on the PC074 and PC075 cabinets ..........................................25Figure 16: LED indicators on the PC085 cabinet ................................................................25Figure 17: Terminal connections on the stand-alone model.............................................26Figure 18: Local-direct connection for monitoring and control ........................................29Figure 19: RS232 Connector Pin Assignment.....................................................................30Figure 20: Troubleshooting flowchart .................................................................................34Figure 21: PC Board Check Points & Voltage Ranges .......................................................35
LIST OF FIGURES
Table 1: Log Variables ...........................................................................................................21Table 2: LED indicators and their meaning .........................................................................25Table 3: Minimum recommended wi re grades (cross-sectional area) .............................37
STANDARDS AND CONVENTIONS
This manual contains diagrams which include images of the LCD display screen of theUPS. Unless otherwise indicated, the readings shown in the screen images arerepresentational only, and are not intended to match the readings on a specificsystem in a particular environment.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
5/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Safety Precautions 1
1. SAFETY PRECAUTIONS
1.1 Dos Read this manual carefully before operating the UPS.
Review the safety precautions described below to avoid damaging users orequipment.
Install the UPS in a clean and well-ventilated location.
Leave at least 20 cm of clearance space between the ventilation holes of theUPS and other objects or walls.
The UPS must be well grounded to the buildings grounding system with aconductor that has a current carrying capacity that matches the rating of theUPS.
If the unit contains an external battery cabinet, periodically check the groundingconnection between the external cabinet and the main UPS cabinet. (Thebatterys cabinet body must be connected with the grounding screw located on
the rear panel of the electronic cabinet.)
Use the UPS only for its intended purpose.
Allow only qualified technicians to service the UPS. There are no user-serviceable components. Do not try to repair it yourself!
WARNING
Appropriate precautions should be taken during inspection and servicing as
there is a risk of lethal electric shock. (The battery cabinet contains a series of
12-Volt batteries that provide high voltage and energy in the UPS body even
when the UPS is not connected to the electricity mains.)
1.2 Donts Do not open the cover under any circumstances.
Do not insert any objects through the ventilation holes.
Do not put objects on the UPS.
Do not move the UPS while it is operating.
Do not turn the UPS upside down during transportation.
Do not connect or disconnect the cable to the battery cabinet before the battery
circuit breaker is turned off.
Do not turn on the battery circuit breaker when the battery cabinet isdisconnected from the UPS.
WARNING
Do not touch the battery terminals of external batteries with bare hands .
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
6/44
Gamatronic Electronic Industries Ltd.
2 General Features PS 3:1, 1030 kVA, 220 Vac ou t
2. GENERAL FEATURES
The PS Series3:1 Phase, Uninterruptible Power Supply (UPS) employs Pulse WidthModulation (PWM) and is controlled by a 16-bit micro-controller, to provide reliable,sophisticated protection for every type of line fluctuation, including interruption of themains (electrical) supply.
Figure 1: UPS Operational Schematic
In case of a power failure, the UPS provides backup power for a specific period of time.
The unit is oriented to operate like module in parallel with similar Gamatronic UPSsystems. The load is shared between the units. The parallel system is the most reliableenergy source for any critical load. If the system uses N+1 UPS units (the redundantparallel system), the output voltage is not interrupted even if one of the units is faulty. Ifthe parallel system is equipped with additional Gamatronic Static Switch unit, the outputvoltage is not interrupted even if more than one UPS is faulty.
The Gamatronic parallel UPS system contains the following features:
Each UPS is equipped with its own battery set
Up to 10 units can be connected in parallel
The system is user-friendly. Its operation is simple and requires no previous technicalknowledge. The UPS operates on-line and once activated, the unit provides voltage of220 V at a stabilized 60 Hz frequency to any practical load.
When backup service is provided (on main line power breakdown), the UPS is poweredby batteries and maintains a constant output voltage supply. The system informs theoperator by means of LED indicators and audible signals of the occurrence of a powerfailure.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
7/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t General Features 3
An LCD display on the UPS front panel provides real-time, current operational statusproviding the user with complete information regarding the operational status of theUPS.
Using an RS232 communications port, similar status information may be viewed on acomputer monitor. Additionally, the system may be connected to a remote location viaa modem and a telephone line.
The unit consists of two major subsystems:
Electronic Cabinet, including all electronic devices: charger, inverter, staticswitch, microprocessor board, panel, etc.
Battery Cabinets, including batteries and circuit breaker.
2.1 Major SubsystemsThe device consists of the following modules:
2.1.1 Rectifier/ChargerThe Rectifier/charger supplies stabilized DC voltage to the device at 216 2V
2.1.2 Batteries
The batteries are connected to the charger output and supply voltage during powerfailures. The batteries are housed in the battery cabinets. The UPS include n internal2-pole Battery circuit breaker as shown in figure 1.
2.1.3 Inverter
The inverter receives a DC voltage from the charger or batteries and supplies aregulated, frequency-stabilized, AC voltage (power). The inverter incorporates an IGBTtransistorized bridge; driver, (PC968 board), an L-C filter circuit, isolated outputtransformer circuit, current transformer, PC906 board, and a PC801 control board.
