DATA SHEET DB4121-E Issue C Page 1 of 1

Ordering information optical patch cords

8 - - -

Fibre type Code

9/125 μm (OS-2, G.652.D) 1

9/125 μm (OS-2, G.657.A2) 2

9/125 μm (OS-2, G.657.A1) 3

50/125 μm (OM-2) 4

50/125 μm (OM-3) 5

50/125 μm (OM-4) 6

62.5/125 μm (OM-1) 7

Connector type Code

No connector 0

ST (BFOC) 1

SMA 905 2

PBJR Plug 3

PBJR panel connector 4

FC 5

PBSR Plug 6

SC 7

PBSR panel connector 8

MT-RJ 9

DIN B

DIN/APC C

FC/APC (R-type) D

SC/APC E

E-2000 F

E-2000/APC G

FC/APC (N-type) H

LC/APC K

LC L

MU M

Additions

1 = angle, 1. connector

2 = angle, 2. connector

3 = angle, both ends

4 = MT-RJ with pins

Other = internal info

Cable type Code

1-fibre, 2.9 mm OS2=yellow, OM1=grey, OM2=orange, OM3=turquoise, OM4=turquoise (only on request) 2

2-fibre, 2.9 mm OM1, red (only on request) 3

2-fibre, 2.9 mm OS2=yellow, OM1=grey, OM2=orange, OM3=turquoise, OM4=turquoise (only on request) 5

1-fibre, 0.9 mm, tight buffer (100mm strip length), OS2=yellow, OM1=grey, OM2=orange, OM3=turquoise, OM4=turquoise

8

1-fibre, 2.0 mm, OS2=yellow, OM1=grey, OM2=orange, OM3=turquoise, OM4=turquoise A

2-fibre, 2.0 mm, OS2=yellow, OM1=grey, OM2=orange, OM3=turquoise, OM4=turquoise B

2-fibre, 2.0 mm, OM1, red (only on request) D

2-fibre, 2.0 mm, OM1, green (only on request) E

2-fibre, 2.0 mm, OS2, blue F

1-fibre, 2.0 mm, OS2, red (only on request) G

2-fibre, 2.0 mm, OS2, red (only on request) H

1-fibre, 2.8 mm, G.657.A2, white P

1-fibre, 4.5 mm, G.657.A2, white R

2-fibre, 4.5 mm, G.657.A2, white S

Length information

015 = 1.5 m

050 = 5.0 m

100 = 10.0 m

Page 3: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATASHEET DB4100-E Issue C Page 1 of 5

Description

The patch cords can be delivered as:

Pigtail, 0.9 mm Secondary coated fibre* (0.9 mm) with connector in one end.

Patch cord, 0.9 mm Secondary coated fibre* (0.9 mm) with connector in both ends. One patch cord cut in half makes two

pigtails.

Patch cord, 2.0 mm 1-fiber cable (2.0 mm) with connector in both ends.

Duplex patch cord, 2.0 mm 2-fiber cable (2.0 mm, figure 8) with two connectors in each end. The SC and LC connectors are

attached with clips. *Secondary coated fibre is tight buffered fibre, providing around 100 mm strip length.

Specifications Fibre type: ITU-T G.657.A1 compatible with G.652.D

OS-2 EN 50173-1, yellow

Cable: Flame retardant, Zero halogen IEC 60332-3-24, 60332-1-2, 60754-1

Operating wavelength: 1260 - 1625 nm

Operating temperature: -40 °C to 60 °C

Additional loss with fibre bend: <0,05 dB v/1550 nm 10 turns with radius 15 mm

<0,5 dB v/1550 nm 1 turn with radius 10 mm

Patch cords for use in all parts of the network, through the full

CWDM and DWDM ranges.

Can be delivered with most connector types.

PC or APC polish.

Using bend insensitive fibre (G.657.A1).

Delivered in customer specified lengths.

Patch cords - single mode

Page 4: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATASHEET DB4100-E Issue C Page 2 of 5

Specifications cont.

1) There are two types of FC/APC connectors:

FC/APCR (Reduced) with a key width of 2,0 mm (1,97 - 2,02) - often named 2,04 mm and FC/APCN (NTT) with a key width of 2,14 mm (2,09 - 2,14) these two types must not be mixed.

2) The connector features a spring-loaded shutter which closes automatically when the connector is disengaged.

Connector type (single mode)

Standard Ferrule type Polishing technic Insertion loss

(1310/1550 nm)

Return loss Class

according to

IEC 61755-1

Max Typ Max Typ

SC/PC IEC 61 754-4 Zirconia, 2.5 mm PC (0˚ convex)

Colour code blue

0.5 dB 0.15 dB -45 dB -50 dB C2

SC/APC IEC 61 754-4 Zirconia, 2.5 mm APC (8˚ convex)

Colour code green

0.5 dB 0.15 dB -60 dB -65 dB C1

LC/PC IEC 61 754-20 Zirconia, 1.25 mm PC (0˚ convex)

Colour code blue

0.5 dB 0.15 dB -45 dB -50 dB C2

LC/APC IEC 61 754-20 Zirconia, 1.25 mm APC (8˚ convex)

Colour code green

0.5 dB 0.15 dB -60 dB -65 dB C1

FC/PC IEC 61 754-13 Zirconia, 2.5 mm PC (0˚ convex)

Colour code blue

0.5 dB 0.15 dB -45 dB -50 dB C2

FC/APC 1) IEC 61 754-13 Zirconia, 2.5 mm APC (8˚ convex)

Colour code green

0.5 dB 0.15 dB -60 dB -65 dB C1

MU/PC IEC 61 754-6 Zirconia, 1.25 mm PC (0˚ convex)

Colour code blue

0.5 dB 0.15 dB -45 dB -50 dB C2

E2000/

PC 2)

IEC 61 754-15 Zirconia, 2.5 mm PC (0˚ convex)

Colour code blue

0.5 dB 0.15 dB -45 dB -50 dB C2

E2000/

APC 2)

IEC 61 754-15 Zirconia, 2.5 mm APC (8˚ convex)

Colour code green

0.5 dB 0.15 dB -60 dB -65 dB C1

ST/PC IEC 61 754-2 Zirconia, 2.5 mm PC (0˚ convex) 0.65 dB 0.25 dB -45 dB -50 dB D2

Page 5: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATASHEET DB4100-E Issue C Page 3 of 5

Article numbers 8-3XYY-zzz

Examples:

SC/PC:

8-3870-015 Pigtail, SC/PC, 9/OS2/900, 1.5 m, yellow 0.9 mm

8-3877-zzz Patch cord, SC/PC-SC/PC, 9/OS2/900, z m, yellow 0.9 mm

8-3A77-zzz Patch cord, SC/PC-SC/PC, 9/OS2/2000, z m, yellow 2.0 mm

8-3B77-zzz Duplex Patch cord, SC/PC-SC/PC, 9/OS2/2000, z m, yellow 2.0 mm

LC/APC:

8-38K0‐015 Pigtail, LC/APC, 9/OS2/900, 1.5 m, yellow 0.9 mm

8-38KK‐zzz Patch cord, LC/APC‐LC/APC, 9/OS2/900, z m, yellow 0.9 mm

8-3AKK‐zzz Patch cord, LC/APC‐LC/APC, 9/OS2/2000, z m, yellow 2.0 mm

8-3BKK‐zzz Duplex Patch cord, LC/APC‐LC/APC, 9/OS2/2000, z m, yellow 2.0 mm

SC/PC - LC/PC:

