LAPORAN KULIAH KERJA NYATA-PRAKTEK (KKN-P) PENGADAAN KONSTRUKSI/PEMBELIAN GEDUNG KANTOR DINAS PENDIDIKAN KOTA MALANG
6.7 PERHITUNGAN PONDASI
DATA STRUKTUR
1. Dimensi kolom b = 300 mm
h = 500 mm
Type kolom αs = 30
2. Dimensi Pondasi B = 1.5 m
L = 1.5 m
Ht = 0.45 m
3. Mutu Beton = 20Mpa
4. Mutu Baja = 320 Mpa
5. Besi Tulangan = 16 mm
6. BJ Beton = 24 kN/m3
DATA TANAH
1. Daya dukung tanah σt = 105 kPa (estimasi)
2. Berat tanah γt = 17.20 kN/m3 (estimasi)
3. Tebal tanah diatas ha = 1.55
pondasi
DATA BEBAN
1. Beban P ultimate Pult = 526 kN
2. Beban M ultimate Mult = 20.35 kNm
σ = (Pult / ( B x L ) + (Mu / (1/6 x B (L2 )) + q …..<< σt
TEKNIK SIPIL UNIVERSITAS BRAWIJAYA
79
LAPORAN KULIAH KERJA NYATA-PRAKTEK (KKN-P) PENGADAAN KONSTRUKSI/PEMBELIAN GEDUNG KANTOR DINAS PENDIDIKAN KOTA MALANG
q = Berat pondasi + berat tanah
= ( ht x γc ) + ( ha + γt )
= ( 0.45 x 24 kN/m3 ) + ( 1.55 x 17.2 kN/m3 )
= 37.46 kN/m3
Tegangan yang terjadi pada tanah
σ maks = (Pult / ( B x L ))+ (Mu / (1/6 x B (L2 )) + q …..<< σt
= ( 622 / (1.5m x 1.5m )) + (12.943/ (1/6 x 1.5m x (1.52 ))) + 37.46 <<<σt
= 276.44 + 23.01 + 37.46
= 336.914 ≤ 450 kN/m2
σ min = (Pult / ( B x L )) - (Mu / (1/6 x B (L2 )) + q …..<< σt
= ( 622 / (1.5m x 1.5m )) - (12.943/ (1/6 x 1.5m x (1.52 ))) + 37.46 <<<σt
= 276.44 - 23.01 + 37.46
= 290.895 ≤ 450 kN/m2
a) Kontrol Gaya Geser 1 Arah
ds = 75 + (D / 2)
= 75 +(16 / 2)
= 83 mm
TEKNIK SIPIL UNIVERSITAS BRAWIJAYA
80
LAPORAN KULIAH KERJA NYATA-PRAKTEK (KKN-P) PENGADAAN KONSTRUKSI/PEMBELIAN GEDUNG KANTOR DINAS PENDIDIKAN KOTA MALANG
d = ht – ds
= 450 – 83
= 367 mm
a = ( B / 2 ) – (b/2) – d
= 750 – 250 – 367
= 133 mm
= 0.133 m
σ a = σ min + ( B – a ) x ((σ maks - σ min) / 2 )
= 290.895 + ( 1.5 – 0.133 ) x ((336.914 - 290.895)/2)
= 332.834 kN/m2
Gaya tekan keatas dari tanah ( Vu)
Vu = ( a x B x (σ maks + σ a) / 2
= ( 0.133 x 1.5 ( 336.914 + 332.834 ) /2
= 66.807 kN
Gaya geser yang dapat ditahan oleh beton (Ǿ Vc )
Ǿ Vc = Ǿ x ( 1/6 (fc’)0.5
= 0.75 x ( 1/6 * (20 )0.5
= 307.739 kN
Ǿ Vc > Vu
307.739 > 66.8047…………..AMAN
b) Kontrol Gaya Geser 2 Arah
Dimensi kolom
b = 30 cm = 300 mm
h = 50 cm = 500 mm
b + d = 300 mm + 367 mm = 667 mm………> 0.667 m
TEKNIK SIPIL UNIVERSITAS BRAWIJAYA
81
LAPORAN KULIAH KERJA NYATA-PRAKTEK (KKN-P) PENGADAAN KONSTRUKSI/PEMBELIAN GEDUNG KANTOR DINAS PENDIDIKAN KOTA MALANG
h + d = 500 mm + 367 mm = 867 mm………> 0.867 m
Gaya tekan keatas
Vu = (B2 – (( b + d) x ( h + d))) x ((σ maks + σ min) / 2 )