2.1.4 Static Switch
In case the inverter can't supply the load with the correct voltage (i.e. because ofoverload, inrush current on connecting the load, inverter malfunction, etc.), theST.SW/Bypass automatically transfers the load from the inverter to the mains withoutvoltage interruption or disturbance. When the UPS is in BYPASS mode, the load draws
power directly from the mains, bypassing the inverter. The ST.SW automaticallyswitches the load back to the inverter when inverter's output voltage returns to normal.
The inverter is synchronized with the mains in both frequency and phase to ensurecorrect operation of the static switch. The static switch includes PC690/PC920 boardsand RA101 - RA103 contactors.
2.1.5 Control System
The control system performs the following functions:
a. Tests input, bypass, inverter, battery voltage, output current, input/output
signal frequency, and temperature.b. Controls the inverter and the bypass contactorRA101and manages
the static switch and charger voltage during battery tests.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
8/44
Gamatronic Electronic Industries Ltd.
4 General Features PS 3:1, 1030 kVA, 220 Vac ou t
c. Controls the ALARM interface.
d. Reads the panel keyboard and sends messages to the front panel LCDdisplay.
e. Communicates with devices via the RS232 interface.
The control system includes the PC801 control board, PC075 panel board, PC873power supply, current, and temperature sensors. Measured voltages and currents are
connected to the control board via the PC800 interface board.
2.2 Control PanelThe UPS is equipped with an LCD-display and touch pad control panel that enables theuser to effectively manage the UPS. Once the UPS is installed, the control panelserves as the users primary interface with the system. Messages, warnings and errorconditions are relayed to the user through the control panels LCD display and throughaudible alarms.
Figure 2: Control panel on smaller units (PC074)
Figure 3: Control panel on medium-sized units (PC075)
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
9/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t General Features 5
Figure 4: Control panel on the larger units (PC085)
2.3 Power On Self TestsThe UPS automatically performs a series of diagnostic tests when initially powered on.
2.4 MeasurementThe user can receive real-time information regarding the units operation and conditionsimply by pressing the appropriate status buttonthe real-time results are displayed onthe front LCD panel. A sample display follows.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
10/44
Gamatronic Electronic Industries Ltd.
6 General Features PS 3:1, 1030 kVA, 220 Vac ou t
2.5 Real-TimeThe system includes a real-time clock and calendar that sequentially manage the logfile and provides the user with historical data. This information is accessible via theLCD display or, optionally, through the RS-232 communications port.
2.6 CommunicationsThe UPS relays all the measured data and events of the log file through an RS232communications port to a host computer or, using a modem connected to a telephoneline, to a remote location, or via GMAC or GMACi, proprietary SNMP agents, fornetwork access.
2.7 Event LogsThe system compiles a listing of up to 256 extraordinary events of the mains, unit andload during operation. This data is written to the log file and can be accessed easily at
any time through the display panel or computer (optional). This information is veryuseful for maintenance and analyzing performance statistics.
2.8 Ease of UseThe UPS includes an on-line help feature that explains the systems features anddescribes each of the LCD control buttons and indicators.
2.9 Battery CheckThe unit automatically and continuously checks the battery cabinet connection with the
UPS.
2.10 Service ModeThe UPS has a technicians SERVICE MODE that is password protected. Access tothe service mode is only permitted after the technician successfully enters an assignedpassword.
2.11 ConnectionsAll connectionsconnection panel, input, output, and ST. SW are accessed via the
rear panel of the UPS.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
11/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t General Features 7
2.12 Parallel Operation (Option)Each UPS can optionally operate in parallel with similar units as part of a modular UPSsystem. Up to 10 units can be connected in parallel.
Special technical solutions are used to synchronize all the units of the system, toprevent circulation of energy between the UPS units and to isolate the faulty unit from
the common power bus. In addition, an active current sharing circuit changes theoutput voltage of each UPS to provide proportional load sharing between the units.
One of the system's units takes on the function of Master. This unit is synchronized tothe mains power. The other units are Slaves and follow the Master. The function ofMaster is not dedicated to one of the units. Any normally functioning UPS can be theMaster.
2.12.1 Centralized vs. Decentralized Static Switch
The UPS employs a Static Switch for functional over-ride. In parallel mode there are 2possible options of Static Switch operation, centralized and decentralized.
In decentralized mode each UPS includes its own Static Switch which worksindependently. However, if one UPS were to fail, the Static Switch would instantly betriggered and supply the load directly from the mains. This would connect the inverterof the other UPS directly to the mains which could potentially damage the other UPS.Therefore, as illustrated below, (Figure 7A) to avoid such a hazard in decentralizedmode, the Static Switches are synchronized using a 3-wire cable.
For additional security, a second option is available as a centralized Static Switch. Asillustrated below, (Figure 7C) there is only one Static Switch (in a separate housing) forthe entire system. This method goes a long way in increasing system reliability,because the output voltage is constant even if both UPSs are disconnected.
Figure 5: Special parallel communication cable
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
12/44
Gamatronic Electronic Industries Ltd.