8-387L-zzz Patch cord, SC/PC-LC/PC, 9/OS2/900, z m, yellow 0.9 mm

8-3A7L-zzz Patch cord, SC/PC-LC/PC, 9/OS2/2000, z m, yellow 2.0 mm

8-3B7L-zzz Duplex Patch cord, LC/PC-SC/PC, 9/OS2/2000, z m, yellow 2.0 mm

FC/APCR:

8-38DD-zzz Patch cord, FC/APCR-FC/APCR, 9/OS2/900, z m, yellow 0.9 mm

8-3ADD-zzz Patch cord, FC/APCR-FC/APCR, 9/OS2/2000, z m, yellow 2.0 mm

8-3BDD-zzz Duplex Patch cord, FC/APCR-FC/APCR, 9/OS2/2000, z m, yellow 2.0 mm

MU/PC:

8-38M0-015 Pigtail, MU/PC, 9/OS2/900, 1.5 m, yellow 0.9 mm

8-38MM-zzz Patch cord, MU/PC-MU/PC, 9/OS2/900, z m, yellow 0.9 mm

E2000/APC:

8-3AGG-zzz Patch cord, E2000/APC-E2000/APC, 9/OS2/2000, z m, yellow 2.0 mm

8-3BGG-zzz Duplex Patch cord, E2000/APC-E2000/APC, 9/OS2/2000, z m, yellow 2.0 mm

X = Cable type:

8 = Pigtail/patch cord 0.9 mm

A = Patch cord 2.0 mm

B = Duplex patch cord 2.0 mm

Y = Connector type:

0 = No connector 5 = FC/PC L = LC/PC F = E2000/PC

7 = SC/PC D = FC/APCR K = LC/APC G = E2000/APC

E = SC/APC H = FC/APCN 1 = ST/PC

M = MU/PC

zzz = length code: 010 = 1.0 m, 015 = 1.5 m, 100 = 10 m etc.

Page 6: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATASHEET DB4100-E Issue C Page 4 of 5

Interferometric geometrical control

The geometry of the connectors (the ferrule) are tested according to IEC 61755-3-1 (PC) and

IEC 61755-3-2 (APC). The tests are performed at type approval and by sample tests, using an

interferometer. Geometry deviations from standard can cause bit errors. For critical systems,

we are now capable of delivering entire orders or part of orders with interferometric

certificate. Please contact us for details.

Gallery

Patch cord, ST/PC-ST/PC, 9/OS2/900

Patch cord, FC/APC-FC/APC, 9/OS2/2000

Pigtail, SC/PC, 9/OS2/900 Pigtail, LC/APC, 9/OS2/900 Pigtail, FC/PC, 9/OS2/900

Patch cord, E2000/APC-E2000/APC, 9/OS2/900 Patch cord, MU/PC-MU/PC, 9/OS2/900

Patch cord, SC/APC-SC/APC, 9/OS2/2000 Patch cord, LC/PC-LC/PC, 9/OS2/2000

Page 7: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATASHEET DB4100-E Issue C Page 5 of 5

Gallery cont.

Duplex Patch cord, LC/APC-LC/APC, 9/OS2/2000

Patch cord, ST/PC-ST/PC, 9/OS2/2000 Patch cord, LC/PC-LC/PC, 9/OS2/2000 Patch cord, MU/PC-MU/PC, 9/OS2/2000

Duplex Patch cord, ST/PC-ST/PC, 9/OS2/2000 Duplex Patch cord, MU/PC-MU/PC, 9/OS2/2000

Duplex Patch cord, FC/PC-FC/PC, 9/OS2/2000 Duplex Patch cord, E2000/APC-E2000/APC, 9/OS2/2000

Page 8: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATASHEET DB4101-E Issue E Page 1 of 3

Description

The patch cords can be delivered as:

Pigtail, 0.9 mm Secondary coated fibre* (0.9 mm) with connector in one end.

Patch cord, 0.9 mm Secondary coated fibre* (0.9 mm) with connector in both ends. One patch cord cut in half makes two

pigtails.

Patch cord, 2.0 mm 1-fiber cable (2.0 mm) with connector in both ends.

Duplex Patch cord, 2.0 mm 2-fiber cable (2.0 mm, figure 8) with two connectors in each end. The SC and LC connectors are

attached with clips. *Secondary coated fibre is tight buffered fibre, providing around 100 mm strip length.

Specifications Fibre type: OM-1 (62.5/125) EN 50173-1, grey

OM-2 (50/125) EN 50173-1, orange

OM-3 (50/125) EN 50173-1, turquoise

OM-4 (50/125) EN 50173-1, turquoise

Cable: Flame retardant, Zero halogen IEC 60332-3-24, 60332-1-2, 60754-1

Operating temperature: -40 °C to 60 °C

Multi mode patch cords for use in local area network in the

850/1300 nm wavelength ranges.

Can be delivered with most connector types.

Delivered in customer specified lengths.

Patch cords - multi mode

Page 9: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATASHEET DB4101-E Issue E Page 2 of 3

Specifications cont.

The connector colours may deviate from the pictures.

Connector type (Multi mode)

Standard Ferrule type Polishing technic Insertion loss

(850/1300 nm)

Max Typ

SC IEC 61 754-4 Zirconia, 2.5 mm PC (0˚ convex)

Colour code beige

0.5 dB 0.2 dB

LC IEC 61 754-20 Zirconia, 1.25 mm PC (0˚ convex)

Colour code beige

0.5 dB 0.2 dB

FC IEC 61 754-13 Zirconia, 2.5 mm PC (0˚ convex) 0.5 dB 0.2 dB

ST IEC 61 754-2 Zirconia, 2.5 mm PC (0˚ convex) 0.5 dB 0.2 dB

Page 10: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATASHEET DB4101-E Issue E Page 3 of 3

Article numbers 8-WXYY-zzz

Examples:

OM-4 (50/125) SC:

8-6870-015 Pigtail, SC, 50/OM4/900, 1,5 m, turquoise 0.9 mm

8-6877-zzz Patch cord, SC-SC, 50/OM4/900, z m, turquoise 0.9 mm

8-6A77-zzz Patch cord, SC-SC, 50/OM4/2000, z m, turquoise 2.0 mm

8-6B77-zzz Duplex Patch cord, SC-SC, 50/OM4/2000, z m, turquoise 2.0 mm

OM-3 (50/125) SC:

8-5870-015 Pigtail, SC, 50/OM3/900, 1,5 m, turquoise 0.9 mm

8-5877-zzz Patch cord, SC-SC, 50/OM3/900, z m, turquoise 0.9 mm

8-5A77-zzz Patch cord, SC-SC, 50/OM3/2000, z m, turquoise 2.0 mm

8-5B77-zzz Duplex Patch cord, SC-SC, 50/OM3/2000, z m, turquoise 2.0 mm

OM-2 (50/125) LC:

8-48L0-015 Pigtail, LC, 50/125/900, 1,5 m, orange 0.9 mm

8-48LL-zzz Patch cord, LC-LC, 50/125/900, z m, orange 0.9 mm

8-4ALL-zzz Patch cord, LC-LC, 50/125/2000, z m, orange 2.0 mm

8-4BLL-zzz Duplex Patch cord, LC-LC, 50/125/2000, z m, orange 2.0 mm

OM-1 (62.5/125) ST:

8-7810-015 Pigtail, ST, 62.5/125/900, 1,5 m, grey 0.9 mm

8-7811-zzz Patch cord, ST-ST, 62.5/125/900, z m, grey 0.9 mm

8-7A11-zzz Patch cord, ST-ST, 62.5/125/2000, z m, grey 2.0 mm

8-7B11-zzz Duplex Patch cord, ST-ST, 62.5/125/2000, z m, grey 2.0 mm

OM-3 (50/125) SC-LC:

8-587L-zzz Patch cord, SC-LC, 50/OM3/900, z m, turquoise 0.9 mm

8-5A7L-zzz Patch cord, SC-LC, 50/OM3/2000, z m, turquoise 2.0 mm

8-5B7L-zzz Duplex Patch cord, SC-LC, 50/OM3/2000, z m, turquoise 2.0 mm

X = Cable type:

8 = Pigtail/patch cord 0.9 mm

A = Patch cord 2.0 mm

B = Duplex patch cord 2.0 mm

Y = Connector type:

0 = No connector 5 = FC

7 = SC 1 = ST

L = LC

zzz = length code: 010 = 1.0 m, 015 = 1.5 m, 100 = 10 m etc.

