FC722 Cerberus™ PRO Fire control panel · 5 Building Technologies Fire Safety...

12
A6V10206525_i_en_-- 2016-05-23 Building Technologies Control Products and Systems FC722 Cerberus™ PRO Fire control panel FS720 series, IP6 κ Compact, pre-assembled, microprocessor-controlled fire control panel with integrated operating unit for up to 252 addresses κ Fire control panel can be used as a standalone version or can be networked κ Up to 64 stations, such as control panels and terminals, can be linked to form a network κ Integrated degraded mode function κ Redundant network node, degraded mode operation according to EN 54 κ Fast Ethernet interface for a heterogeneous network κ Integrated user-friendly operating unit κ Can be extended by adding printer, key switches, LED indicators κ Slots for RS232 and RS485 serial interfaces κ Emergency power supply for emergency operating time of up to 72 hours κ Detection and automatic reading in (auto-configuration) of all C-NET devices, ready for operation immediately κ Processes signals from Cerberus PRO FD720 detector series κ Floor repeater displays, floor repeater operating units, and alarm devices on C- NET detector line κ Flexible configuration of complex applications and controls κ Configuration data can be uploaded/downloaded via remote access κ Firmware for all processor-controlled control panel components can be updated

Transcript of FC722 Cerberus™ PRO Fire control panel · 5 Building Technologies Fire Safety...

A6V10206525_i_en_--2016-05-23

Building TechnologiesControl Products and Systems

FC722 Cerberus™ PRO

Fire control panelFS720 series, IP6

κ Compact, pre-assembled, microprocessor-controlled fire control panel withintegrated operating unit for up to 252 addresses

κ Fire control panel can be used as a standalone version or can be networkedκ Up to 64 stations, such as control panels and terminals, can be linked to form a

networkκ Integrated degraded mode functionκ Redundant network node, degraded mode operation according to EN 54κ Fast Ethernet interface for a heterogeneous networkκ Integrated user-friendly operating unitκ Can be extended by adding printer, key switches, LED indicatorsκ Slots for RS232 and RS485 serial interfacesκ Emergency power supply for emergency operating time of up to 72 hoursκ Detection and automatic reading in (auto-configuration) of all C-NET devices,

ready for operation immediatelyκ Processes signals from Cerberus PRO FD720 detector seriesκ Floor repeater displays, floor repeater operating units, and alarm devices on C-

NET detector lineκ Flexible configuration of complex applications and controlsκ Configuration data can be uploaded/downloaded via remote accessκ Firmware for all processor-controlled control panel components can be

updated

2

Building TechnologiesFire Safety

A6V10206525_i_en_--2016-05-23

System overview

2 (4) loopsmax. 252 addresses

C-NET

stub line

24VDC ext.possible

FC722Fire control panel

Fire controlsvia FCI2008-A1

Remote accessEngineering Tool,

Operating Tool

FDCL221

FDM22xFDM221

DBS720

OH720

HI722

HI720

OP720 Conventional horn linevia FCI2009-A1

FDCIO221

1 input

1 output

1 input

FDCI221

OH720

24VDC ext.

2 in-/outputsoptionally

FDCIO223

Cluster (C-WEB/SAFEDLINK)

RepeaterFN2002

FT724

FC722

Detection line collective Siemens,Synova SynoLINE300 or

SynoLINE600

TM Transmission of analarm signalTransmission of afault signalvia FCI2007-A1

Mimic displayFT2001-A1

OP720

DBS721 / DBS729

FC10 or XC10

Fire detection orExtinguishingcontrol unitcollective

FDCI222

4 inputs

4 outputs

FDCIO222

FDS221/FDS229

4 inputs

FT2010/FT2011Floor repeater terminal /Floor repeater display

Explosion-hazard area

FDOOT271

Radio detectors

FDM273

FDCW241

FDA221/FDA241

FDM233-Ex

OOH740-A9-Ex

FDCI723

FDCL221-Ex

3

Building TechnologiesFire Safety

A6V10206525_i_en_--2016-05-23

Networking of several fire control panels

Up to 32 control panels and terminals can be linked to form a cluster (C-WEB/SAFEDLINK network). If the cluster is connected to a danger managementsystem via BACnet, up to 16 control panels and terminals can be networked.