8 General Features PS 3:1, 1030 kVA, 220 Vac ou t
Figure 6: Cabling for centralized ST.SW. configuration
Figure 7: Cabling for decentralized ST.SW. configuration
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
13/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Control Panel & Indicators 9
3. CONTROL PANEL & INDICATORS
The control panel serves as an interface between the UPS and the user. Real-timeinformation is displayed visually and audibly. Textual information is presented throughthe LCD display. Messages notifying of alarm conditions are reinforced with an audiblealarm to alert the user of extraordinary circumstances.
The LCD control panel includes function buttonsfor controlling the unit andinformational buttonsfor reporting the status of the UPS.
The console model will be either PC074 (Figure 8), PC075 (Figure 9), or PC085 (. Thetwo consoles have the same functionality; the placement of their buttons and LEDs isslightly different.
In some of the diagrams throughout this user manual only one of the console models isshown, for simplicitys sake.
The control panels of the smaller and medium cabinets (PC074 and PC075) are verysimilar to each other. The control panel of the larger cabinet (PC085) is rather different
in arrangement. Because of this, the PC074 and PC075 panels are explained togetherin section XXXX, and the PC075 panel is described separately in section XXX.
Figure 8: PC074 console
Figure 9: PC075 console
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
14/44
Gamatronic Electronic Industries Ltd.
10 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac ou t
Figure 10: PC085 console
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
15/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Control Panel & Indicators 11
3.1 Function buttons on the smaller cabinets
BUTTON DESCRIPTION
UPS OFF
Pressing the UPS OFF button turns off the UPS. Confirmation of this action is
required. Wait 2 seconds, and confirm it by pressing UPS OFF again.
UPS ON
Pressing the UPS ON button turns on the UPS and sequentially displays the resultsof the start-up diagnostic tests
ALARM OFF
Pressing the ALARM OFF button silences the alarm that sounds when there is asystem fault. If another fault occurs, the alarm returns to active mode.
Note: The ALARM LED remains lit until the problem is resolved to notify usersabout the continued existence of a system fault.
BATTERY TEST
Pressing the BATTERY TEST button manually initiates a battery test. The unit alsocontinuously checks the battery cabinet connection with the UPS. Battery checksare automatically performed at the following times:
Upon start-up
Every 200 hours of accumulated operating time
After battery cabinet reconnection (following a disconnection)
INV
Pressing the INV button connects the inverter to the output, manually taking theUPS out of BYPASS mode.
Note: There is no display associated with this action.
B/P
Pressing the B/P button connects the mains to the output, putting the unit intoBYPASS mode. The unit requires confirmation of this action. Wait approximately 2seconds, and confirm the selection by pressing the B/P button a second time.
3.2 Information ButtonsThe UPS continually monitors its operational status. The user can display real-timeinformation about this status by pressing the appropriate information button. If an alarm
is triggered, the information buttons (except for LOG and ?) display information forapproximately 10 seconds, after which the LCD display reverts to the default STATUSdisplay.
The UPS maintains an event history in its log. The log can be accessed by pressing theLOG button or, alternatively, by a computer through the optional RS232 connection orat a remote location via modem communications.
Where appropriate, the LCD display provides information per R, S, and T phase and forboth voltage and current.
Sample LCD displays are presented below.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
16/44
Gamatronic Electronic Industries Ltd.
12 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac ou t
IN (Input)
Press the IN button to display theunits input voltage.
NOTE: Input current current display is
available as an option.
B/P (Bypass)
Press the B/P button to display theunits bypass voltage and current.
INV (Inverter)
Press the INV button to display theunit's inverter voltage and current.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
17/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Control Panel & Indicators 13
OUT (Output)
Press the OUT button to display theunits output voltage and current.
FREQ (Frequency)
Press the FREQ button to display theunits output and bypass frequency.
The operating inverter frequency is determined by the bypass frequency when operatingnormally. Otherwise, the inverter frequency is determined by the quartz oscillator and
should be set at 50/60 Hz.
BATT (Battery)
Press the BATT buttonto display the battery voltage.
Note: Battery current display is also
available as an option
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
18/44
Gamatronic Electronic Industries Ltd.
14 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac ou t
TIME
Press the TIME button to display theunits current day/month (DD/MM), andcurrent time (HH:MM:SS).
STAT (Status)
Press the STAT button to display theunits status and accumulated workingtime (HHHHH:MM:SS).
For status and fault analysis, see
System Fault Diagnostics on page 23.
Note: This is the UPSs default display.
TEMP (Temperature)Press the TEMP button to display thestatus of the unit's heatsinktemperature.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
19/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Control Panel & Indicators 15
3.3 The Control Panel on the Larger CabinetThe control panel has 6 function buttonsfor controlling the unit and 12informationbuttonsfor reporting the status of the UPS.
Figure 11: Control panel on the larger cabinet
3.3.1 Function Buttons on the Larger Cabinet
BUTTON DESCRIPTION
UPS ON/OFF
When the UPS is OFF, pressing the UPS ON/OFF button turns on the UPS andsequentially displays the results of the start-up diagnostic tests
When the UPS is ON, pressing the UPS ON/OFF button turns off the UPS.Confirmation of this action is required. Wait 2 seconds, and confirm it by pressingUPS OFF again.