W=Fibre type:

4 = Multi mode, OM-2 (50/125)

5 = Multi mode, OM-3 (50/125)

6 = Multi mode, OM-4 (50/125)

7 = Multi mode, OM-1 (62.5/125)

Page 11: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATASHEET DB4103-E Issue A Page 1 of 2

Description

The patch cords can be delivered as:

Patch cord, 0.9 mm Secondary coated fibre* (0.9 mm) with connector in both ends. One patch cord cut in half makes two

pigtails.

Patch cord, 2.0 mm 1-fiber cable (2.0 mm) with connector in both ends.

Duplex patch cord, 2.0 mm 2-fiber cable (2.0 mm, figure 8) with two connectors in each end.

*Secondary coated fibre is tight buffered fibre, providing around 100 mm strip length.

Specifications Standard: IEC 61 754-3

Ferrule type: Zirconia 2.5 mm

Cable: Flame retardant, Zero halogen IEC 60332-3-24, 60332-1-2, 60754-1

Operating temperature: -40 °C to 60 °C

Single mode:

Polishing technic: PC (0˚ convex) Colour code blue

APC (8˚ convex) Colour code green

Fibre type: ITU-T G.657.A1 compatible with G.652.D

OS-2 EN 50173-1, yellow

Insertion loss: < 0.5 dB at 1310/1550 nm < 0.15 dB typical

Return loss: < -45 dB at 1310/1550 nm for PC < -50 dB typical

< -60 dB at 1310/1550 nm for APC < -65 dB typical

Classification: Class C2 (PC), class C1 (APC) IEC 61755-1

Operating wavelength: 1260 - 1625 nm

Additional loss with fibre bend: <0,05 dB v/1550 nm 10 turns with radius 15 mm

<0,5 dB v/1550 nm 1 turn with radius 10 mm

Multi mode:

Polishing technic: PC (0˚ convex)

Fibre type: OM-1 (62.5/125) EN 50173-1, grey

OM-2 (50/125) EN 50173-1, orange

Insertion loss: < 0.5 dB at 850/1300 nm < 0.2 dB typical

Single or multi mode.

Single mode connectors are delivered with PC or APC polish.

Single mode patch cords are delivered with bend insensitive fibre

(G.657.A1).

Delivered in customer specified lengths.

Patch cords, DIN

Page 12: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATASHEET DB4103-E Issue A Page 2 of 2

Article numbers Single mode:

8-38BB-xxx Patch cord, DIN/PC-DIN/PC, 9/125/900, x m, yellow 0.9 mm

8-3ABB-xxx Patch cord, DIN/PC-DIN/PC, 9/125/2000, x m, yellow 2.0 mm

8-3BBB-xxx Duplex Patch cord, DIN/PC-DIN/PC, 9/125/2000, x m, yellow 2.0 mm

8-38CC-xxx Patch cord, DIN/APC-DIN/APC, 9/125/900, x m, yellow 0.9 mm

8-3ACC-xxx Patch cord, DIN/APC-DIN/APC, 9/125/2000, x m, yellow 2.0 mm

8-3BCC-xxx Duplex Patch cord, DIN/APC-DIN/APC, 9/125/2000, x m, yellow 2.0 mm

Multi mode:

OM-1 (62.5/125):

8-78BB-xxx Patch cord, DIN-DIN, 62.5/125/900, x m, grey 0.9 mm

8-7ABB-xxx Patch cord, DIN-DIN, 62.5/125/2000, x m, grey 2.0 mm

8-7BBB-xxx Duplex Patch cord, DIN-DIN, 62.5/125/2000, x m, grey 2.0 mm

OM-2 (50/125):

8-48BB-xxx Patch cord, DIN-DIN, 50/125/900, x m, orange 0.9 mm

8-4ABB-xxx Patch cord, DIN-DIN, 50/125/2000, x m, orange 2.0 mm

8-4BBB-xxx Duplex Patch cord, DIN-DIN, 50/125/1800, x m, orange 2.0 mm

xxx = length: 010 = 1.0 m, 015 = 1.5 m, 100 = 10 m etc.

Gallery

Patch cord, DIN/PC-DIN/PC, 9/125/900 Patch cord, DIN/APC-DIN/APC, 9/125/2000 Duplex patch cord, DIN/PC-DIN/PC, 9/125/2000

Patch cord, DIN-DIN, 62.5/125/900 Patch cord, DIN-DIN, 50/125/2000 Duplex patch cord, DIN-DIN, 50/125/2000

Page 13: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATASHEET DB4143-E Issue B Page 1 of 2

Description

Single mode attenuated patch cord with connector in both ends. Diameter is 2.0 mm and standard length is 1 m.

Specifications Attenuation accuracy*: +/- 13 % For values of 1 - 6 dB nominal

+/- 10 % For values of 7 - 20 dB nominal

Operating wavelength: 1260 - 1620 nm

Operating temperature: -25 °C to 60 °C

* Insertion loss from the connectors will be added

Connectors:

Polishing technic: PC (0˚ convex) Colour code blue

APC (8˚ convex) Colour code green

Insertion loss: < 0.5 dB < 0.15 dB typical

Article numbers ATN-77-xx-010 Attenuated patch cord, SC/PC - SC/PC, xx dB, 1 m

ATN-EE-xx-010 Attenuated patch cord, SC/APC - SC/APC, xx dB, 1 m

ATN-LL-xx-010 Attenuated patch cord, LC/PC - LC/PC, xx dB, 1 m

ATN-KK-xx-010 Attenuated patch cord, LC/APC - LC/APC, xx dB, 1 m

ATN-55-xx-010 Attenuated patch cord, FC/PC - FC/PC, xx dB, 1 m

ATN-DD-xx-010 Attenuated patch cord, FC/APCR - FC/APCR, xx dB, 1 m

ATN-HH-xx-010 Attenuated patch cord, FC/APCN - FC/APCN, xx dB, 1 m

ATN-MM-xx-010 Attenuated patch cord, MU/PC - MU/PC, xx dB, 1 m

ATN-FF-xx-010 Attenuated patch cord, E2000/PC - E2000/PC, xx dB, 1 m

ATN-GG-xx-010 Attenuated patch cord, E2000/APC - E2000/APC, xx dB, 1 m

xx = attenuation: 01, 02, 03, 04, 05, 06, 07, 08, 09, 10, 15, 20 dB May on request be delivered as hybrids patch cords (different connectors in each end). Other lengths may also be delivered.

Single mode attenuated patch cord (1 m).

May be delivered with most connector types, PC- or APC polished.

