MODCON® PREMIUM PLUG SERIES · A6M (CAT6A) O = Options: Di˝erent Wire Diameter Angled Latch or...
Transcript of MODCON® PREMIUM PLUG SERIES · A6M (CAT6A) O = Options: Di˝erent Wire Diameter Angled Latch or...
Technical Spec.: Insulation Resistance: 1.000 MΩ Contact Resistance: 20mΩ Current/Voltage: 1,5A / 150 VWithstanding Voltage: 1.000 V AC/min Durability: Minimum 750 Mating Cycles Selective Gold Plating: 30 μ” or 50 μ” Contacts: Phosphor Bronze w Au Plating on Ni Housing: Polycarbonate UL94-V0 / UL94-V2 Operation Temperature: -40°C .... +85°C PLUG COMPLIES WITH TIA-1096-A REQUIREMENTS Conform to ANSI/TIA/EIA-568-B.2-10, ISO/IEC11801and CENELEC EN50173 for Category 6A/Class EA
Key Features: Excellent electrical performance Single-Step termination process – shield and contacts are crimped in 1 operation 360 degree shield termination Direct shield connection from cable to connector Management bar for ease of assembly Smooth gold plated contacts Contact design which allows solid or stranded conductor termination slim design for use in high density applications capability for eld termination hoods and color key rings in various colors
PART NUMBERS: PX8CY O-(G)X = U(unshielded) / S(shielded) C = Number of Contacts Y = IND (Industrial/Pro�net) A6M (CAT6A) O = Options: Di�erent Wire Diameter Angled Latch or Straight Latch Opening Angle of Strain Relief
G = Gold Plating; standard is 30μ“ - add G50 for 50 μ“ ASSEMBLY TOOLING
INELCO’s modcon® modular connectors are a part of one of the most advanced connector series on the market, with one of the broadest range of products. INELCO’s modcon® modular connectors are widely used in various applications. The modcon® modular PREMIUM plug series, with ADVANCED ALIGNMENT TECHNOLOGY, is a forward thinking development of a building block system for modular plugs, to be used for industrial and o ce environments.
CATEGORY WIRE MAN. BAR CONDUCTOR OD
CABLE OD
CAT6A - AAT ALIGNER
ANGLED LATCH STYLE
STRAIGHT LATCH STYLE
HOOD
0,8 1,0 1,15
max. 6,5mm
CABLE O.D. < 6,5MM; PC
Pro net 100M
CAT6A
CABLE O.D. < 6,5MM; PC/PA66
<7,5MM; PA66
Pro net 100M
CAT6A
Pro net 100M
W/O WIRE MB - 1,35/1,60 / 1,70 max.
6,5mm max.
9,0mm
Pro net 1Gig
W/O WIRE MB -
max. 9,0mm
WWW.INELCOTECH.COM [email protected]
1,35/1,60
MODCON® PREMIUM PLUG SERIES
All DIA in mm are incl. toleranceAWG is an estimation only and very depending on cable supplier and spec
Wire Aligner Wire Manager Hood
WMBA6M-08 WMBA6M WMBA6M-11 WMBA6M-1236 PWS1 MB-A6M PC-A6M-XX PCPA6M65-XX PCPA6M75-XX
wire ⌀ ≤ 0.8 mm wire ⌀ ≤1.0 mm wire ⌀ ≤1.15 mm wire ⌀ ≤ 1.0 mm ⌀ ≤ 6.5 mm ⌀ ≤ 6.5 mm ⌀ ≤ 7.5 mm
est. AWG 28 est. AWG 26 est. AWG 24 est. AWG 26 PC Zamak PC PA66 PA66
Profinet 100M
PS88A6M-HA ✔️ ✔️ ✔️
PS88A6M-HS ✔️ ✔️ ✔️
CAT5e
PS88A6M-HA ✔️ ✔️ ✔️ ✔️ ✔️ ✔️
PS88A6M-HS ✔️ ✔️ ✔️ ✔️ ✔️ ✔️
CAT6
PS88A6M-HA ✔️ ✔️ ✔️ ✔️1 ✔️ ✔️ ✔️
PS88A6M-HS ✔️ ✔️ ✔️ ✔️1 ✔️ ✔️ ✔️
CAT6A
PS88A6M-HA ✔️ ✔️ ✔️ ✔️2 ✔️2 ✔️ ✔️ ✔️
PS88A6M-HS ✔️ ✔️ ✔️ ✔️2 ✔️2 ✔️ ✔️ ✔️
CAT7
PS88A6M-HA ✔️ ✔️ ✔️ ✔️ ✔️ ✔️ ✔️
PS88A6M-HS ✔️ ✔️ ✔️ ✔️ ✔️ ✔️ ✔️
✔️1 could be used to improve values ✔️2 depending on cable and spec could be used either or - must be tested by customer
www.inelcotech.com [email protected]
INELCO - the home of unparalleled quality and service in INterconnection and ELectronic COmponents! Version: 191205
insilco® - inelco® - modcon® - intrajack® - compu-shield® - circon® - discom® - voice series®
insilco® - inelco® - modcon® - intrajack® - compu-shield® - circon® - discom® - voice series®[email protected]
All DIA in mm are incl. toleranceAWG is an estimation only and very depending on cable supplier and spec
Wire Aligner Wire Manager Hood