BATT
TEST
BATTERY TEST
Pressing the BATTERY TEST button manually initiates a battery test. The unit alsocontinuously checks the battery cabinet connection with the UPS. Battery checksare automatically performed at the following times:
Upon start-up
Every 200 hours of accumulated operating time
After battery cabinet reconnection (following a disconnection)
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
20/44
Gamatronic Electronic Industries Ltd.
16 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac ou t
B/P
INV
B/P INV
When the UPS is in Invertermode, pressing the B/P INV button connects themains to the output, putting the unit into Bypassmode. The unit requiresconfirmation of this action. Wait approximately 2 seconds, and confirm the selectionby pressing the B/P INVbutton a second time.
When the UPS is in Bypassmode, pressing the B/P INV button connects theinverter to the output, manually taking the UPS out of Bypass mode.
Note: There is no display associated with this action.
ALARM OFF
Pressing the ALARM OFF button silences the alarm that sounds when there is asystem fault. If another fault occurs, the alarm returns to active mode.
Note: The ALARM LED remains lit until the problem is resolved to notify usersabout the continued existence of a system fault.
3.3.2 Information Buttons on the Larger Cabinet
The UPS continually monitors its operational status. The user can display real-timeinformation about this status by pressing the appropriate information button. If an alarmis triggered, the information buttons (except for LOG and ?) display information forapproximately 10 seconds, after which the LCD display reverts to the default STATUSdisplay.
The UPS maintains an event history in its log. The log can be accessed by pressing theLOG button or, alternatively, by a computer using the optional RS232 connection, orfrom a remote location via a modem.
Where appropriate, the LCD display provides information for the R, S, and T phasesand for voltage and current.
Sample LCD displays are presented below.
IN (Input)
Press the IN button to displaythe units Input Voltage.
NOTE: Input current current
display is available as an
option.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
21/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Control Panel & Indicators 17
B/P (Bypass)
Press the B/P button to displaythe units bypass voltage andcurrent.
INV (Inverter)
Press the INV button to displaythe unit's Inverter Voltage and
Current.
OUT (Output)
Press the OUT button to displaythe units Output Voltage andCurrent.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
22/44
Gamatronic Electronic Industries Ltd.
18 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac ou t
FREQ (Frequency)
Press the FREQ button todisplay the units Bypass andInverter Frequency.
The operating inverter frequency is determined by the bypass frequency when operatingnormally. Otherwise, the inverter frequency is determined by the quartz oscillator and shouldbe set at 50/60 Hz.
BATT (Battery)
Press the BATT buttonto display the battery voltage.
Note: Battery current display is
also available as an option
TIME
Press the TIME button todisplay the units currentday/month (DD/MM), andcurrent time (HH:MM:SS).
To set the proper time or dateuse the SET button, describedon page 21.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
23/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Control Panel & Indicators 19
STAT (Status)
Press the STAT button todisplay the units status andaccumulated working time(HHHHH:MM:SS).
For status and fault analysis,
see System Fault Diagnosticson page 23.
Note: This is the default display.
TEMP (Temperature)
Press the TEMP button to
display the status of the unit'sthermosensors.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
24/44
Gamatronic Electronic Industries Ltd.
20 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac ou t
3.4 The LOG, SET, and HELP Buttons for All Models
LOG
Pressing the LOG button displays the units event log, which contains information aboutthe last extraordinary events of the mains, unit and load that occurred while the unit was
operating.
The log contains the 256 most recent events, each of which can be perused using the uparrow
Each log occupies 2 windows. The first window to appear is the first part of the most
recent fault. Press the down arrow to view the second window of the event.
To view the 1stwindow of a previous event, press the up arrow ;pressing the uparrow once again will show the 1stwindow of the event previous to that. The down arrow
will show the second window. See the cycle in Figure 12below.
Figure 12: LOG Messages Structure
To view the contents of the log:
Press the LOG button to enter LOGmode.
Press the arrow buttons to scrollthrough the information recorded inthe log.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
25/44
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
26/44
Gamatronic Electronic Industries Ltd.
22 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac ou t
The following messages are presented:
Model type: True on-line UPS, model name etc.)
Serial number
Nominal power
Number of phases in and out
Nominal input and output voltage between phase and neutral Voltage range of input and bypass
Nominal output current per phase
Nominal output frequency
Frequency tracking range when the inverter is synchronized to thebypass
Number of batteries connected in series
Nominal capacity of each battery (for use in calculating backup durationwhere the battery current meter option is installed)
DC shutdown voltage in battery discharge mode Bypass: YES for option with bypass, NO for option without bypass
Rectifier: YES for UPS, NO for DC/AC inverter
Distance shutdown: YES if EPO and shutdown via interface alarm andRS232 are supported, NO if shutdown is inhibited
Par. Operation: YES for parallel UPS, NO for stand-alone UPS
Load LED bar: Triple for panel with 3 LED bars, Single for one integralbar
Input current meter: YES for specified option, NO as standard
Battery current meter: YES for specified option, NO as standard Date of manufacture: Format DD/MM/YY
Date of last battery installation: Format DD/MM/YY
Software version number
To quit the help, press the ? button once again.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
27/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Control Panel & Indicators 23
3.4.1 System Fault Diagnostics
Select the STAT button and press the down arrow . The display will show 2 bytesrepresenting the FAULT (see LOG on page 20) followed by two bytes (each of 8 bits)are now on display, each representing the STATEand the INSTRUCTION.