Siemens DangerManagement System

DL3750+

Matrix printerRS232

FC722

FT724/FC72x

Cluster (C-WEB/SAFEDLINK)16 stations

In-/Outputs

Ethernet

FC722/FC724

RepeaterFN2002

4

Building TechnologiesFire Safety

A6V10206525_i_en_--2016-05-23

An optical Ethernet network (C-WEB/LAN) allows up to 14 clusters with up to 16stations to be operated on one network. A maximum of 64 stations is supported in total.

You will find details of system networking in product data sheet A6V10227649.

5

Building TechnologiesFire Safety

A6V10206525_i_en_--2016-05-23

Function features

κ The FC722 is a compact fire control panel with integrated operating unit forprocessing signals from FD720 devices.

κ The control panel may be used as a standalone unit or networked.κ The control panel and the fire detection system are custom-configured using

the Cerberus-Engineering-Tool software.κ All detector lines are monitored for ground faults.κ Customer texts can be adapted directly on the operating unit of the control

panel or with the Cerberus-Engineering-Tool software.κ Up to 2000 events can be retrieved from the event memory based on various

criteria.κ Automatic summer/winter time changeoverκ Siemens danger management system can be connected

Function elements

Operating unitThe following elements are available on the operating unit:– CPU module and electronics– Ethernet connection– Slots for RS232 and RS485 modules and network modules (SAFEDLINK)– Space for 'Kaba' or 'Nordic' key switch– Space for event printer (depending on version)– Peripheral data bus connection for optional LED modules (for FC722 in Comfort

housing)

Periphery boardThe following elements are available on the periphery board:– Connection terminals for C-NET lines, remote transmission (alarm, fault), horn

output, configurable control inputs and outputs, monitored alarm and fault output,emergency supply, power supply

– Slot for loop extension (C-NET)

70 W or 150 W power supply, emergency power supplyThe power supply feeds the hardware and charges the batteries.In the event of a power cut, the batteries provide emergency current.

HousingA pivoting mounting plate can be fitted for the following elements above the peripheryboard on the rear housing panel:– 1x fire brigade periphery module (for Germany)– 1x sounder module (as an alternative to mounting on U-rail TS3)

ConfigurationThe FXS7212 Cerberus-Engineering-Tool allows the system to be customized.

6

Building TechnologiesFire Safety

A6V10206525_i_en_--2016-05-23

Application ranges

The FC722 is ideal for smaller applications, e.g., for use in workshops or hotels, or as adevice in a network.However, thanks to the flexible networking options, the FC722 can also be used forlarge-scale sites.

Operation

Each control unit has an integrated operating unit. The control panel can also beoperated via a separate FT724 fire terminal.You will find details and more information in product data sheet A6V10207898.

7

Building TechnologiesFire Safety

A6V10206525_i_en_--2016-05-23

Overview of FC722 fire control panels

Housing (Standard) Housing (Comfort)FC722-ZZ FC722-YZ FC722-ZA FC722-ZE

Featuring 24 indicator groups Featuring 48 indicator groupswith one red/green + one yellow

LED eachwith one red/green + one yellow

LED each

2 loops 2 loopswith power supply (70 W) with power supply (70 W)

Max. battery capacity 12 Ah Max. battery capacity 12 Ah

2 loops 2 loopswith power supply (150 W) with power supply (150 W)Max. battery capacity 26 Ah Max. battery capacity 26 Ah

Extensions External printerFH7202-Z3 FH7203-Z3 FTO2001-A1 DL3750+

Housing (Standard) Housing (Comfort) Event printer Matrix printer (external)430 x 398 x 183 mm 430 x 796 x 183 mm RS232 interface

