9
GSW360V Main Features Frequency Hz 50 Voltage V 400 Power factor cos ϕ 0.8 Phase and connection 3 Power Rating Standby power LTP kVA 357.64 Standby power LTP kW 286.11 Prime power PRP kVA 326.08 Prime power PRP kW 260.86 Ratings definition (According to standard ISO8528 1:2005) PRP - Prime Power: It is defined as being the maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load when operated for an unlimited number of hours per year under the agreed operating conditions with the maintenance intervals and procedures being carried out as prescribed by the manufacturer. The permissible average power output over 24 h of operation shall not exceed 70 % of the prime power. LTP - Limited-Time running Power: It is defined as the maximum power available, under the agreed operating conditions, for which the generating set is capable of delivering for up to 500 h of operation per year (whose no more than 300 for continuative use) with the maintenance intervals and procedures being carried out as prescribed by the manufacturers. No overload capability is available.

Transcript of Product sheet extended - yats.hk · Mounted on the genset, complete with digital control unit...

GSW360V

Main Features

Frequency Hz 50

Voltage V 400

Power factor cos ϕ 0.8

Phase and connection 3

Power Rating

Standby power LTP kVA 357.64

Standby power LTP kW 286.11

Prime power PRP kVA 326.08

Prime power PRP kW 260.86

Ratings definition (According to standard ISO8528 1:2005) PRP - Prime Power: It is defined as being the maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load when operated for an unlimited number of hours per year under the agreed operating conditions with the maintenance intervals and procedures being carried out as prescribed by the manufacturer. The permissible average power output over 24 h of operation shall not exceed 70 % of the prime power. LTP - Limited-Time running Power: It is defined as the maximum power available, under the agreed operating conditions, for which the generating set is capable of delivering for up to 500 h of operation per year (whose no more than 300 for continuative use) with the maintenance intervals and procedures being carried out as prescribed by the manufacturers. No overload capability is available.

Engine specifications

Engine manufacturer Volvo

Model TAD1351GE

Version 50 Hz

[50Hz] Exhaust emission level Stage IIIA

Engine cooling system Water

Nr. of cylinder and disposition 6 in line

Displacement cm³ 12780

Aspiration Turbocharged intercooled

Speed governor Electronic

Prime gross power PRP kW 286

Maximum gross power LTP kW 313

Oil capacity l 30

Lube oil consumption @ PRP (max) % 0.10

Coolant capacity l 23.8

Fuel Diesel

Specific fuel consumption @ 75% PRP g/kWh 204

Specific fuel consumption @ PRP g/kWh 200

Starting system Electric

Starting engine capability kW 7

Electric circuit V 24

ENGINE EQUIPMENT

StandardsThe engine performance corresponds to ISO 3046, BS 5514 and DIN 6271. Power output guaranteed within 0 to +2% att rated ambient conditions at delivery. Ratings are based on ISO 8528. Engine speed governing in accordance with ISO 3046/IV, class A1 and ISO 8528-5 class G3

Engine and block• Optimized cast iron cylinder block with optimum distribution of forces• Wet, replaceable cylinder liners• Crankshaft induction hardened bearing surfaces and fillets with seven bearings for moderate load on main and high-end bearings• Keystone top compression rings for long service life• Replaceable valve guides and valve seats• Tapered connecting rods for increased piston lifetime• Over head camshaft and four valves per cylinder

Fuel system• Electronic unit injectors• Fuel prefilter with water separator and waterin-fuel indicator / alarm• Fine fuel filter with manual feed pump and fuel pressure switch

Lubrication system• Full flow oil cooler• Full flow disposable spin-on oil filter, for extra high filtration• Gear type lubricating oil pump, gear driven by the transmission

Cooling system• Efficient cooling with accurate coolant control through a water distribution duct in the cylinder block. Reliable sleeve thermostat with minimum pressure drop• Belt driven coolant pump with high degree of efficiency

Alternator Specifications

Brand Mecc Alte

Model ECO38-3LN/4

Voltage V 400

Frequency Hz 50

Power factor cos ϕ 0.8

Type Brushless

Poles 4

Voltage regulation system Electronic

Standard AVR DSR

Voltage tolerance % 0.1

Efficiency @ 75% load % 93.7

Class H

IP protection 21

Mechanical structureRobust mechanical structure which permits easy access to the connections and components during routine maintenance check-ups.

Voltage regulatorVoltage regulation with DSR. The digital DSR controls the range of voltage, avoiding any possible trouble that can be made by unskilled personnel. The voltage accuracy is ±1% in static condition with any power factor and with speed variation between 5% and +30% with reference to the rated speed.