To use the hexadecimal indicators, make a note of the bit representations.
The STATEbyte indications are as follows:
Bit 0: UPS power 1 = ON, 0 = OFFBit 1: Load supply 1 = On bypass, 0 = On inverterBit 3: Audible alarm 1 = Disabled, 0 = EnabledBit 4: Load transfer 1 = In progress, 0 = PendingBit 5: Battery check 1 = In progress, 0 = Pending
The INSTRUCTION byte indications are as follows:
Bit 0: UPS power 1 = ON, 0 = OFF
Bit 1: Load supply 1 = On bypass, 0 = On inverterBit 5: Battery check 1 = In progress, 0 = Pending
To view fault condition details, press the down arrow , and 9 bytes are displayed onthe panel:Byte 1 shows input diagnostics. Indications are as follows:
Bit 0: 1 = Fault is in phase RBit 1: 1 = Fault is in phase SBit 3: 1 = Fault is in phase TBit 7: 1 = Fault exists
Byte 2 shows the result of bypass symptoms analysis.Byte 3 shows result of inverter symptoms analysis.
Byte 4 shows output voltage diagnostics. Indications are as per byte 1.
Byte 5 shows DC voltage diagnostics. Indications are as follows:
Bit 0: 1 = Battery is currently dischargingBit 1: 1 = Battery is dischargedBit 2: 1 = Battery is disconnectedBit 3: 1 = Battery check failedBit 4: 1 = Excessive current difference in battery sets. (Option)
Bit 6: 1 = Rectifier failureBit 7: 1 = Fault exists
Byte 6 shows measured temperature diagnostics. Indications are as follows:
Bit 0: 1 = Shutdown limit exceededBit 1: 1 = Alarm limit exceededBit 2: 1 = Fault detected by bi-metal temperature sensorBit 7: 1 = Fault exists
Byte 7 shows bypass frequency diagnostics:
Bit 0: 1 = Bypass frequency incorrect
Byte 8 shows over-current diagnostics. Indications are as follows:
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
28/44
Gamatronic Electronic Industries Ltd.
24 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac ou t
Bit 0: 1 = Over-current detected in phase RBit 1: 1 = Over-current detected in phase SBit 2: 1 = Over-current detected in phase TBit 7: 1 = Fault exists
Byte 9 shows load transferring diagnostics. Indications are as follows:
Bit 0: 1 = Transferring started
Bit 1: 1 = Inverter is OFFBit 2: 1 = Inverter restartingBit 3: 1 = Inverter under diagnosisBit 4: 1 = Switching to inverter SRSW SCR is ONBit 5: 1 = Switching to inverter SRSW SCR is OFFBit 6: 1 = System in wait state
To view the active current sharing status, press the down arrow .
Figure 13: Active Current Sharing
I and Ia in the results of active average current measurements on phases R, S and Tusing a half-scale offset. Zero current is presented as 128. With positive current thisvalue increases, with negative current, this value decreases.
To view the register used for inverter voltage correction, press the down arrow .
Figure 14: Voltage Correction
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
29/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Control Panel & Indicators 25
3.5 LED IndicatorsLED Indicators provide information regarding the status or operation at a glance of theUPS. They are color coded so that the user can easily and quickly identify areas forconcernRed indicates a fault or abnormal status (usually associated with an audiblealarm),
Figure 15: LED indicators on the PC074 and PC075 cabinets
Figure 16: LED indicators on the PC085 cabinet
Table 2: LED indicators and their meaning
INDICATOR INDICATION WHEN ONDEFAULTSTATUS
BYPASS Bypass input voltage is normal. Green
B/P Load connected to bypass. Red
OVERLOAD The UPS is overloaded. Red
BATTERY TEST Battery not normal. Red
SYNC Inverter is synchronized with bypass. Green
CHARGERRectifier/charger is operatingnormally.
Green
INVERTER Inverter is operating normally. Green
INV. Load is on the inverter. Green
LOAD LEVEL Load level. Green
LOAD LEVEL Overload condition (load > 100 %). Red
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
30/44
Gamatronic Electronic Industries Ltd.
26 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac ou t
3.6 Terminal Connections
Figure 17: Terminal connections on the stand-alone model
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
31/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Operating the PS Series UPS 27
4. OPERATING THE PS SERIES UPS
4.1 Turning the UPS ON
To turn the UPS on:
Turn ON the CHARGER and ST. SW circuit breakers.
WAIT 1 minute and then turn ON the BATTERY circuitbreaker.
The UPS performs a self-test (that takes approximatelyone minute). Verify that the UPS OFF message isdisplayed on the LCD after the test is completed.
"UPS off"
Press the UPS ON button.The message UPS ONPLEASE WAIT appears as the unit turns on.