WMBA6M-08 WMBA6M WMBA6M-11 WMBA6M-1236 PWS1 MB2-A6M PC-UX6M-XX PC-UA6M-XX PX-A6M-X
wire ⌀ ≤ 0.8 mm wire ⌀ ≤1.0 mm wire ⌀ ≤1.15 mm wire ⌀ ≤ 1.0 mm ⌀ ≤ 5.5 mm ⌀ ≤ 6.5 mm Color Rings
est. AWG 28 est. AWG 26 est. AWG 24 est. AWG 26 PC Zamak PC PC PP
Profinet 100M
PU88A6M-HA ✔️ ✔️ ✔️
PU88A6M-HS ✔️ ✔️ ✔️
CAT5e
PU88A6M-HA ✔️ ✔️ ✔️ ✔️ ✔️ ✔️
PU88A6M-HS ✔️ ✔️ ✔️ ✔️ ✔️ ✔️
CAT6
PU88A6M-HA ✔️ ✔️ ✔️ ✔️1 ✔️ ✔️ ✔️
PU88A6M-HS ✔️ ✔️ ✔️ ✔️1 ✔️ ✔️ ✔️
CAT6A
PU88A6M-HA ✔️ ✔️ ✔️ ✔️2 ✔️2 ✔️ ✔️ ✔️
PU88A6M-HS ✔️ ✔️ ✔️ ✔️2 ✔️2 ✔️ ✔️ ✔️
CAT7
PU88A6M-HA ✔️ ✔️ ✔️ ✔️ ✔️ ✔️ ✔️
PU88A6M-HS ✔️ ✔️ ✔️ ✔️ ✔️ ✔️ ✔️
✔️1 could be used to improve values ✔️2 depending on cable and spec could be used either or - must be tested by customer
www.inelcotech.com [email protected]
INELCO - the home of unparalleled quality and service in INterconnection and ELectronic COmponents! Version: 191205
insilco® - inelco® - modcon® - intrajack® - compu-shield® - circon® - discom® - voice series®
insilco® - inelco® - modcon® - intrajack® - compu-shield® - circon® - discom® - voice series®[email protected]
All DIA in mm are incl. toleranceAWG is an estimation only and very depending on cable supplier and spec
Latch Design Opening Strainrelief Wire Diameter Hood
Angled Straight 9° 50° ≤ 1.35 mm ≤ 1.60 mm ≤ 1.70 mm PCPA6M65-XX PCPA6M75-XX
est. AWG 23 - 24
est. AWG 22 - 23
est. AWG 22
⌀ ≤ 6.5 mm ⌀ ≤ 7.5 mm
PA66 PA66
100M
PS84IND1 ✔️ ✔️ ✔️ ✔️ ✔️
PS84IND2 ✔️ ✔️ ✔️ ✔️ ✔️
PS84IND3 ✔️ ✔️ ✔️ ✔️ ✔️
PS84IND4 ✔️ ✔️ ✔️ ✔️ ✔️
PS84IND5 ✔️ ✔️ ✔️ ✔️
PS84IND6 ✔️ ✔️ ✔️ ✔️
PS84IND7 ✔️ ✔️ ✔️ ✔️
PS84IND8 ✔️ ✔️ ✔️ ✔️
PS84INDA ✔️ ✔️ ✔️ ✔️ ✔️
1G
PS88IND2 ✔️ ✔️ ✔️ (✔️)
PS88IND6 ✔️ ✔️ ✔️ (✔️)
PS88INDA ✔️ ✔️ ✔️ (✔️)
www.inelcotech.com [email protected]
INELCO - the home of unparalleled quality and service in INterconnection and ELectronic COmponents! Version: 191205
insilco® - inelco® - modcon® - intrajack® - compu-shield® - circon® - discom® - voice series®
insilco® - inelco® - modcon® - intrajack® - compu-shield® - circon® - discom® - voice series®[email protected]
Prerequisites• Plug PS84INDX (X = 1 - 6, A)• Hood Optional, PCPA6M65 for cable OD 6.5 mm, PCPA6M75 for cable OD 7.5 mm• Cable 6 mm < OD < 7.5 m, 2 twisted pairs, shielded, profinet, stranded or solid wires,
max. wire OD acc. to part 1.35 mm, 1.60 mm or 1.70 mm to max. 0.2 mm less• Tool Handtool K795 or insert U134 for air crimper machine from bex
Profinet
1: yellow2: orange3: white6: blue
12.12.2017
Wiring Scheme
Profinet1: yellow2: orange3: white6: blue
TIA 568 B1: white/ orange2: orange solid3: white/ green6: green solid
Step 1• Slide the hood over the cable• Strip the cable insulation min. 25 mm
Step 2• Turn the braid back over the cable• Trim the foil off
Step 3• Strip off the inner isolation• Make sure that all wires are intact
Step 4• Arrange the wires acc. to TIA 568 B• Profinet color scheme as above
ASSEMBLY INSTRUCTIONPS84INDX - RJ45 Profinet Industrial Plug 8P4C
1
Step 5• Cut the wires to a length of 20 mm from the end of the cable mantle
Step 6• Hold the plug housing with its contacts facing upwards
Step 7• Push the wires through the plug's holes until all wires are at front
Step 8• Bend the strain relief to the cable• Reduce its opening angle if needed
Step 9• Crimp the plug with handtool K795• Cut off the overlapping braid wires
Step 10• Control contacting and strain relief• Slide the boot over the plug
2
Step 3• Make sure that all wires are intact• Arrange them according to TIA 568 B
Step 2• Score and remove the screening foil• Untwist and straighten the wire pairs
Step 4• Cut the wires to a length of 20 mm from the end of cable's outer jacket
ASSEMBLY INSTRUCTIONPS88INDX - RJ45 Industrial Profinet Plug 8P8C