Empty housing for free use

For installation in all controlpanelsexcept RS232 module must

FC722-YZ be ordered separatelyRS232 module must

be ordered separatelyE.g., for extra batteries,

Operating add-on, or Operating accessoriesEvent printer FCM7214-Y3

Space for batteries 48 display groups 96 indicator groups 2x FA2003-A1 (7 Ah) or with one red/green + one yellow

LED eachwith one red/green + one yellow

LED each 2x FA2004-A1 (12 Ah) or 2x FA2006-A1 (26 Ah)

E.g., for extra batteries,Operating add-on, or

Event printer for retrofitting for retrofittingSpace for batteries

2x FA2003-A1 (7 Ah) or2x FA2004-A1 (12 Ah) or2x FA2005-A1 (17 Ah) or

2x FA2006-A1 (26 Ah)

8

Building TechnologiesFire Safety

A6V10206525_i_en_--2016-05-23

Layout of FC722 inside housing (Standard)

2 1

3

617

18

4 8

10

5

12 13 14

7

9

19

11

15

16

16

2014

21

Basic equipment Designation Comment1 Housing (Standard) FH7202-Z3 Items 1-5: Basic equipment2 Periphery board (2-loop) FCI2002-A13 Power supply (70 W) FP2015-A14 Mains terminals on TS35 DIN rail – Space for socket, relay modules5 Operating unit FCM72xx-xx Operating unit with CPU6 Space for batteries – 2x 12 V/7…12 Ah

Extensions7 Relay module Z3B171 Relay for fire controls8 Event printer FTO2001-A1 For logging events9 Key switch (Kaba) FTO2005-C1 For operating access authorization

Key switch (nordic) FTO2006-B110 Mounting plate FHA2007-A1 E.g., for fire brigade periphery module11 Loop extension (C-NET) FCI2003-A1 For extending the number of loops from 2 to 4, the number of

addresses remains the same12 RS485 module (isolated) FCA2002-A1 For peripheral devices with RS485 interface13 RS232 module (isolated) FCA2001-A1 For devices with an RS232 interface14 Network module (SAFEDLINK) FN2001-A1 For networking several stations15 Repeater (SAFEDLINK) FN2002-A1 For extending the C-WEB system bus, max. 1x repeater

(SAFEDLINK) between two stations (mounted directly on a planesurface, on a TS35 U-rail, or in housing FDCH221)

16 Sounder module FCA2005-A1 For splitting one conventional sounder into four17 Battery (12 V, 7 Ah, VDS) FA2003-A1 For the emergency power supply

Battery (12 V, 12 Ah, VDS) FA2004-A118 Fire brigade periphery module FCI2001-D1 For Germany (FBF, FSD, ÜE, FSE, ÖA, KL)19 19" mounting kit FHA2016-A1 For installation in 19" third-party housing20 License key Sx FCA20xx For special functions21 Cable kit (communication) FCA2014-A1 For flexible cable joints running to the modules on the operating unit

9

Building TechnologiesFire Safety

A6V10206525_i_en_--2016-05-23

Layout of FC722 inside housing (Comfort)

14

1

2

3

4

5

617

78

912 13 14

18

19

8

101822

16

15

11

16

20

21

21

Basic equipment Designation Comment1 Housing (Comfort) FH7203-Z3 Items 1-5: Basic equipment2 Periphery board (2-loop) FCI2002-A13 Power supply (SV 24V-150 W) V24230-Z6-A54 Mains terminals on TS35 DIN rail – Space for socket, relay modules, etc.5 Operating unit FCM72xx-xx Operating unit with CPU6 Space for batteries – 2x 12 V/7…26 Ah

Extensions Designation Comment7 Relay module Z3B171 Relay for fire controls8 Event printer FTO2001-A1 For logging events9 Key switch (Kaba) FTO2005-C1 For operating access authorization