When the UPS is completely turned on:
The UPS OK message is displayed"UPS OK"
TIME indicates how long the Inverter isworking.
Only green display lights are lit.Turn on the OUTPUT circuit breaker
"TIME XXXXXXXX"
4.2 Turning the UPS OFF
To turn the UPS off:
Turn off all the loads connected to the UPS.
Press the UPS OFF button on the display panel.
Turn off all the circuit breakers.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
32/44
Gamatronic Electronic Industries Ltd.
28 Operating the PS Series UPS PS 3:1, 1030 kVA, 220 Vac ou t
4.3 Activating MAINTENANCE BYPASS (Optional)MAINTENANCE BYPASS allows the parallel UPS system to be shut down for servicingwithout the users being affected.
To activate the MAINTENANCE BYPASS mode:
1. Verify that the SYNC and BYPASS lights of the Static Switch unit are lit. (If theyare not lit, the load cant go into BYPASS mode.)
2. Press the INV/BYP button to put the load in BYPASS mode.
3. Verify that the LOAD ON BYP light is lit.
4. Turn ON the MAINTENANCE BYPASS circuit breaker.
5. Turn OFF the OUTPUT circuit breaker of the UPS units.
6. Press twice on the UPS OFF button on the display panel.
7. Turn OFF the ST.SW, CHARGER and BATTERY circuit breakers.
If there are no lights lit on the display panel it is possible to service the UPS.
Note:
1. The MAINTENANCE BYPASS mode cannot be serviced when it isactivated.
2. Do not turn the ST.SW off or on if there is galvanic insulation on theST.SW.
3. Any special, non-standard instructions are on the UPS by the circuitbreakers.
4.4 Deactivating MAINTENANCE BYPASS(Optional)
To deactivate MAINTENANCE BYPASS and retransfer the load to the UPS units:
Operate all the UPS units in the parallel system. After all the unit comes into normaloperation mode, lift up OUTPUT circuit breakers.
Pull down the MAINTENANCE BYPASS switch.
Press IVV/BYP switch of the Static Switch unit and verify that LED LOAD ON INV is lit.
WARNING
NEVER lift the MAINTENANCE BYPASS circuit breaker without first putting
the UPS in BYPASS mode (the red BYPASS light must be lit).
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
33/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Operating the PS Series UPS 29
4.5 Setting the Real-Time ClockThe real time clock is composed of the dateand timefields and may be set by theuser. The date field contains three subfields (DD/MM/YY) and the time field containstwo subfields (HH:MM).
To set the real time clock: Press the TIME button to enter the time mode.
The normal TIME display is shown on the LCD panel.
Press the SET button to initiate setting mode.The year is presented as 2 digits.
Press the SET button to increase the value.
Press the up arrow to continue with the settings, setting month [1-12], day[1-31], hour [0-23] and minutes [0-59].
The UPS is connected to a computer or a modem using a shielded cable, with anRS232-type 9-pin female connector. Maximum allowed cable length is 15 meters.
There are two types of UPS connections:
Directly to a host computer via dedicated software.
Remote monitor through a SNMP/WEB management programs forcommunication with a computer network (optional).
Figure 18: Local-direct connection for monitoring and control
4.6 RS232 InterfaceThe UPS supports standard UPS protocol. Full information about the status of the UPS,the value of its parameters, and the memory events log is displayed on a user-friendlygraphic interface. The graphic interface also allows the user to use the host computerto execute a set of instructions for the UPS that includes shutdown, restart, batterycheck, etc.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
34/44
Gamatronic Electronic Industries Ltd.
30 Operating the PS Series UPS PS 3:1, 1030 kVA, 220 Vac ou t
Communication parameters:
2400 Baud rate
No parity
1 stop bit
No flow control15
69
RxTxCOM
RS232
SIGNAL UPS
RD 2
TD 3
GND 5
Figure 19: RS232 Connector Pin Assignment
4.7 The Alarm InterfaceThe following diagram describes the alarm interface.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
35/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Operating the PS Series UPS 31
EXT. SIDE
LOW BATTERY SIGNALNORMALLY OPEN
UPS SIDE
NORMALLY OPENLINE FAIL SIGNAL
5
3
LINE FAIL SIGNAL
NORMALLY CLOSED
4
6
MAXIMUM24VDC/1A
COMMON
ISOLATED FROM GROUND
LINE FAIL OUTPUT SIGNAL
(TYP. +/- 3mA)
GROUND
NORMALLY OPEN
GENERAL FAULTMAX. 24VDC/1A
LINE
-9V
1
9
(INPUT RESISTANCE TYP, 5Kohm)VIA AN EXTERNAL PULSE
UPS SHUTDOWN
OUTPUT CIRCUIT SCHEMATIC DIAGRAM
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
36/44
Gamatronic Electronic Industries Ltd.
32 Operating the PS Series UPS PS 3:1, 1030 kVA, 220 Vac ou t
4.8 Remote Monitor Box (Optional)The remote monitor box can be located a maximum distance of 50m from the UPS. Itis directly connected to the UPS with a 4-wire cable connected to the REMOTEMONITOR interface of the UPS.