Prerequisites• Plug PS88INDX (X = 1 - 6)• Hood Optional, PCPA6M75 for cable OD 7.5 mm• Cable OD < 8.5 mm, 4 twisted pairs, shielded, profinet, stranded or solid wires,
max. wire OD acc. to part 1.35 mm or 1.60 mm to max. 0.2 mm less• Tool Handtool K791 or insert U137 for air crimper machine from bex
12.12.2017
Step 1• Strip the cable insulation > 20 mm• Turn the braid back over the cable
Wiring Scheme: TIA 568 B
1: white/ orange2: orange solid3: white/ green4: blue solid5: white/ blue6: green solid7: white/brown8: brown solid
1
Step 9• Choose die set for your cable OD• Crimp the plug with handtool K791
Step 7• Push the wires through the plug's holes until all wires are at front
Step 8• Bend the strain relief to the cable• Reduce its opening angle if needed
Step 5• Separate the solid colored wires up and the white colored wires down
Step 6• Hold the plug housing with its contacts facing upwards
Step10• Cut off the overlapping braid wires• Control contacting and strain relief
2
Step 3• Score the foil at a length of 2 mm, peel it off and assure all wires are intact
Step 1• Slide the hood over the cable• Strip the cable isolation by 50 mm
Step 2• Turn the braid back over the cable• Separate the pairs of wires
Step 4• Untwist and straighten the wires• Arrange them according to TIA 586 B
Wiring Scheme: TIA 568 B
1: white/ orange2: orange solid3: white/ green4: blue solid5: white/ blue6: green solid7: white/brown8: brown solid
ASSEMBLY INSTRUCTIONPS88A6M - RJ45 Cat6A Shielded Premium Plug
Prerequisites• Plug PS88A6M, insert WMBA6M-08/ -10/ -11, metal wire manager MB-A6M• Hood Optional, PC-A6M or PCPA6M65 for cable OD 6.5 mm (PCPA6M75 for 7.5 mm)• Cable OD < 6.5 mm, 4 twisted pairs, shielded, min. Cat6A, stranded or solid wires,
max. wire OD acc. to insert: 0.80 mm, 1.00 mm or 1.15 mm to max. 0.2 mm less• Tool Handtool K791 or air crimper machine with insert U137 from bex
12.12.2017
1
Step 9• Crimp the plug with handtool K791• Cut off the overlapping braid wires
Step 7• Cut the wires straight at insert's edge• Hold the plug with contacts upwards
Step 8• Push insert in plug until wires at front• Bend the strain relief to the cable
Step 5• Arrange the wire pairs into MB-A6M• Cut the wires diagonal for insertion
Step 6• Hold the insert's open side upwards• Thread all wires completely through
Step 10• Control contacting and strain relief• Slide the hood over the plug
2
Step 3• Score the foil at a length of 2 mm, peel it off and assure all wires are intact
Step 1• Slide the hood over the cable• Strip the cable isolation by 50 mm
Step 2• Turn the braid back over the cable• Separate the pairs of wires
Step 4• Untwist and straighten the wires• Arrange the wires acc. to TIA 586 B
Wiring Scheme: TIA 568 B
1: white/ orange2: orange solid3: white/ green4: blue solid5: white/ blue6: green solid7: white/brown8: brown solid
ASSEMBLY INSTRUCTIONPS88A6M - RJ45 Cat6 Shielded Premium Plug
Prerequisites• Plug PS88A6M, insert WMBA6M-08/ -10/ -11• Hood Optional, PC-A6M or PCPA6M65 for cable OD 6.5 mm (PCPA6M75 for 7.5 mm)• Cable OD < 6.5 mm, 4 twisted pairs, shielded, min. Cat6, stranded or solid wires,
max. wire OD acc. to insert: 0.80 mm, 1.00 mm or 1.15 mm to max. 0.2 mm less• Tool Handtool K791 or air crimper machine with insert U137 from bex
11.12.2017
1
Step 9• Crimp the plug with handtool K791• Cut off the overlapping braid wires
Step 7• Cut the wires straight at insert's edge• Hold the plug with contacts upwards
Step 8• Push insert in plug until wires at front• Bend the strain relief to the cable
Step 5 • Cut the wires diagonal for insertion• Hold the insert's open side upwards
