ECE 7800: Renewable Energy Systems Topic 2: Fundamentals of Electric Power Spring 2010 © Pritpal...
-
Upload
damian-ferguson -
Category
Documents
-
view
236 -
download
7
Transcript of ECE 7800: Renewable Energy Systems Topic 2: Fundamentals of Electric Power Spring 2010 © Pritpal...
ECE 7800: Renewable Energy Systems
Topic 2: Fundamentals of Electric Power
Spring 2010
© Pritpal Singh, 2010
AC vs. DC PowerDC is a steady, constant voltage
current power source.
AC is a time varying signal (ideally
sinusoidal) => I = Im cos(ωt +φ)
Power into a resistive load = V2 /R
For any time-varying signal, average
voltage = = Vrms T
dttVT 0
2 )(1
Sinusoidal RMS VoltageFor a sinusoidal waveform, Vrms =
For a wall outlet in the US, Vrms = 120V
and frequency = 60 Hz
For a wall outlet in Europe, Vrms = 240V
and frequency = 50 Hz
pkV2
Ideal LoadsResistive Load:
I = V/R P = I2 R or V2 /R
Capacitive Load:
P = VI cos(2ωt + π/2) ; Pave = 0
Inductive Load:
P = VI cos(2ωt - π/2) ; Pave = 0
Power FactorConsider a general black box as
shown below:
Consider the voltage driving this box
has rms voltage, V and phase angle = 0.
v =
tV cos2
Power Factor (cont’d)The resulting current, i =
… steps to be covered in class …
lead to power output, p is given by:
=> pave = VI cos(θ) = VI (PF)
)cos(2 tI
)cos()2cos( VItVIp
Average = 0
Good vs. Poor Power Factor
Example 2.5
Power Triangle
θ
Example 2.6
ReactivePower, Q(VAR)
Real Power, P(Watts)
P=VIcosθ
Q=VIsinθVolts-amps-reactive
Apparent powerS=VI volt-amps
Three-Wire Single Phase Residential Wiring
Three Phase Systems Commercial systems in the US are
usually produced with 3 phase synchronous generators and with 3 phase transmission lines.
3φ generators are more efficient and offer smoother operation than single phase generators.
3φ transmission and distribution systems use their wires more efficiently saving copper.
Balanced Wye-Connected 3φ To see the advantage of a 3φ system
compared to a single phase system, consider the figure below.
Balanced Wye-Connected 3φ (cont’d)
Suppose that each generator produces the same voltage but 120° shifted in phase. The phase voltages are then given by:
)cos(2 tVva 00VV a
)120cos(2 tVvb
)240cos(2 tVvc
0120VV b
0240VV c
Balanced Wye-Connected 3φ (cont’d) To determine the neutral current, we need to find the current in each phase and add them together. The current in each phase is given by:
The current in the neutral is given by:
…derivation in class
)cos(2 tIia 00II a
)120cos(2 tIib
)240cos(2 tIic
0120II b
0240II c
)120cos()120cos()cos(2 tttIiiii cban
Balanced Wye-Connected 3φ (cont’d)
Derivation of line and phase voltages
Delta-Connected 3φ
Power Quality – Harmonic Distortion
A distortion to the sinusoidal waveform due to high frequency components in the waveform.
Example 2.11 Harmonic Analysis of a Square Wave
Total Harmonic Distortion If the current of a distorted
waveform is given by:
where In is the rms value of the current in the nth harmonic. The rms value of current is given by:
We can show that:
...)3cos2coscos(2 321 tItItIi
...)3cos2coscos(2)( 3212 tItItIiI averms
...23
22
21 IIII rms
Total Harmonic Distortion (cont’d)
Total harmonic distortion (THDi) is a common way of expressing waveform distortion. The THDi is given by:
Example 2.12
1
24
23
22 ...
I
IIITHDi