May be delivered with attenuation from 1 to 20 dB.

Attenuated patch cords

Page 14: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATASHEET DB4143-E Issue B Page 2 of 2

Gallery

Attenuated patch cord, SC/PC Attenuated patch cord, LC/APC Attenuated patch cord, SC/APC

Attenuated patch cord, MU/PC Attenuated patch cord, LC/PC—MU/PC Attenuated patch cord, LC/PC

Page 15: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4122-E Issue B Page 1 of 1

Ordering information pre-terminated cable

Article no. cable

Type of termination

None Terminated on 0.9 mm secondary fibre B Delivered as break-out cable, 3.0 mm jacket

on each fibre

Length information

015 = 15 m

050 = 50 m

100 = 100 m

- ( ) - -

Connector type Code

No connector 0

ST (BFOC) 1

SMA 905 2

PBJR Plug 3

PBJR panel connector 4

FC 5

PBSR Plug 6

SC 7

PBSR panel connector 8

MT-RJ 9

DIN B

DIN/APC C

FC/APC (R-type) D

SC/APC E

E-2000 F

E-2000/APC G

FC/APC (N-type) H

LC/APC K

LC L

MU M

Page 16: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4123-E Issue C Page 1 of 1

AXAI, AXXI:

If more than 24 fibres they are organized in several layers. The first layer is placed in the middle of the cable. Each layer is separated with tape.

QXXI and micro cable (Draka: Nano A-DQ2Y):

If there are many tubes they may be organized in several groups. The first group will then be in the middle of the cable. Each group will start

with red, green, etc.

NB! Other types of cable may have other colour codes — if so follow those codes.

NB! Some other cable types may use patterns with more speckles (in stead of layers) to mark more than 24 fibres.

Colour codes, cable

1 White

2 Red

3 Yellow

4 Green

5 Blue

6 Grey

7 Brown

8 Black

9 Violet

10 Turquoise

11 Orange

12 Pink

13 White with black speckles

14 Red with black speckles

15 Yellow with black speckles

16 Green with black speckles

17 Blue with black speckles

18 Grey with black speckles

19 Brown with black speckles

20 Light blue with black speckles

21 Violet with black speckles

22 Turquoise with black speckles

23 Orange with black speckles

24 Pink with black speckles

Tubes

1 Red

2 Green

3 White (next to the green tube)

4 White (next tube)

5 White

6 White

7 White

8 White

9 White

10 White

11 White

12 White

Fibre in tubes

1 White

2 Red

3 Yellow

4 Green

5 Blue

6 Grey

7 Brown

8 Black

9 Violet

10 Turquoise

11 Orange

12 Pink

Page 17: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4104-E Issue C Page 1 of 3

Description The pre-terminated cable is delivered with connectors at one or both sides. The cable is prepared for installation in FOSS FP70 and FP80

panel* - 1 m of the fibre is protected by a spiral cable wrap and may therefor be placed under the drawer. This simplifies maintenance

because it enables you to take the drawer out of the panel (without loosening the fibres from their guides).

As an option the connector sides of the cable may be protected with a flexible tube. This is often used if this side needs to be pulled for a long

distance. Outside this tube an optional cable pulling grip may be placed if the cable shall be pulled through tubes.

* cable for FP60 may be delivered on request

Specifications

Cable type: Tight buffer, AXAI, yellow Flame retardant, Zero halogen

Tight buffer, AXXI, black Flame retardant, Zero halogen

Diameter cable: 5/6/6.5/8 mm 4/8/12/24-fibre AXAI

9.6/9.6/9.9/10.8 mm 4/8/12/24-fibre AXXI

Tension strength cable: 440/680/900/1400 N 4/8/12/24-fibre AXAI

800 N AXXI

Diameter w/cable grip: 34 mm 4-fibre

40 mm 8/12/24-fibre

Tension strength cable grip: 350 N

Fibre type: ITU-T G.657.A1 (compatible with G.652.D) AXAI

ITU-T G.652.D AXXI

OS-2 EN 50173-1

Insertion loss connectors: < 0.5 dB @ 1310/1550 nm < 0.15 dB typical

Return loss connectors: < -45 dB @ 1310/1550 nm for PC < -50 dB typical

< -60 dB @1310/1550 nm for APC < -65 dB typical

Classification, connectors: Class C2 (PC), class C1 (APC) IEC 61755-1

Operating temperature: -40°C to 60°C

Single mode pre-terminated cable prepared for simple and fast

installation in FOSS FP70 and FP80 panels.

May be delivered with most connector types.

PC‐ or APC‐polished connectors.

4-, 8-, 12– or 24-fibre cable with tight buffer.

Delivered in customer specified lengths.

Pre-terminated cable for panel installation - SM

Page 18: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4104-E Issue C Page 2 of 3

Article numbers

Pre-terminated cable - connectors at one side

x-692120-0-yyy 4-fibre AXAI, SM, x, y m

x-692140-0-yyy 8-fibre AXAI, SM, x, y m

x-692150-0-yyy 12-fibre AXAI, SM, x, y m

x-692180-0-yyy 24-fibre AXAI, SM, x, y m

x-695720-0-yyy 4-fibre AXXI, SM, x, y m

x-695740-0-yyy 8-fibre AXXI, SM, x, y m

x-695750-0-yyy 12-fibre AXXI, SM, x, y m

x-695780-0-yyy 24-fibre AXXI, SM, x, y m

Pre-terminated cable - connectors at both sides

x-692120-x-yyy 4-fibre AXAI, SM, x-x, y m

x-692140-x-yyy 8-fibre AXAI, SM, x-x, y m

x-692150-x-yyy 12-fibre AXAI, SM, x-x, y m

x-692180-x-yyy 24-fibre AXAI, SM, x-x, y m

x-695720-x-yyy 4-fibre AXXI, SM, x-x, y m

x-695740-x-yyy 8-fibre AXXI, SM, x-x, y m

x-695750-x-yyy 12-fibre AXXI, SM, x-x, y m

x-695780-x-yyy 24-fibre AXXI, SM, x-x, y m x = connector type: 0 = No connector 5 = FC/PC L = LC/PC F = E2000/PC 7 = SC/PC D = FC/APCR K = LC/APC G = E2000/APC E = SC/APC H = FC/APCN M = MU/PC yyy = length code: 010 = 10 m, 015 = 15 m, 100 = 100 m etc. Other cable types may be delivered on request.

Accessories 990140 Protection cable-end, w/cable grip

990141 Protection cable-end, without/cable grip

Ordered length 2,5 m

1 m spiral cable wrap + 1,5 m free fibre

Page 19: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4104-E Issue C Page 3 of 3

Gallery

Pre-terminated cable Pre-terminated cable in FP70 panel Pre-terminated cable in FP70 panel - with drawer open

Pre-terminated cable with protection cable-end w/cable grip

Page 20: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4105-E Issue B Page 1 of 3

Description The pre-terminated cable is delivered with connectors at one or both sides. The cable is prepared for installation in FOSS FP70 and FP80

panel* - 1 m of the fibre is protected by a spiral cable wrap and may therefor be placed under the drawer. This simplifies maintenance

because it enables you to take the drawer out of the panel (without loosening the fibres from their guides).

As an option the connector sides of the cable may be protected with a flexible tube. This is often used if this side needs to be pulled for a long

distance. Outside this tube an optional cable pulling grip may be placed if the cable shall be pulled through tubes.