Step 6• Thread all wires completely through the insert' holes
Step 10• Control contacting and strain relief• Slide the hood over the plug
2
Step 1• Slide the hood over the cable• Strip the cable insulation > 20 mm
Step 2• Assure that all wires are intact• Separate the pairs of wires
Step • Arrange the wires into metal manager• Cut the wires diagonal for insertion
ASSEMBLY INSTRUCTIONPU88A6M - RJ45 Cat6A Unshielded Premium Plug
Prerequisites• Plug PU88A6M, insert WMBA6M-08/ -10/ -11, metal wire manager MB2-A6M• Hood Obligatory, PC-UX6M for cable OD 5.5 mm, PC-UA6M for cable OD 6.5 mm• Cable 5.5 mm < OD < 6.5 mm, 4 twisted pairs, unshielded, > Cat6A, stranded or solid,
max. wire OD acc. to insert: 0.80 mm, 1.00 mm or 1.15 mm to max. 0.2 mm less• Tool Handtool K750 or air crimper machine with insert U149 from bex
12.12.2017
Wiring Scheme: TIA 568 B
1: white/ orange2: orange solid3: white/ green4: blue solid5: white/ blue6: green solid7: white/brown8: brown solid
Step 3• Untwist and straighten the wires• Arrange them according to TIA 586 B
1
Step 9• Crimp the plug with handtool K750• Control contacting and strain relief
Step 7• Hold the plug with contacts upwards• Press the cable jacket into the plug
Step 5• Hold the insert's open side upwards• Pull wires completely through insert
Step 6• Reduce the space to the cable's jacket• Cut the wires straight at edge of insert
Step 8• Control that all wires are at front• Click the hood into the plug housing
2
Step 3• Untwist and straighten the wires• Arrange them according to TIA 586 B
Step 1• Slide the hood over the cable• Strip the cable insulation > 20 mm
Step 2• Assure that all wires are still intact• Separate the pairs of wires
Step 4• Cut the wires diagonal for insertion• Hold the insert with its arrow upwards
ASSEMBLY INSTRUCTIONPU88A6M - RJ45 Cat6 Unshielded Premium Plug
Prerequisites• Plug PU88A6M with insert WMBA6M-08/ -10/ -11• Hood Obligatory, PC-UX6M for cable OD 5.5 mm, PC-UA6M for cable OD 6.5 mm• Cable 5.5 mm < OD < 6.5 mm, 4 twisted pairs, unshielded, > Cat6, stranded or solid,
max. wire OD acc. to insert: 0.80 mm, 1.00 mm or 1.15 mm to max. 0.2 mm less• Tool Handtool K750 or air crimper machine with insert U149 from bex
12.12.2017
Wiring Scheme: TIA 568 B
1: white/ orange2: orange solid3: white/ green4: blue solid5: white/ blue6: green solid7: white/brown8: brown solid
1
Step 9• Crimp the plug with handtool K750• Control contacting and strain relief
Step 7• Press the cable jacket into the plug• Assure the strain relief is above jacket
Step 8• Control that all wires are at front• Click the hood into the plug housing
Step 5• Pull the wires completely through• Reduce the space to cable jacket
Step 6• Cut the wires straight insert's edge• Hold the plug with contacts upwards
2
Test Reportmodcon® - PS88A6M
Date: 2012.11.01 Page 1 of 11
Transmission Characteristics of PS88A6M /CAT6 shielded plug PS88A6M shielded CAT6 plug ful�lls the requirements for electrical transmission performance according to IEC 60603-7-51; detail speci�cation for 8-way, shielded, free and �xed connectors, for data transmissions with frequencies up to 500 MHz": 2010 and according to IEC11801 Ed. 2.2, Cat 6 : 2011 : - insertion loss - return loss - near-end crosstalk - far-end crosstalk - TCl - TCTl - transfer impedance
Di�erent length (0,5m, 1 m, 13m) of CAT 6 balanced cables assembled to PS88A6M ful�ll the RF performance (return loss, near-end crosstalk) according to IEC 61935-2: 2010 "Speci�cation for the testing of balanced and coaxial informationtechnology cabling - Part 2: Cords as speci�ed in ISOIIEC 11801 and related standards".