= ( 1.52 – (0.667 + 0.867 )) x ((336.914 + 290.895)/2)
= 524.7575 kN
βc = ( hkolom / bkolom )
= ( 500 / 300 ) = 1.667
bo = 2 x ((bk + d) + (hk + d))
= 2 x ((300 + 367) + (500 + 367))
= 3068 mm
Gaya geser yang ditahan oleh beton
Vc1 = ( 1 + (2 / βc)) x (1/6 x (f’c0.5) x bo x d)
= ( 1 + (2 / 1.667)) x (1/6 x ( 20) 0.5 x 3068 mm x 367 mm
= 1846.324 kN
Vc2 = ( 2 + (αs x d / bo)) x (1/12 x (f’c0.5) x bo x d)
= ( 1 + (30 x 367 / 3068)) x (1/12 x ( 20) 0.5 x 3068 mm x 367 mm
= 1925.488kN
TEKNIK SIPIL UNIVERSITAS BRAWIJAYA
82
LAPORAN KULIAH KERJA NYATA-PRAKTEK (KKN-P) PENGADAAN KONSTRUKSI/PEMBELIAN GEDUNG KANTOR DINAS PENDIDIKAN KOTA MALANG
Vc3 = 1/3 x (f’c0.5) x bo x d)
= 1/3 x ( 20) 0.5 x 3068 mm x 367 mm
= 1678.476 kN
dari hasil perhitungan Vc diatas, diambil yang terkecil yaitu Vc3 = 1678.476 kN
Ǿ Vc > Vu
0.75 x 1678.476 kN > 524.758 kN
1258.857 kN > 524.758 kN/……………… AMAN
c) Perhitungan Penulangan Pondasi
ds = 75 + D + D/2
= 75 + 16 + (16/2)
= 99 mm = 0.099 m
d = ht – ds
= (0.45 – 0.099)
= 0.351 m = 351 m
x = (B/2 – h/2 )
= ((1500 / 2) – (500/2))
= 500 mm = 0.5 m
σx = σ min + (( B – x ) x (σ max - σ min)/B)
= 290.895 +(( 1.5 – 0.5 ) x (336.914 – 290.895)/1.5)
= 321.574 kN/m3
Mu = 0.5 x σx x ( X2 ) x (1/3 x (σ max - σ min)/( X2 )
= 0.5 x 321.574 kN/m3 x (0.52) x (1/3 x (336.914-290.895)/( 0.52 )
= 41.475 kNm
K = Mu / (Ǿ x b x d2)
= 41475117.284 / ( 0.8 x 1000 x ( 3512)
= 0.421 Mpa
TEKNIK SIPIL UNIVERSITAS BRAWIJAYA
83
LAPORAN KULIAH KERJA NYATA-PRAKTEK (KKN-P) PENGADAAN KONSTRUKSI/PEMBELIAN GEDUNG KANTOR DINAS PENDIDIKAN KOTA MALANG
Kmax = (382.5 x 0.85 x ( 600 + fy – ( 225 x β1 ) x f’c) / (600 + fy)
= (382.5 x 0.85 x ( 600 + 320 – (225 x 0.85 ) x 20) / (600 + 320)
= 5.599
K <<<< Kmax……………………0.421 < 5.599 >>>OK!!!
a’ = (1 – ( 1 – ( 2 x K )/(0.85 x fc’))0.5) x d
= (1- (1- (2 x 0.421 ) / (0.85 x 20 )) 0.5) x 351
= 8.799 mm
As(1) = ( 0.85 x fc’ x a’ x b) / (fy)
= ( 0.85 x 20 x 8.799 x 1000)/ (320 )
= 467.432 mm2
karena fc’ < 31.36 Mpa
maka untuk rumus As(2)
As(2) = (1.4 x b x d )/ fy
= ( 1,4 x 1000 x 351 ) / 320
= 15325.625 mm2
dari perhitungan As(1) dan As(2) diambilyang paling besar = 15325.625 mm2
Menghitung jarak tulangan:
S = (0.25 x π x D2 x b) / As
= (0.25 x π x (162 x 1000) / 15325.625
= 130.865 mm
S < 2 x ht
< 2 x (450mm)
< 900 mm
S < 450 mm
Sehingga dari perhitungan diatas diambil yang terkecil yaitu S = 130.865 mm ~ 130 mm
TEKNIK SIPIL UNIVERSITAS BRAWIJAYA
84LAMPIRAN PERHITUNGAN STAAD PRO