* cable for FP60 may be delivered on request

Specifications

Cable type: Tight buffer, AXAI, several colours (see fibre type) Flame retardant, Zero halogen

Tight buffer, AXXI, black Flame retardant, Zero halogen

Diameter cable: 5/6/6.5/8 mm 4/8/12/24-fibre AXAI

9.6/9.6/9.9/10.8 mm 4/8/12/24-fibre AXXI

Tension strength cable: 440/680/900/1400 N 4/8/12/24-fibre AXAI

800 N AXXI

Diameter w/cable grip: 34 mm 4-fibre

40 mm 8/12/24-fibre

Tension strength cable grip: 350 N

Fibre type (acc. to EN 50173-1): OM-1 (62.5/125) AXAI: grey

OM-2 (50/125) AXAI: orange

OM-3 (50/125) AXAI: turquoise

Insertion loss connectors: < 0.5 dB @ 850/1300 nm < 0.2 dB typical

Operating temperature: -40°C to 60°C

Multi mode pre-terminated cable prepared for simple and fast

installation in FOSS FP70 and FP80 panels.

May be delivered with most connector types.

4-, 8-, 12– or 24-fibre cable with tight buffer.

Delivered in customer specified lengths.

Pre-terminated cable for panel installation, MM

Page 21: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4105-E Issue B Page 2 of 3

Article numbers

Fibre type: 50/125 (OM-3)

x-692123-x-yyy 4-fibre AXAI, 50/OM3, x-x, y m

x-692143-x-yyy 8-fibre AXAI, 50/OM3, x-x, y m

x-692153-x-yyy 12-fibre AXAI, 50/OM3, x-x, y m

x-692183-x-yyy 24-fibre AXAI, 50/OM3, x-x, y m

x-695723-x-yyy 4-fibre AXXI, 50/OM3, x-x, y m

x-695743-x-yyy 8-fibre AXXI, 50/OM3, x-x, y m

x-695753-x-yyy 12-fibre AXXI, 50/OM3, x-x, y m

x-695783-x-yyy 24-fibre AXXI, 50/OM3, x-x, y m

Fibre type: 50/125 (OM-2)

x-692122-x-yyy 4-fibre AXAI, 50/125, x-x, y m

x-692142-x-yyy 8-fibre AXAI, 50/125, x-x, y m

x-692152-x-yyy 12-fibre AXAI, 50/125, x-x, y m

x-692182-x-yyy 24-fibre AXAI, 50/125, x-x, y m

x-695722-x-yyy 4-fibre AXXI, 50/125, x-x, y m

x-695742-x-yyy 8-fibre AXXI, 50/125, x-x, y m

x-695752-x-yyy 12-fibre AXXI, 50/125, x-x, y m

x-695782-x-yyy 24-fibre AXXI, 50/125, x-x, y m

Fibre type: 62.5/125 (OM-1)

x-692124-x-yyy 4-fibre AXAI, 62.5/125, x-x, y m

x-692144-x-yyy 8-fibre AXAI, 62.5/125, x-x, y m

x-692154-x-yyy 12-fibre AXAI, 62.5/125, x-x, y m

x-692184-x-yyy 24-fibre AXAI, 62.5/125, x-x, y m

x-695724-x-yyy 4-fibre AXXI, 62.5/125, x-x, y m

x-695744-x-yyy 8-fibre AXXI, 62.5/125, x-x, y m

x-695754-x-yyy 12-fibre AXXI, 62.5/125, x-x, y m

x-695784-x-yyy 24-fibre AXXI, 62.5/125, x-x, y m x = connector type: 0 = No connector, 1 = ST, 5 = FC, 7 = SC, L = LC yyy = length code: 010 = 10 m, 015 = 15 m, 100 = 100 m etc. Other cable types may be delivered on request.

Accessories 990140 Protection cable-end, w/cable grip

990141 Protection cable-end, without/cable grip

Ordered length 2,5 m

Page 22: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4105-E Issue B Page 3 of 3

Gallery

Pre-terminated cable, OM1 Pre-terminated cable, OM1, in FP70 panel Pre-terminated cable, OM3, in FP70 panel

Page 23: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4106-E Issue C Page 1 of 3

Description A manifold is attached at the end of the cable to fan out the fibres in a controlled way. Each fibre is individually protected by a 3.0 mm tube.

Cables with 2 or 4 fibres will have a free fibre length of ca. 0,35 m. For cables with more than 4 fibres the 2 shortest will be 0,60 m, the length

will then increase with 8 cm for every fibre pair (every 4.th fibre for 24-fibre cable). The manifold type will depend on the number of fibres and

the diameter of the cable.

As an option the connector side of the cable may be protected with a flexible tube. This is often used if this side needs to be pulled for a long

distance. Outside this tube an optional cable pulling grip may be placed if the cable shall be pulled through tubes.

Specifications

Cable type: Tight buffer, AXAI, yellow Flame retardant, Zero halogen

Tight buffer, AXXI, black Flame retardant, Zero halogen

Diameter cable: 4.5/5/6/6.5/8 mm 2/4/8/12/24-fibre AXAI

9.6/9.6/9.9/10.8 mm 4/8/12/24-fibre AXXI

Tension strength cable: 325/440/680/900/1400 N 2/4/8/12/24-fibre AXAI

800 N AXXI

Dimensions manifold (fan-out): Ø 14 mm x 36 mm 2-fibre

Ø 20 mm x 75 mm 4-fibre

Ø 17 mm x 105 mm 8-fibre

Ø 30 mm x 130 mm 12-fibre

Ø 40 mm x 140 mm 24-fibre

Diameter w/cable grip: 34 mm 2/4-fibre

40 mm 8/12-fibre

52 mm 24-fibre

Tension strength cable grip: 350 N

Fibre type: ITU-T G.657.A1 (compatible with G.652.D) AXAI

ITU-T G.652.D AXXI

OS-2 EN 50173-1

Insertion loss connectors: < 0.5 dB @ 1310/1550 nm < 0.15 dB typical

Return loss connectors: < -45 dB @ 1310/1550 nm for PC < -50 dB typical

< -60 dB @1310/1550 nm for APC < -65 dB typical

Classification, connectors: Class C2 (PC), class C1 (APC) IEC 61755-1

Operating temperature: -40°C to 60°C

May be delivered with most connector types.

PC‐ or APC‐polished connectors.

2-, 4-, 8-, 12– or 24-fibre cable with tight buffer.

Delivered in customer specified lengths.

Pre-terminated cable, Breakout - single mode

Page 24: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4106-E Issue C Page 2 of 3

Article numbers

Breakout cable - connectors at one side

x-B692110-0-yyy 2-fibre AXAI, SM, x, y m

x-B692120-0-yyy 4-fibre AXAI, SM, x, y m

x-B692140-0-yyy 8-fibre AXAI, SM, x, y m

x-B692150-0-yyy 12-fibre AXAI, SM, x, y m

x-B692180-0-yyy 24-fibre AXAI, SM, x, y m

x-B695720-0-yyy 4-fibre AXXI, SM, x, y m

x-B695740-0-yyy 8-fibre AXXI, SM, x, y m

x-B695750-0-yyy 12-fibre AXXI, SM, x, y m

x-B695780-0-yyy 24-fibre AXXI, SM, x, y m

Breakout cable - connectors at both sides

x-B692110-x-yyy 2-fibre AXAI, SM, x-x, y m

x-B692120-x-yyy 4-fibre AXAI, SM, x-x, y m

x-B692140-x-yyy 8-fibre AXAI, SM, x-x, y m

x-B692150-x-yyy 12-fibre AXAI, SM, x-x, y m

x-B692180-x-yyy 24-fibre AXAI, SM, x-x, y m

x-B695720-x-yyy 4-fibre AXXI, SM, x-x, y m

x-B695740-x-yyy 8-fibre AXXI, SM, x-x, y m

x-B695750-x-yyy 12-fibre AXXI, SM, x-x, y m

x-B695780-x-yyy 24-fibre AXXI, SM, x-x, y m x = connector type: 0 = No connector 5 = FC/PC L = LC/PC F = E2000/PC 7 = SC/PC D = FC/APCR K = LC/APC G = E2000/APC E = SC/APC H = FC/APCN M = MU/PC yyy = length code: 010 = 10 m, 015 = 15 m, 100 = 100 m etc. Other cable types may be delivered on request.