A
A
A
A
Test Reportmodcon® - PS88A6M
Date: 2012.11.01 Page 2 of 11
1. Insertion loss
1M 100M 200M 300M 400M 500M 600M-0,8
-0,7
-0,6
-0,5
-0,4
-0,3
-0,2
-0,1
0,0
-0,8
-0,7
-0,6
-0,5
-0,4
-0,3
-0,2
-0,1
0,0
Inse
rtio
n lo
ss [d
B]
frequency [Hz]Test order : 12-0193date : 17.10.12
pair 12 pair 36 pair 45 pair 78
Cat6A Limit for connecting hardware acc. to IEC 60603-7-51: 2010 and ISO IEC 11801: 2011
Insertion loss of sample 1 INELCO CAT6 shielded plugPS88A6M
A
mated to Patchcord Test Head Cat 6A, Telegärtner PASS
1M 100M 200M 300M 400M 500M 600M-0,8
-0,7
-0,6
-0,5
-0,4
-0,3
-0,2
-0,1
0,0
-0,8
-0,7
-0,6
-0,5
-0,4
-0,3
-0,2
-0,1
0,0
Inse
rtio
n lo
ss [d
B]
frequency [Hz]Test order : 12-0193date : 17.10.12
pair 12 pair 36 pair 45 pair 78
Cat6A Limit for connecting hardware acc. to IEC 60603-7-51: 2010 and ISO IEC 11801: 2011
Insertion loss of sample 2 INELCO CAT6 shielded plugPS88A6M
A
mated to Patchcord Test Head Cat 6A, Telegärtner PASS
Test Reportmodcon® - PS88A6M
Date: 2012.11.01 Page 3 of 11
2. Return loss
1M 100M 200M 300M 400M 500M 600M-70
-60
-50
-40
-30
-20
-10
0
-70
-60
-50
-40
-30
-20
-10
0
Ret
urn
loss
[dB
]
frequency [Hz]Test order : 12-0193date : 17.10.12
plug side pair 12 pair 36 pair 45 pair 78
Cat6A Limit for connecting hardware acc. to IEC 60603-7-51: 2010 and ISO IEC 11801: 2011
Return loss of sample 1
A
mated to Patchcord Test Head Cat 6A, Telegärtner PASS
1M 100M 200M 300M 400M 500M 600M-70
-60
-50
-40
-30
-20
-10
0
-70
-60
-50
-40
-30
-20
-10
0
Ret
urn
loss
[dB
]
frequency [Hz]Test order : 12-0193date : 17.10.12
plug side pair 12 pair 36 pair 45 pair 78
Cat6A Limit for connecting hardware acc. to IEC 60603-7-51: 2010 and ISO IEC 11801: 2011
Return loss ofsample 2
mated to Patchcord Test Head Cat 6A, Telegärtner PASS
INELCO CAT6 shielded plugPS88A6M
A
INELCO CAT6 shielded plugPS88A6M
Test Reportmodcon® - PS88A6M
Date: 2012.11.01 Page 4 of 11
3. Near-end crosstalk
1M 100M 200M 300M 400M 500M 600M-110
-100
-90
-80
-70
-60
-50
-40
-30
-110
-100
-90
-80
-70
-60
-50
-40
-30
Nea
r-en
d cr
osst
alk
[dB
]
frequency [Hz]
Test order : 12-0193date : 17.10.12
Cat6A Limit for connecting hardware acc. to IEC 60603-7-51: 2010 and ISO IEC 11801: 2011
Near-end crosstalk between ... pairs 12/36 pairs 12/45 pairs 12/78 pairs 36/45 pairs 36/78 pairs 45/78
Near-end crosstalk of sample 1
mated to Patchcord Test Head Cat 6A, Telegärtner PASS
1M 100M 200M 300M 400M 500M 600M-110
-100
-90
-80
-70
-60
-50
-40
-30
-110
-100
-90
-80
-70
-60
-50
-40
-30
Nea
r-en
d cr
osst
alk
[dB
]
frequency [Hz]Test order : 12-0193date : 17.10.12
Cat6A Limit for connecting hardware acc. to IEC 60603-7-51: 2010 and ISO IEC 11801: 2011
Near-end crosstalk between ... pairs 12/36 pairs 12/45 pairs 12/78 pairs 36/45 pairs 36/78 pairs 45/78
Near-end crosstalk of sample 2
mated to Patchcord Test Head Cat 6A, Telegärtner PASS