The control panel on the front of the monitor box displays audio and visual information
about the condition of the UPS, the mains, and the load. It also contains the followingfunction buttons:
UPS ON
UPS OFF
INV
ALARM OFF
BATTERY TEST
B/P
4.8.1 Connect ing the Monitor Box to the UPS MS/MP
Attach the back of the monitor box to the wall.
The UPS PC908 card in the monitor box is connected to the PC021 card on the rearpanel of the UPS with a 4-wire cable connected to the appropriate 1-4 Pin male orfemale DB9 connector terminal in the UPS row of terminals.
The cable is attached to the side of the monitor box with two screws.
DB9
Row of Terminals
The measurements of the Monitor box are: Length - 265mm, height -135 mm, anddistance between the screws on the back of the box - 200mm.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
37/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Troubleshooting 33
5. TROUBLESHOOTING
If the unit stops operating normally, a red alarm light (ALARM) flashes, a warning beepsounds, and one of the following emergency messages appears on the LCD:
MESSAGE STATE COMMENTS
BATTERY LOW Battery is low
INPUT FAULT
1. Input voltage is toolow.
2. Input voltage is toohigh.
3. No input voltage
Corrects itself automatically when theinput voltage stabilizes or returns.
B/P FAULT
1. Bypass voltage istoo low.
2. Bypass voltage istoo high.
3. No bypass voltage
Corrects itself automatically when thebypass voltage stabilizes or returns.
OVERLOAD Overload
The unit goes to bypass and stays thatway as long as there is an overload. Theload transfers from bypass to inverterwhen the load is corrected.
INVERTER FAULT Malfunctioning inverterMake up to 7 attempts to reconnect to theinverter.
OVERTEMPERATURE
Over temperature
Over 90 paralyzes the inverters actionand transfers the load to bypass. It returnsautomatically to normal operation onlyafter the temperature goes below 55.
BATT. NOTCONNECT
Battery is not connectedCheck the status of the battery switch andthe connections to the batteries.
BATTERY UNDERLOAD
Power failure. Inverteroperating on batteries.
A slow beep indicates that the battery isstarting to discharge.
A fast beep and a TEST BATT lightindicates that the battery has almostfinished discharging.
BYPASS FREQ.FAULT
The frequency bypassexceeds the allowablelimits.
Works on an independent frequency of theinverter and will synchronize back whenthe frequency will return to normal.
FAULT CONDITIONSERVICE REQUIRED
Self-test has a negativeresult
Call service technician
RECTIFIER FAULT DC voltage is faulty Call service technician
Note: The following procedures are relevant in cases where the unit is not operating
normally and there are no LCD display panel messages.
These procedures are to be performed BY A TRAINED TECHNICIAN ONLY.
In the event that the unit has stopped operating in a normal manner, and the displaypanel is not functioning, the technician should perform the following:
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
38/44
Gamatronic Electronic Industries Ltd.
34 Troubleshooting PS 3:1, 1030 kVA, 220 Vac ou t
Figure 20: Troubleshooting flowchart
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
39/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Troubleshooting 35
BOARDCHASSIS CHECK
POINTVOLTAGE
PC 801 TP10 5V 5%
PC 800 P13/1 12V 5%
PC 800 P13/2 12V 20%
Figure 21: PC Board Check Points & Voltage Ranges
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
40/44
Gamatronic Electronic Industries Ltd.
36 Site Preparation PS 3:1, 1030 kVA, 220 Vac ou t
6. SITE PREPARATION
6.1 Site Preparation and ConsiderationsThe UPS is designed to operate under varied environmental conditions.
To insure long-term, trouble-free operation:
Select a well-ventilated and dust-free site that is conveniently located to both theelectrical closet and the desired load.
Make sure that there is a minimum of 20 cm. clearance.
Make sure that the air vents are not obstructed.
Make sure that the room temperature does not exceed 40oC. UPS operation and
battery charging generates heat. Battery life can be extended by insuring a cooloperating site.
Place electrical equipment (load, computer monitor, etc.) at least 1 meter from theUPS.
6.2 AccessibilityAll access to the UPS is accomplished through the rear panel of the UPS.
All connectionsconnection panel, input, output, and STSW are accessed via therear panel of the UPS.
6.3 Circui t BreakersThe UPS has circuit breakers that are accessible through the rear of the unit.
Charger
Static Switch
Output
Battery Switch (optional it may be located on the battery cabinet)
The UPS also has a Maintenance Bypass switch. This switch must only be operatedby qualified technical personnel according to the special procedures described in 4.3and 4.4.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
41/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Installation 37
7. INSTALLATION
7.1 Installation ProcedureTo prepare the UPS for the initial power-up:
1. Open the front access door using a flathead screwdriver to turn the lock.2. Remove the lower access panel.
3. Turn OFF ALLof the circuit breaker switches:
RECTIFIER
BYPASS
OUTPUT
BATTERY (optional)
MAINTENANCE BYPASS (optional)
4. Connect the batteries to the UPS.
5. Connect the unit to the mains (electrical) cabinet with the grades of wire shownin the following table. If local or national codes are stricter, follow those codes.