Accessories 990140 Protection cable-end, w/cable grip

990141 Protection cable-end, without/cable grip

Ordered length Free fibre

Page 25: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4106-E Issue C Page 3 of 3

Gallery

Break-out cable Break-out cable with protection cable-end, w/cable grip

Manifold with 2 fibres

Manifold with 12 fibres Manifold with 8 fibres

Page 26: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4107-E Issue A Page 1 of 3

Description A manifold is attached at the end of the cable to fan out the fibres in a controlled way. Each fibre is individually protected by a 3.0 mm tube.

Cables with 2 or 4 fibres will have a free fibre length of ca. 0,35 m. For cables with more than 4 fibres the 2 shortest will be 0,60 m, the length

will then increase with 8 cm for every fibre pair (every 4.th fibre for 24-fibre cable). The manifold type will depend on the number of fibres and

the diameter of the cable.

As an option the connector side of the cable may be protected with a flexible tube. This is often used if this side needs to be pulled for a long

distance. Outside this tube an optional cable pulling grip may be placed if the cable shall be pulled through tubes.

Specifications

Cable type: Tight buffer, AXAI, several colours (see fibre type) Flame retardant, Zero halogen

Tight buffer, AXXI, black Flame retardant, Zero halogen

Diameter cable: 4.5/5/6/6.5/8 mm 2/4/8/12/24-fibre AXAI

9.6/9.6/9.9/10.8 mm 4/8/12/24-fibre AXXI

Tension strength cable: 325/440/680/900/1400 N 2/4/8/12/24-fibre AXAI

800 N AXXI

Dimensions manifold (fan-out): Ø 14 mm x 36 mm 2-fibre

Ø 20 mm x 75 mm 4-fibre

Ø 17 mm x 105 mm 8-fibre

Ø 30 mm x 130 mm 12-fibre

Ø 40 mm x 140 mm 24-fibre

Diameter w/cable grip: 34 mm 2/4-fibre

40 mm 8/12-fibre

52 mm 24-fibre

Tension strength cable grip: 350 N

Fibre type (acc. to EN 50173-1): OM-1 (62.5/125) AXAI: grey

OM-2 (50/125) AXAI: orange

OM-3 (50/125) AXAI: turquoise

Insertion loss connectors: < 0.5 dB @ 850/1300 nm < 0.2 dB typical

Operating temperature: -40°C to 60°C

May be delivered with most connector types.

2-, 4-, 8-, 12– or 24-fibre cable with tight buffer.

Delivered in customer specified lengths.

Pre-terminated cable, Breakout - multi mode

Page 27: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4107-E Issue A Page 2 of 3

Article numbers

Fibre type: 50/125 (OM-3)

x-B692113-x-yyy 2-fiber AXAI, 50/OM3, x-x, y m

x-B692123-x-yyy 4-fibre AXAI, 50/OM3, x-x, y m

x-B692143-x-yyy 8-fibre AXAI, 50/OM3, x-x, y m

x-B692153-x-yyy 12-fibre AXAI, 50/OM3, x-x, y m

x-B692183-x-yyy 24-fibre AXAI, 50/OM3, x-x, y m

x-B695723-x-yyy 4-fibre AXXI, 50/OM3, x-x, y m

x-B695743-x-yyy 8-fibre AXXI, 50/OM3, x-x, y m

x-B695753-x-yyy 12-fibre AXXI, 50/OM3, x-x, y m

x-B695783-x-yyy 24-fibre AXXI, 50/OM3, x-x, y m

Fibre type: 50/125 (OM-2)

x-B692112-x-yyy 2-fiber AXAI, 50/125, x-x, y m

x-B692122-x-yyy 4-fibre AXAI, 50/125, x-x, y m

x-B692142-x-yyy 8-fibre AXAI, 50/125, x-x, y m

x-B692152-x-yyy 12-fibre AXAI, 50/125, x-x, y m

x-B692182-x-yyy 24-fibre AXAI, 50/125, x-x, y m

x-B695722-x-yyy 4-fibre AXXI, 50/125, x-x, y m

x-B695742-x-yyy 8-fibre AXXI, 50/125, x-x, y m

x-B695752-x-yyy 12-fibre AXXI, 50/125, x-x, y m

x-B695782-x-yyy 24-fibre AXXI, 50/125, x-x, y m

Fibre type: 62.5/125 (OM-1)

x-B692114-x-yyy 2-fiber AXAI, 62.5/125, x-x, y m

x-B692124-x-yyy 4-fibre AXAI, 62.5/125, x-x, y m

x-B692144-x-yyy 8-fibre AXAI, 62.5/125, x-x, y m

x-B692154-x-yyy 12-fibre AXAI, 62.5/125, x-x, y m

x-B692184-x-yyy 24-fibre AXAI, 62.5/125, x-x, y m

x-B695724-x-yyy 4-fibre AXXI, 62.5/125, x-x, y m

x-B695744-x-yyy 8-fibre AXXI, 62.5/125, x-x, y m

x-B695754-x-yyy 12-fibre AXXI, 62.5/125, x-x, y m

x-B695784-x-yyy 24-fibre AXXI, 62.5/125, x-x, y m x = connector type: 0 = No connector, 1 = ST, 5 = FC, 7 = SC, L = LC yyy = length code: 010 = 10 m, 015 = 15 m, 100 = 100 m etc. Other cable types may be delivered on request.

Accessories 990140 Protection cable-end, w/cable grip

990141 Protection cable-end, without/cable grip

Ordered length Free fibre

Page 28: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4107-E Issue A Page 3 of 3

Gallery

Break-out cable, OM-1 with 2 fibres and LC connectors

Break-out cable, OM-1 with 12 fibres and ST connectors

Break-out cable, OM-1 with 8 fibres and ST connectors

Manifold with 12 fiber Manifold with 8 fiber Manifold with 2 fiber

Page 29: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4108-E Issue C Page 1 of 3

Description A manifold is attached at the end of the cable to fan out the fibres in a controlled way. Each fibre is individually protected by a 3.0 mm tube.

Cables with 2 or 4 fibres will have a free fibre length of ca. 0,35 m. For cables with more than 4 fibres the 2 shortest will be 0,60 m, the length

will then increase with 8 cm for every fibre pair (every 4.th fibre for 24-fibre cable). The manifold type will depend on the number of fibres

and the diameter of the cable.

As an option the connector side of the cable may be protected with a flexible tube. This is often used if this side needs to be pulled for a long

distance. Outside this tube an optional cable pulling grip may be placed if the cable shall be pulled through tubes.