A
INELCO CAT6 shielded plugPS88A6M
A
INELCO CAT6 shielded plugPS88A6M
Test Reportmodcon® - PS88A6M
Date: 2012.11.01 Page 5 of 11
4. Far-end crosstalk
1M 100M 200M 300M 400M 500M 600M-100
-90
-80
-70
-60
-50
-40
-30
-20
-100
-90
-80
-70
-60
-50
-40
-30
-20 Cat6A Limit for connecting hardware acc. to IEC 60603-7-51: 2010 and ISO IEC 11801: 2011
Far-end crosstalk between ... pairs 12/36 pairs 12/45 pairs 12/78 pairs 36/45 pairs 36/78 pairs 45/78
Far-
end
cros
stal
k [d
B]
frequency [Hz]Test order : 12-0193date : 17.10.12
Far-end crosstalk of sample 1
mated to Patchcord Test Head Cat 6A, Telegärtner PASS
1M 100M 200M 300M 400M 500M 600M-100
-90
-80
-70
-60
-50
-40
-30
-20
-100
-90
-80
-70
-60
-50
-40
-30
-20 Cat6A Limit for connecting hardware acc. to IEC 60603-7-51: 2010 and ISO IEC 11801: 2011
Far-end crosstalk between ... pairs 12/36 pairs 12/45 pairs 12/78 pairs 36/45 pairs 36/78 pairs 45/78
Far-
end
cros
stal
k [d
B]
frequency [Hz]Test order : 12-0193date : 17.10.12
Far-end crosstalk of sample 2
mated to Patchcord Test Head Cat 6A, Telegärtner PASS
A
INELCO CAT6 shielded plugPS88A6M
A
INELCO CAT6 shielded plugPS88A6M
Test Reportmodcon® - PS88A6M
Date: 2012.11.01 Page 6 of 11
5. TCL of connecting
1M 100M 200M 300M 400M 500M 600M-80
-70
-60
-50
-40
-30
-20
-10
0
-80
-70
-60
-50
-40
-30
-20
-10
0
pair 12 pair 36 pair 45 pair 78
TCL
[dB
]
frequency [Hz]Test order : 12-0193date : 17.10.12
Cat6A Limit for connecting hardware acc. to IEC 60603-7-51: 2010 and ISO IEC 11801: 2011
TCL of sample 1
mated to Patchcord Test Head Cat 6A, Telegärtner PASS
1M 100M 200M 300M 400M 500M 600M-80
-70
-60
-50
-40
-30
-20
-10
0
-80
-70
-60
-50
-40
-30
-20
-10
0
pair 12 pair 36 pair 45 pair 78
TCL
[dB
]
frequency [Hz]Test order : 12-0193date : 17.10.12
Cat6A Limit for connecting hardware acc. to IEC 60603-7-51: 2010 and ISO IEC 11801: 2011
TCL of sample 2
mated to Patchcord Test Head Cat 6A, Telegärtner PASS
A
INELCO CAT6 shielded plugPS88A6M
A
INELCO CAT6 shielded plugPS88A6M
Test Reportmodcon® - PS88A6M
Date: 2012.11.01 Page 7 of 11
6. TCTL
1M 100M 200M 300M 400M 500M 600M-80
-70
-60
-50
-40
-30
-20
-10
0
-80
-70
-60
-50
-40
-30
-20
-10
0
pair 12 pair 36 pair 45 pair 78
TCTL
[dB
]
frequency [Hz]Test order : 12-0193date : 17.10.12
Cat6A Limit for connecting hardware acc. to IEC 60603-7-51: 2010 and ISO IEC 11801: 2011
TCTL of sample 1
mated to Patchcord Test Head Cat 6A, Telegärtner PASS
1M 100M 200M 300M 400M 500M 600M-80
-70
-60
-50
-40
-30
-20
-10
0
-80
-70
-60
-50
-40
-30
-20
-10
0
pair 12 pair 36 pair 45 pair 78
TCTL
[dB
]
frequency [Hz]Test order : 12-0193date : 17.10.12
Cat6A Limit for connecting hardware acc. to IEC 60603-7-51: 2010 and ISO IEC 11801: 2011
TCTL of sample 2
mated to Patchcord Test Head Cat 6A, Telegärtner PASS
Test Reportmodcon® - PS88A6M
Date: 2012.11.01 Page 8 of 11
7. Transfer impedance