Key switch (nordic) FTO2006-B110 Mounting plate FHA2007-A1 E.g., for fire brigade periphery module11 Loop extension (FDnet/C-NET) FCI2003-A1 For extending the number of loops from two to four, the number of

addresses remains the same12 RS485 module (isolated) FCA2002-A1 For peripheral devices with RS485 interface13 RS232 module (isolated) FCA2001-A1 For devices with an RS232 interface14 Network module (SAFEDLINK) FN2001-A1 For networking several stations15 Repeater (SAFEDLINK) FN2002-A1 For extending the C-WEB system bus, max. 1x repeater

(SAFEDLINK) between two stations (mounted directly on a planesurface, on a TS35 U-rail, or in housing FDCH221)

16 Sounder module FCA2005-A1 For splitting one conventional sounder into four

10

Building TechnologiesFire Safety

A6V10206525_i_en_--2016-05-23

Extensions Designation Comment17 Battery (12 V, 12 Ah, VDS) FA2004-A1 For the emergency power supply

Battery (12 V, 26 Ah, VDS) FA2006-A118 Fire brigade periphery module FCI2001-D1 For Germany (FBF, FSD, ÜE, FSE, ÖA, KL)19 19" mounting kit FHA2016-A1 For installation in 19" third-party housing20 License key Sx FCA20xx For special functions21 Cable kit (communication) FCA2014-A1 For flexible connections running to the modules on the operating

unit22 Power supply kit (150 W, B) FP2005-A1 For extra power supply

Technical data

FC722 inside housing (Standard) FC722 inside housing (Comfort)Mains voltage AC 97…127 V/AC 196…253 V AC 115/230 V +10/-15 %Power supply 70 W 150 WOperating voltage DC 20.5…28.6 V DC 21…28.4 VOperating current Max. 2.5 A Max. 5 ABattery capacity 2x 12 V, 7…12 Ah 2x 12 V, 26 AhBattery monitoring Yes YesNetwork monitoring Yes YesConnectable detector series Cerberus PRO FD720 (C-NET) Cerberus PRO FD720 (C-NET)Number of lines– Loops (with loop extension) or– Stubs

2 (4)4 (8)

2 (4)4 (8)

Number of addresses Max. 252 Max. 252Integrated inputs/outputs– Relay output

– RT alarm– RT fault

– Monitored outputs– Alarm– Fault– Horn

– Freely programmable inputs/outputs

11

1118

11

1118

Operating unit Integrated IntegratedSlots for RS232, RS485 serial ports 2 2Slots for network modules 2 2Slot for loop extension 1 1Mounting space for cable kit (communication) 1 2Sounder module Max. 1 Max. 1Ethernet port RJ45 1 1Operating temperature -8…+42 °C -8…+42 °CStorage temperature -20…+60 °C -20…+60 °CAir humidity (no condensation permitted) ≤95 % rel. ≤95 % rel.Dimensions (W x H x D)– Without cover cap– With cover cap

430 x 398 x 160 mm430 x 398 x 183 mm

430 x 796 x 160 mm430 x 796 x 183 mm

Color– Housing– Cover cap

~RAL 7035, light gray~RAL 000 50 00

~RAL 7035, light gray~RAL 000 50 00

Protection category (IEC 60529) IP30 IP30Approvals– VdS– LPCB– FM– DNV GL (Marine)

G209076126bn/063051081

-

G209076126bn/063051081

See document A6V10339425

11

Building TechnologiesFire Safety

A6V10206525_i_en_--2016-05-23

Siemens Switzerland LtdBuilding Technologies DivisionInternational HeadquartersGubelstrasse 22CH-6301 ZugTel. +41 41 724 24 24www.siemens.com/buildingtechnologies

© Siemens Switzerland Ltd, 2009Technical specifications and availability subject to change without notice.