Specifications

Cable:

Cable type: Tight buffer, AICI, black, Flame retardant, Zero halogen NEK 606 Code F6

Loose tube, QFCI, black, Flame retardant, Zero halogen NEK 606 Code F1

Diameter cable: 8.2/9.4/10.3/12.0 mm 4/8/12/24-fibre AICI

13,5 mm QFCI

Tension strength at installation: 700/800/1200/1700 N 4/8/12/24-fibre AICI

1500 N QFCI

Dimensions manifold (fan-out): Ø 14 mm x 36 mm 2-fibre

Ø 20 mm x 75 mm 4-fibre

Ø 17 mm x 105 mm 8-fibre

Ø 30 mm x 130 mm 12-fibre

Ø 40 mm x 140 mm 24-fibre

Diameter w/cable grip: 34 mm 2/4-fibre

40 mm 8/12-fibre

52 mm 24-fibre

Tension strength cable grip: 350 N

Operating temperature: -40°C to 60°C

Fibre (single mode):

Fibre type: ITU-T G.652.D

OS-2 EN 50173-1

Insertion loss connectors: < 0.5 dB @ 1310/1550 nm < 0.15 dB typical

Return loss connectors: < -45 dB @ 1310/1550 nm for PC < -50 dB typical

< -60 dB @1310/1550 nm for APC < -65 dB typical

Classification, connectors: Class C2 (PC), class C1 (APC) IEC 61755-1

Fibre (multimode):

Fibre type: OM-1 (62.5/125), OM-2 (50/125) or OM-3 (50/125) EN 50173-1

Insertion loss connectors: < 0.5 dB @ 850/1300 nm < 0.2 dB typical

Cable according to NEK 606 for use offshore and on ship.

Single- or multi mode.

May be delivered with most connector types.

2-, 4-, 8-, 12- or 24-fibre cable.

Delivered in customer specified lengths.

Pre-terminated cable, Breakout - offshore

Page 30: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4108-E Issue C Page 2 of 3

Ordered length Free fibre

Article numbers

Single mode:

x-B69zz10-x-yyy 2-fibre zz, SM, x-x, y m

x-B69zz20-x-yyy 4-fibre zz, SM, x-x, y m

x-B69zz40-x-yyy 8-fibre zz, SM, x-x, y m

x-B69zz50-x-yyy 12-fibre zz, SM, x-x, y m

x-B69zz80-x-yyy 24-fibre zz, SM, x-x, y m

Multimode:

Fibre type: 50/125 (OM-3)

x-B69zz13-x-yyy 2-fibre zz, 50/OM3, x-x, y m

x-B69zz23-x-yyy 4-fibre zz, 50/OM3, x-x, y m

x-B69zz43-x-yyy 8-fibre zz, 50/OM3, x-x, y m

x-B69zz53-x-yyy 12-fibre zz, 50/OM3, x-x, y m

x-B69zz83-x-yyy 24-fibre zz, 50/OM3, x-x, y m

Fibre type: 50/125 (OM-2)

x-B69zz12-x-yyy 2-fibre zz, 50/125, x-x, y m

x-B69zz22-x-yyy 4-fibre zz, 50/125, x-x, y m

x-B69zz42-x-yyy 8-fibre zz, 50/125, x-x, y m

x-B69zz52-x-yyy 12-fibre zz, 50/125, x-x, y m

x-B69zz82-x-yyy 24-fibre zz, 50/125, x-x, y m

Fibre type: 62.5/125 (OM-1)

x-B69zz14-x-yyy 2-fibre zz, 62.5/125, x-x, y m

x-B69zz24-x-yyy 4-fibre zz, 62.5/125, x-x, y m

x-B69zz44-x-yyy 8-fibre zz, 62.5/125, x-x, y m

x-B69zz54-x-yyy 12-fibre zz, 62.5/125, x-x, y m

x-B69zz84-x-yyy 24-fibre zz, 62.5/125, x-x, y m x = connector type: Multimode: 0 = No connector 1 = ST 5 = FC 7 = SC L = LC Single mode: 0 = No connector 5 = FC/PC L = LC/PC F = E2000/PC 7 = SC/PC D = FC/APCR K = LC/APC G = E2000/APC E = SC/APC H = FC/APCN M = MU/PC yyy = length code: 010 = 10 m, 015 = 15 m, 100 = 100 m etc. zz = cable type: 54 = AICI, 41 = QFCI

Accessories 990140 Protection cable-end, w/cable grip

990141 Protection cable-end, without/cable grip

Page 31: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4108-E Issue C Page 3 of 3

Gallery

Break-out cable, with 4 fibre and SC connectors Manifold with 2 fibres Manifold with 4 fibres

Manifold with 12 fibres Manifold with 8 fibres

Page 32: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4109-E Issue D Page 1 of 2

Description A manifold is attached at the end of the cable to fan out the fibres in a controlled way. Each fibre is individually protected by a 3.0 mm tube.

The tactical cable may be delivered on a ruggedized cable reel. A wide selection of reels with stand are available, see separated data sheet for

details.

As an option the connector side of the cable may be protected with a flexible tube. This is often used if this side needs to be pulled for a long

distance. Outside this tube an optional cable pulling grip may be placed if the cable shall be pulled through tubes.

Dust caps attached to the cable may also be delivered.

Specifications

Cable

Cable type: Military tactical cable, black Polyurethane

Military tactical cable LSZH, black Polyurethane, LSZH (Low Smoke Zero Halogen)

Diameter: 5.0/5.5 mm 2/4 fibre

Tension strength: 1800 N

Crush resistance: 440 N/cm

Bend diameter: 80/88 mm 2/4-fibre

Dimensions manifold (fan-out): Ø 14 mm x 36 mm 2-fibre

Ø 20 mm x 75 mm 4-fibre

Diameter w/cable grip: 34 mm

Tension strength cable grip: 350 N

Operating temperature: -40°C to 60°C

Fibre (single mode)

Fibre type: ITU-T G.657.D

OS-1 EN 50173-1

Insertion loss connectors: < 0.5 dB @ 1310/1550 nm < 0.15 dB typical

Return loss connectors: < -45 dB @ 1310/1550 nm for PC < -50 dB typical

< -60 dB @1310/1550 nm for APC < -65 dB typical

Classification, connectors: Class C2 (PC), class C1 (APC) IEC 61755-1

Fibre (multi mode)

Fibre type: OM-1 (62.5/125), OM-2 (50/125) EN 50173-1

Insertion loss connectors: < 0.5 dB @ 850/1300 nm < 0.2 dB typical

Single– or multi mode.

May be delivered with most connector types.

2- or 4-fibre military tactical cable for extreme conditions.

May be delivered on ruggedized reel with stand.

Delivered in customer specified lengths.