M001M01M1k0031
10
100
1.000
1
10
100
1000
Test order : 12-0193date : 17.10.12
with Cat 7 cable; couple length 39cm
sample 3 sample 4
Tran
sfer
impe
danc
e [m
ΩΩ ΩΩ]
Frequency [Hz]
Test setup acc. to IEC 60512-26-100,Test 26e: 2008 ; triaxial method
Cat6A Limit for connecting hardware acc. to ISO IEC 11801: 2011
Transfer impedance of sample 3, 4
PASS
Cable ID: 21-151, PC-CAT6A: 0,5M Test Summary: PASSDate / Time: 01.11.2012 09:58:53 Operator: P. Pardal Model: DTX-1800Headroom 2.1 dB (NEXT 36-45) Software Version: 2.6300 Main S/N: 9132029Test Limit: ISO Patch Cord Cat6A 0.5m Limits Version: 1.8100 Remote S/N: 9132030Cable Type: Cat 6A FTP NVP: 74.0% Main Adapter: DTX-PC6A/MN ISO/IEC
Remote Adapter: DTX-PC6A/MN ISO/IEC
LinkWare Version 7.2
Length (m) [Pair 12] 0.4Prop. Delay (ns) [Pair 45] 3Delay Skew (ns) [Pair 45] 1Resistance (ohms) [Pair 45] 0.2
Worst Case Margin Worst Case ValuePASS MAIN SR MAIN SRWorst Pair 36-45 36-45NEXT (dB) 2.1 4.8Freq. (MHz) 294.0 500.0Limit (dB) 37.5 30.9
PASS MAIN SR MAIN SRWorst Pair 12 78RL (dB) 0.0* 3.0Freq. (MHz) 24.1 450.0Limit (dB) 24.0 10.2
0.4 m
Wire Map (T568B)PASS
* Measurement is within the accuracy limits of the instrument.
Cable ID: 21.151, PC-CAT6A: 1M Test Summary: PASSDate / Time: 01.11.2012 10:09:15 Operator: P. Pardal Model: DTX-1800Headroom 2.3 dB (NEXT 36-45) Software Version: 2.6300 Main S/N: 9132029Test Limit: ISO Patch Cord Cat6A 1.0m Limits Version: 1.8100 Remote S/N: 9132030Cable Type: Cat 6A FTP NVP: 74.0% Main Adapter: DTX-PC6A/MN ISO/IEC
Remote Adapter: DTX-PC6A/MN ISO/IEC
LinkWare Version 7.2
Length (m) [Pair 12] 1.1Prop. Delay (ns) [Pair 45] 6Delay Skew (ns) [Pair 45] 1Resistance (ohms) [Pair 45] 0.4
Worst Case Margin Worst Case ValuePASS MAIN SR MAIN SRWorst Pair 36-45 36-45NEXT (dB) 2.3 2.3Freq. (MHz) 479.0 484.0Limit (dB) 31.5 31.3
PASS MAIN SR MAIN SRWorst Pair 12 78RL (dB) 0.3* 3.6Freq. (MHz) 19.1 441.0Limit (dB) 23.7 10.3
1.1 m
Wire Map (T568B)PASS
* Measurement is within the accuracy limits of the instrument.
Cable ID: 21-151, PC-CAT6A: 13M Test Summary: PASSDate / Time: 01.11.2012 10:08:18 Operator: P. Pardal Model: DTX-1800Headroom 4.6 dB (NEXT 36-45) Software Version: 2.6300 Main S/N: 9132029Test Limit: ISO Patch Cord Cat6A 10.0m Limits Version: 1.8100 Remote S/N: 9132030Cable Type: Cat 6A FTP NVP: 74.0% Main Adapter: DTX-PC6A/MN ISO/IEC
Remote Adapter: DTX-PC6A/MN ISO/IEC
LinkWare Version 7.2
Length (m) [Pair 78] 13.5Prop. Delay (ns) [Pair 12] 62Delay Skew (ns) [Pair 12] 1Resistance (ohms) [Pair 45] 3.7
Worst Case Margin Worst Case ValuePASS MAIN SR MAIN SRWorst Pair 36-45 36-45NEXT (dB) 4.6 4.6Freq. (MHz) 414.0 473.0Limit (dB) 33.3 32.2
PASS MAIN SR MAIN SRWorst Pair 45 45RL (dB) 0.3* 4.3Freq. (MHz) 4.0 387.0Limit (dB) 21.6 11.2
13.5 m
Wire Map (T568B)PASS
* Measurement is within the accuracy limits of the instrument.