Document no. A6V10206525_i_en_-- FS720 manualEdition 2016-05-23

Details for ordering

Type Art. no. Designation WeightControl panels FC722-ZZ S54400-C29-A5 Fire control panel (2L) 10.660 kg

FC722-YZ S54400-C29-A4 Fire control panel (2L, 1LED) 10.500 kgFC722-ZA S54400-C29-A2 Fire control panel (2L) 18.250 kgFC722-ZE S54400-C29-A1 Fire control panel (2L, 2LED) 20.850 kg

Extensions Z3B171 BPZ:4843830001 Relay module AC 250 V / 10 A (1 relay) 0.042 kgFTO2001-A1 A5Q00010126 Event printer 0.250 kg– A5Q00017619 Spare printer reels (10 reels) 0.090 kgFTO2005-C1 A5Q00010113 Key switch (Kaba) 0.013 kgFTO2006-B1 A5Q00010129 Key switch (nordic) 0.050 kgFHA2007-A1 A5Q00010151 Mounting plate 0.800 kgFCI2003-A1 A5Q00010136 Loop extension (FDnet/C-NET) 0.064 kgFCA2002-A1 A5Q00009923 RS485 module (isolated) 0.067 kgFCA2001-A1 A5Q00005327 RS232 module (isolated) 0.068 kgFN2001-A1 A5Q00012851 Network module (SAFEDLINK) 0.077 kgFN2002-A1 S24236-B2502-A1 Repeater (SAFEDLINK) 0.154 kgFCA2005-A1 A5Q00014866 Sounder module 0.140 kgFCA2014-A1 A5Q00023027 Cable kit (communication) 0.224 kgFCI2001-D1 A5Q00013100 Fire brigade periphery module 0.482 kgFH7202-Z3 S54400-B70-A101 Housing (Standard) 7.500 kgFH7203-Z3 S54400-B71-A101 Housing (Comfort) 15.000 kgFCM7213-Y3 S54400-B149-A1 Operating add-on (2xLED indicator) 2.600 kgFCM7214-Y3 S54400-B150-A1 Operating add-on (4xLED indicator) 2.800 kgFHA2016-A1 A5Q00020179 19" mounting kit 3.000 kgFN2006-A1 S54400-A109-A1 Fiber network module (SM) 0.770 kgFN2007-A1 S54400-A110-A2 Fiber network module (MM) 0.770 kg

Auxiliary power supply FP2015-A1 S54400-B121-A1 Power supply (70 W) 1.300 kg

FP2004-A1 A5Q00020825 Power supply kit (150 W, A) for installationinto empty housing

1.366 kg

FP2005-A1 A5Q00018779 Power supply kit (150 W, B) for cascading 1.100 kgNetworks (backbone) FN2012-A1 S54400-B152-A Ethernet switch (modular) 0.560 kg

FCA2031 S54400-A153-A1 Connection module (MoNet) 0.020 kg+ 0.050 kg

for cableVN2002-A1 S54400-A43-A1 Ethernet module (MM) 0.030 kgVN2003-A1 S54400-A44-A1 Ethernet module (SM) 0.030 kgFHA2029-A1 S54400-B79-A1 Installation kit (switch, comf.) 1.240 kg

Batteries FA2003-A1 A5Q00019353 Battery (12 V, 7 Ah, VDS) 2.450 kgFA2004-A1 A5Q00019354 Battery (12 V, 12 Ah, VDS) 3.930 kgFA2005-A1 A5Q00019677 Battery (12 V, 17 Ah, VDS) 5.640 kgFA2006-A1 A5Q00019356 Battery (12 V, 26 Ah, VDS) 7.572 kg

License keys FCA2033-A1 S54400-P154-A1 License key (S1) 0.010 kgFCA2034-A1 S54400-P155-A1 License key (S2) 0.010 kgFCA2035-A1 S54400-P156-A1 License key (S3) 0.010 kg

External printer DL3750+ A5Q00023962 Matrix printer (external) 7.300 kgSpare part – A5Q00023963 Color ribbon for matrix printer DL3750+ 0.078 kg