Windings / Excitation systemGenerator stator is wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th …) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches. MAUX  (Standard): The MAUX MeccAlte Auxiliary Winding is a separate winding within the main stators that feeds the regulator. This winding enables to take an overload of 300% forced current (short circuit maintenance) for 20 seconds. This is ideal for motor starting requirements.

Insulation / ImpregnationInsulation is of class H standard. Impregnation is made with premium tropicalised epoxy resins by dipping and dripping. High voltage parts are impregnated by vacuum, so the insulation level is always very good. In the high-power models, the stator windings undergo a second insulation process. Grey protection is applied on the main and exciter stator to give enhanced protection.

Reference standardsAlternator manufactured according to , and complies with , the most common specification such as CEI 2-3, IEC 34-1, EN 60034-1, VDE 0530, BS 4999-5000, CAN/CSA-C22.2 No14-95-No100-95.

Genset equipment

BASE FRAME MADE OF WELDED STEEL PROFILE, COMPLETE WITH:

• Anti-vibration mountings properly sized

• Screwed support legs.

PLASTIC FUEL TANK WITH THE FOLLOWING COMPONENT:

• Filler neck

• Air breather (ventilation pipe)

• Minimum fuel level sensor

MANUAL OIL DRAININ PUMP:

• Oil draining facilities

ENGINE COMPLETE WITH:

• Battery

• Liquids (no fuel)

CANOPY:

• Soundproof canopy made up of modular panels, realized with zinced steel as treatment against corrosion and aggressive conditions, properly fixed and sealed allowing a full weatherproof enclosure.• Easy access to the genset for maintenance purposes thanks to: Wide lateral access doors fixed by stainless steel hinges and provided with plastic lockable handles and internal perforated galvanized steel-sheet; Detachable panels, with screws holes protected by rubber tap. • Control panel protection door provided with suitable window and lockable handle. • Lateral air inlet opening properly protected and soundproofed. Exhaust air outlet from the roof, trough wet section protected by proper grid. • Double lifting points frame structure.

SOUNDPROOF:

• Noise attenuation thanks to soundproofing material (rock wool)

• Efficient residential silencer placed inside the canopy

Dimensional data

Length (L) mm 3951

Width (W) mm 1438

Height (H) mm 2085

Dry weight Kg 3671

Fuel tank capacity l 636

Autonomy

Fuel consumption @ 75% PRP l/h 52.41

Fuel consumption @ 100% PRP l/h 68.09

Running time @ 75% PRP h 12.14

Running time @ 100% PRP h 9.34

Noise level

Guaranteed noise level (LWA) dB(A) 97

Noise pressure level @ 7 mt dB(A) 68

Installation data

Total air flow m³/min 413.18

Exhaust gas flow @ PRP m³/min 48.9

Exhaust gas temperature @ LTP °C 480

Data Current

Battery capacity Ah 155

MAX current A 516.22

Circuit breaker A 630

Control panel availability

AUTOMATIC CONTROL PANEL  ACP

MODULAR PARALLEL PANEL  MPP

ACP - Automatic control panel

Mounted on the genset, complete with digital control unit AC03 for monitoring, control and protection of the generating set, protected through door with lockable handle

DIGITAL INSTRUMENTATION (through AC-03)• Generating set voltage (3 phases)• Mains voltage• Generating set frequency • Generating set current (3 phases) • Battery voltage• Power (kVA - kW - kVAr)• Power factor Cos φ• Hours-counter• Engine speed r.p.m.• Fuel level (%) • Engine temperature (depending on model)

COMMANDS AND OTHERS• Four operation modes: OFF - Manual starting - Automatic starting - Automatic test• Pushbutton for forcing Mains contactor or Genset contactor     • Push-buttons: start/stop, fault reset, up/down/page/enter selection• Remote starting availability• DC system disconnection switch• Acoustic alarm• Automatic battery charger• RS232 Communication port• Settable PASSWORD for protection level

PROTECTIONS WITH ALARM• Engine protections: low fuel level, low oil pressure, high engine temperature• Genset protections: under/over voltage, overload, under/over frequency, starting failure, under/over battery voltage

PROTECTIONS WITH SHUTDOWN• Engine protections: low fuel level, low oil pressure, high engine temperature• Genset protection: under/over voltage, overload, under/over battery voltage, battery charger failure• Circuit breaker protection: III poles• Earth Fault included in the control unit

OTHERS PROTECTIONS• Emergency stop button• Panel protected through door with lockable handle

OUT PUT PANEL ACP

Plinth row for connection from ACP to LTS panel.  