�
PS88A6M VALIDATION DOCUMENTATION
ID# Test Criteria Standards & Specs Procedures Result
1.0 Environmental Requirements
Non-operating Temperature Range -40 ͦ C to + 70 ͦ C Pass
Operating Temperature Range -10 ͦ C to + 60 ͦ C TIA-568-C.2, sect.5.7.1 Pass
Communications cables - safety
compliant to UL444 and NEC articles 800
UL444 - communications cable NEC - National electrical code
RoHS RoSH compliance Directive 2002/95/EC Pass
2.0 Electrical Requirements - Cable
DC resistance 14Ω max. TIA-568-C.2, sect.6.6.1 as per ASTM 4566 Pass
Resistance unbalance4% max for Cat 6A cable cord 5% max for Cat 5E / Cat 6 cable cord
TIA-568-C.2, sect.6.4.2 as per ASTM 4566 Pass
Mutual capacitance < 5.6 nF @1kHz , 20ͦ C TIA-568-C.2, sect.6.4.3 as per ASTM 4566 Pass
Capacitance unbalance <330 pF @1kHz , 20ͦ C TIA-568-C.2, sect.6.4.4 as per ASTM 4566 Pass
Dielectric strength (screened cable only)
Withstand 2.5 kV DC for 2sec (between conductors) Withstand 5 kV DC for 2sec (between cre shield and conductor)
TIA-568-C.2, sect.5.3.10 TIA-568-C.2, sect.5.6.8
as per IEC 60189-1 as per ASTM 4566 Pass
Surface transfer impedance (for screened cable only) < Z f Tcable =10 mΩ/m TIA-568-C.2, sect.
6.4.20as per IEC 62153-4-3 Pass
3.0 Electrical Requirements - Plug
Current rating 1.5 A IEC 60603-7 IEC 60603-7, section 6.4.3 Pass
Voltage rating 30 V AC Pass
UL94 UL94 V-0 UL1863 UL94 section 8 Pass
Insulation resistance (mating)
Insulation Resistance: - 500 MΏ Min.
IEC 60603-7 series, clause 6.4.7 IEC 60512-2, test 3A Pass
Voltage Proof (Mating) compliance IEC 60603-7 series Section 6.4.2
IEC 60512, Test 4a, Method A Pass
Contact Resistance 20 mOhm maximum (2a) IEC 60603-7 IEC 60512, 2a Pass
4,0 Physical Requirements
Conductor Material - CableFully annealed solid bare copper or stranded (tinned or bare) copper
Pass
Contact blade - PlugPhosphor bronze with 50 µ inch of Gold over Nickel Plating
Pass
Plug dimensions FCC Part 68, Subpart F, IEC 60603-7 compliance IEC 60603-7 IEC 60603-7 Pass
Crimp Height ±0.005" from nominal 0.237" IEC 60603-7 IEC 60603-7 section 3.2.2 (Parameter K2) Pass
5.0 Mechanical Requirements
Mechanical conformance for cord cable
Cord Cable Cat 6/6A : ANSI/ICEA S-102-732-2009 Cord Cable Cat 5E : ANSI/ICEA S-90-661-2006
TIA-568-C.2, sect 5.3 Pass
Pull Test 2lbf each wire UL1863 UL1863 section 40 Pass
Flex Test 90 degress UL1863 UL1863 section 39 Pass
Strain ReliefWithstand 1min without discontinuity of the signal (45 degree with 11.25 lbf)
UL1863 UL1863 section 26 Pass
Mechanical operations 750 operations TIA-568-C.2 , sect. A.3 IEC 60603-7 Pass
�
PS88A6M VALIDATION DOCUMENTATION
ID# Test Criteria Standards & Specs Procedures Result
6.0 Reliability Requirements - Plug
Mating Reliability test schedule
TIA-568-C.2 Annex A. Reference to Clause A.5.3
TIA-568-C.2 Annex A. IEC 60603-7 series
Reliability test schedule Pass
7.0 Transmission Requirements
Patch cord performance
NEXT : TIA-568-C.2, clause 6.9.2 Return loss : TIA-568-C.2, clause 6.9.1
TIA-568-C.2 , sect. 9
NEXT: TIA-568-C.2, clause C.5 Return Loss : TIA-568-C.2, clause C.5.3 see Belden TP-11001
Pass
Plug PerformancePlug- DNEXT as per Table C.2 and Table C.3 of TIA-568-C.2
TIA-568-C.2 , sect. C.4.4.3
TP-10027 (Plug- Dnext qualification) Pass
Cord Cable transmission performance
compliant to TIA-568-C.2 refer to tab 'Cord Cable performance'
TIA-568-C.2 as per TIA-568-C.2 Pass