Table 3: Minimum recommended wire grades (cross-sectional area)
FOR PS-SP 3-1, 3X220 VAC INPUT, 220 VAC OUTPUT, 192 VDC
UPSRECTIFIERAC INPUT
BYPASSAC INPUT
OUTPUT BATTERY
10 kVA 6 mm2 10 mm
2 10 mm
2 16 mm
2
15 kVA 10 mm2 16 mm2 16 mm2 25 mm2
20 kVA 16 mm2 25 mm2 25 mm2 35 mm2
30 kVA 25 mm2 35 mm
2 35 mm
2 50 mm
2
6. Turn ON the CHARGER and ST.SW circuit breakers of thefirst UPS in the parallel system.
7. The UPS performs a self-test (that takes approximately oneminute). Verify that the UPS OFF message is displayed onthe LCD display after the test is completed.
"UPS OFF"
8. Press UPS ON. The UPS is ready for use and begins charging the batteries.
9. After the UPS comes into normal operation:
a. Lift up the OUTPUT circuit breaker
b. Measure the AC voltage between the UPS and BYPASS phaseterminals of the Static Switch unit.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
42/44
Gamatronic Electronic Industries Ltd.
38 Installation PS 3:1, 1030 kVA, 220 Vac ou t
c. Verify that the voltage between the terminals is no more than 20V.
10. Measure AC voltage between UPS phase- neutral terminals (V1)
11. Pull down OUTPUT circuit breaker of the UPS and:
a. Operate the next UPS in the parallel system. Repeat all checks(Steps 6-11) and verify that output voltage V2 does not differ from V1by more than 4V.
b. Repeat the check (Step 12) for all the UPS units in the system.
c. Observe the LCD messages in STAT indication mode. Verify that oneof the UPS is the Master and others are Slaves.
12. Lift up the OUTPUT circuit breakers.
13. Measure the current between the UPS units in no load condition (circulationcurrent).
14. Verify that the current between each two UPS units is less than 0.1*Inom (forexample, 7 A for 20 kVA). If this value is exceeded, regulate the current withpotentiometer R102 of PC871 PWM board.
15. Press the INV/BYP key of the Static Switch unit and verify that transfer from UPSto mains power and vice-versa is performed normally.
16. Lift up the OUTPUT circuit breaker of the Static Switch unit.
17. Verify that load is shared between the UPS units. (The difference between outputcurrents should be no more than 0.1*Inom. Adjust R102 of PC871 if necessary.
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
43/44
Gamatronic Electronic Industries Ltd.
PS 3:1, 1030 kVA, 220 Vac ou t Technical specifications 39
8. TECHNICAL SPECIFICATIONS
PS 3:1
AC INPUT (Recti fier/charger) 10 kVA 15 kVA 20 kVA 30 kVA
Voltage (V) 3 X 220 Vac (3Ph +G)
Voltage range +10 % -15 %
Frequency 57-63 Hz
Power walk-in 12 sec.
Protection Circuit breaker, RFI filter
Power Factor 0.80
BYPASS AC INPUT 220 Vac / 60 Hz 2-Phase
OUTPUT
Voltage (V) 220 Vac / 60 Hz, Phase-Common
Power(kVA)(kW)
108
1512
2016
3024
Efficiency ac-ac
at 100% load (%)at 50% Load (%)
89
88
Heat dissipation (W) at full load
(1W = 3.4 BTU)989 1483 1978 2966
Inverter efficiency at 100% load (%) 92
Regulation 2 %
Frequency tracking range 1, 2 3 Hz., selectable
Slew rate 1 Hz/Sec.
Overload:
at 125%at 150%at 1000%
10 Minutes30 Seconds
1 Cycle
Load P.F. 0.8
Waveform Sinusoidal
Crest factor 3:1
Total harmonic distortion (THD) Less than 2 % (at linear load)
Protection Overload & short circuit
Dynamic response to 100% loadchange 2 %
Transition time: to and from line Less than 0.5 msec.
Rejection ratio More than 100 dB
Nominal DC voltage 192 Vdc
-
7/24/2019 PS-SP 10-30kVA 3-1 With Bypass Isolation Transformer (Option)
44/44
Gamatronic Electronic Industries Ltd.
COMMUNICATION OPTIONS
RS232 interface SNMP
Alarm interface Shutdown software
Remote indication panel Optional
LCD DATA
Input VoltageOutput & inverter Voltage, Current, Frequency
Bypass Voltage & frequency
Batteries Voltage & Current
Temperature Heat sink
Log (events memory) 256 lost events
ENVIRONMENT & OTHER
Ambient temperature:
OperatingStorage
-10 to 40 C-20 to 60 C
Relative humidity 95 % max., non-condensingAltitude 1500 m w/o derating
UPS Standard
General & SafetyEMCDesign
EN50091-1EN50091-2
ENV50091-3
MTBF (hours)
With ST. SwitchWithout ST. Switch
250,000100,000
Audible noise (dB) at 1.5m 54
PHYSICALSize (cm)
Height 75 95 95 130
Width 24 40 40 55
Depth 80 83.5 83.5 80
Weight (kg)
W/O batteries 200 220 240 275