Predisposed for remote control optional:  RCG

External Terminal Board (ETB) Standard

Socket kit Optional

MPP - Modular parallel panel

Mounted on the genset, complete with digital control unit InteliVision5 for monitoring, control, protection and load sharing for both single and multiple gen-sets operating in standby or parallel modes (up to 32 gen-sets in island).

DIGITAL INSTRUMENTATION• Mains: voltage, Intensity, Frequency.• Mains kW - kVAr -Power factor Cos f.• Genereting set voltage (3 phases).• Generating set frequency. • Generating set current (3 phases).• Generating set Power (kVA - kW - kVAr).• Generating set Power factor Cos f. • Generating set kWh and kVAh. • Battery voltage.• Hours-counter.• Engine speed r.p.m.• Fuel level (%).• Engine temperature (depending on model).• Oil pressure (depending on model).

COMMAND AND OTHERS• Graphical display 320x240 pixels.• Operation modes: OFF - AMF function - Single Parallel to mains Island application - Single Parallel to Mains AMF application - Mulitple parallel genset Island application. • Pushbutton for forcing Mains Breaker/contactor or Genset Breaker/contactor.     • Push-buttons: start/stop, fault reset, up/down/page/enter selection.• Multiple parallel and Power Management operation with digital load  AVR sharing.• Automatic synchronizing and power control (via speed goveroner or ECU)• Baseload Import/Export and Peak shaving• Voltage and PF control (AVR).• Configurable digital I/O (12/12) and analogue inputs (3).• Integrate PLC programmable functions.• Event-based history (up to 500records).• Selectable measurment range 120/277V and 0-1/0-5A.• Remote starting and Blocking signal availability.  • DC system disconnection switch.• Acoustic alarm.• Automatic battery charger.• 2xRS232/RS485/USB Comuncation ports.• Setable PASSWORD for protection level.

PROTECTION WITH ALARM AND SHUTDOWN• Engine protections: low fuel level, low oil pressure, high engine temperature. • Genset protections: under/over voltage, overload, under/over frequency, starting failure, under/over battery voltage• Others: overcurrent, shortcircuit, reverse power, Earth fault

OTHERS PROTECTION:• Circuit breaker protection: IV poles Motorized.• Emergency stop button.• Panel protected through door with lochetable handle

OUT PUT PANEL MPP

Multi-pin connectors (in and out ) for parallel with other generators

n 2

Connecting cable with 2 connectors multipin (length 10m) n 1

ETB External terminal board  ETB

Supplements:

Only Available when order :

Socket kit

Kit SKB or Kit SKC (for total n. 4 socket) - avaliable for model:  ACP

Individual CB and Earth Fault protection  

3P+N+T 400V 63A n 1

3P+N+T CEE 400V 32A n 1

230V/16A SCHUKO n 1

With version SKB:  

3P+N+T CEE 400V 16A n 1

With version SKC:  

400V/125A 3P+N+T CEE n 1

GENSET EQUIPMENT

LPT - Leak Proof Tray  

AFP - Automatic Fuel Pump ACP MPP

KRT- Kit Rental for HEI gensets which includes: 3-way fuel valve, battery switch

Extended Fuel Tank

Fuel tank capacity l 2330

Length (Genset) (L) mm 3976

Width (Genset) (W) mm 1618

Height (Genset) (H) mm 2421

ENGINE SUPPLEMENTS

PHS - Coolant Pre-Heating System - available for models: ACP MPP

Accessories

Items available as accessory equipment  

LTS - LOAD TRANSFER SWITCH - Accessories ACP

Automatic under-load change-over (AC22, AC23) from and to any of positions “1”, “0”, “2” both electrical and manual (emergency change-over), transfer function with direct transition from position “1” to position “2” and vice versa.• Safety: locking by padlock preventing any electrical or manual operation, key lock for the selection of electrical or manual operation.- Quick operating time from pos. “1” to “2” and vice versa. • Easy and fast electrical connections by means of terminal blocks of quick connection type.• Conformity to standards: IEC 60947-1 IEC 60947-3, CEI EN 60947-1 / CEI EN 60947-3IEC 439-1, CEI EN 60439-1IEC 204-1, CEI EN 60204-1, VDE 0660 Teil 107

NOMINAL CURRENT & DIMENSIONS PANEL LTS (standard*)

Nominal Current A 630

Width (W) mm 1000

Height (H) mm 800

Depth (D) mm 400

* = Available electrical power more  

Printed on 10/11/2015 (ID 1308)

©2012 | PR INDUSTRIAL s.r.l. | All rights reserved | Image shown may not reflect actual package. Specifications subject to change without notice | ENERGY GENERATION is registered trademarks of PR INDUSTRIAL s.r.l. Other company, product or service names may be trademarks or service marks of others. RevA (06/2012).