Pre-terminated tactical cable

Page 33: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4109-E Issue D Page 2 of 2

Ordered length Free fibre

Article numbers Single mode

x-902MIL9-x-yyy 2-fibre tactical cable, 9/125, x-x, y m

x-904MIL9-x-yyy 4-fibre tactical cable, 9/125, x-x, y m

x-902MILG9-x-yyy 2-fibre tactical cable LSZH, 9/125, x-x, y m

x-904MILG9-x-yyy 4-fibre tactical cable LSZH, 9/125, x-x, y m

Multi mode:

Fibre type: 50/125 (OM-2)

x-902MIL50-x-yyy 2-fibre tactical cable, 50/125, x-x, y m

x-904MIL50-x-yyy 4-fibre tactical cable, 50/125, x-x, y m

x-902MILG50-x-yyy 2-fibre tactical cable LSZH, 50/125, x-x, y m

x-904MILG50-x-yyy 4-fibre tactical cable LSZH, 50/125, x-x, y m

Fibre type: 62.5/125 (OM-1)

x-902MIL62-x-yyy 2-fibre tactical cable, 62/125, x-x, y m

x-904MIL62-x-yyy 4-fibre tactical cable, 62/125, x-x, y m

x-902MILG62-x-yyy 2-fibre tactical cable LSZH, 62/125, x-x, y m

x-904MILG62-x-yyy 4-fibre tactical cable LSZH, 62/125, x-x, y m x = connector type: Multi mode: 0 = No connector 1 = ST 5 = FC 7 = SC L = LC Single mode: 0 = No connector 5 = FC/PC L = LC/PC F = E2000/PC 7 = SC/PC D = FC/APCR K = LC/APC G = E2000/APC E = SC/APC H = FC/APCN M = MU/PC yyy = length code: 010 = 10 m, 015 = 15 m, 100 = 100 m etc. Free fibre length is 0,35—0,4 m

Accessories 990140 Protection cable-end, w/cable grip

990141 Protection cable-end, without/cable grip

EFA0212ASS Dust cap, ST, w/cable tie

EFA0215ASS Dust cap, SC, w/cable tie

23303128 Dust cap, FC, w/cable tie

Gallery

Tactical cable, with 4 fibres and SC connectors Manifold with 2 fibres Manifold with 4 fibres

Page 34: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4111-E Issue D Page 1 of 3

Description The digital broadband technology within the fibre to the home segment is evolving rapidly. To

be able to offer services with the quality expected by the customer, cables and components

used must have the necessary quality.

When running cable in a house the cable may be exposed to more severe bends than are

normal in other parts of the network. This requires a fibre that is more insensitive to these

types of effects. In the Subscriber patch cord/Subscriber cable a single mode fibre according to

ITU-T G.657.A2 is used which meets these requirements.

There are two variants:

Subscriber patch cord White cable with a connector in both ends. Suited for

connecting wall outlet and the home central.

Subscriber cable White cable with connector in one end. The connector is either

connected to the wall outlet or directly to the home central.

The other end is typically spliced to the incoming cable (from

the broadband supplier) in an external subscriber box.

Subscriber cable

w/0.9 mm ending White cable with 1 or 2 fibres and connector(s) in one end.

Terminated side have a stripped ending of 65cm with 0.9 mm

fibre. This enables fibre storage inside the wall outlet or home

central. The connector is either connected to the wall outlet or

directly to the home central. The other end is typically spliced

to the incoming cable (from the broadband supplier) in an

external subscriber box.

The subscriber cable is meant for indoor use, but may also be used outdoors for a short

distance. Outdoor it should be put on the wall (not on/in the ground), also make sure that

water is prevented from coming into the cable-end. The cable is UV-resistant, but there may

be some miscolouring over time.

Optical patch cord/cable for use at private subscribers.

Using bend insensitive fibre according to ITU-T G.657.A2.

2.8 mm white, unmarked subscriber patch cord.

4.5 mm white, unmarked subscriber cable.

Meets fire safety requirements (flame retardant, Zero halogen).

Delivered in customer specified lengths.

Subscriber patch cord and Subscriber cable

Subscriber

box

Here the Subscriber cable is used directly to the home central.

Example usage of Subscriber patch cord

Here the 2-fibre Subscriber cable w/0.9 mm ending is used directly to the home central. This enables fibre storage inside the central.

Subscriber

box

Page 35: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4111-E Issue D Page 2 of 3

65 cm Ordered length

Subscriber cable w/0.9 mm ending (valid for both 1- and 2-fibre)

Specifications Connector type: SC or LC IEC 61 754-4 (SC), IEC 61 754-20 (LC)

Ferrule type: Zirconia 2.5 mm

Polishing: PC (0˚ convex) Colour code blue

APC (8˚ convex) Colour code green

Cable: Tight buffer, white Flame retardant, Zero halogen

Fibre type: ITU-T G.657.A2 compatible with G.652.D

OS-2 EN 50173-1

Insertion loss connectors: < 0.5 dB @ 1310/1550 nm < 0.15 dB typical

Return loss connectors: < -45 dB @ 1310/1550 nm for PC < -50 dB typical

< -60 dB @1310/1550 nm for APC < -65 dB typical

Classification, connectors: Class C2 (PC), class C1 (APC) IEC 61755-1

Operating wavelength : 1260 - 1625 nm

Operating temperature: -20°C to 60°C

Additional loss with sharp bends: <0,02 dB @/1550 nm 6 rounds w/radius of 15 mm

<0,1 dB @/1550 nm 1 round w/radius of 10 mm

<0,5 dB @/1550 nm 1 round w/radius of 7.5 mm

Article numbers Subscriber patch cord

8-2P77-xxx Subscriber patch cord, SC/PC-SC/PC, 9/OS2/2800, xx.x m, white 2.8 mm

8-2PEE-xxx Subscriber patch cord, SC/APC-SC/APC, 9/OS2/2800, xx.x m, white 2.8 mm

8-2P7L-xxx Subscriber patch cord, SC/PC-LC/PC, 9/OS2/2800, xx.x m, white 2.8 mm

Subscriber cable

8-2R70-xxx Subscriber cable, SC/PC, 9/OS2/4500, xx.x m, white 4.5 mm

8-2RE0-xxx Subscriber cable, SC/APC, 9/OS2/4500, xx.x m, white 4.5 mm

8-2RL0-xxx Subscriber cable, LC/PC, 9/OS2/4500, xx.x m, white 4.5 mm

1-fibre subscriber cable w/0.9 mm ending

8-2R70-xxx-E/D Subscriber cable, SC/PC, 9/OS2/4500, 0.9 mm end, xx.x m, white 4.5 mm

8-2RE0-xxx-E/D Subscriber cable, SC/APC, 9/OS2/4500, 0.9 mm end, xx.x m, white 4.5 mm

8-2RL0-xxx-E/D Subscriber cable, LC/PC, 9/OS2/4500, 0.9 mm end, xx.x m, white 4.5 mm

2-fibre subscriber cable w/0.9 mm ending

8-2S70-xxx-E/D Subscriber cable, 2 x SC/PC, 9/OS2/4500, 0.9 mm end, xx.x m, white 4.5 mm

8-2SE0-xxx-E/D Subscriber cable, 2 x SC/APC, 9/OS2/4500, 0.9 mm end, xx.x m, white 4.5 mm

8-2SL0-xxx-E/D Subscriber cable, 2 x LC/PC, 9/OS2/4500, 0.9 mm end, xx.x m, white 4.5 mm

xxx = length code: 010 = 10 m, 015 = 15 m, 100 = 100 m etc. Other cable types may be delivered on request.

Page 36: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4111-E Issue D Page 3 of 3

Gallery

Subscriber patch cord connected between wall outlet and the home central

Wall outlet with incoming Subscriber cable with 0.9 mm ending and SC/PC connector

Wall outlet with incoming Subscriber cable with SC/PC connector

Subscriber box with a splice between incoming cable and internal cable (the Subscriber cable)

Example installation with both Subscriber patch cord and Subscriber cable

Subscriber patch cord with SC/PC - LC/PC Subscriber patch cord with ending w SC/PC Subscriber cable with SC/APC

Subscriber patch cord or Subscriber cable connected to the home central

Page 37: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4139-E Issue C Page 1 of 2

Description The digital broadband technology within the fibre to the home segment is evolving rapidly. To be able to offer services with the quality

expected by the customer, cables and components used must have the necessary quality.

When running cable in a house the cable may be exposed to more severe bends than are normal in other parts of the network. This requires a

fibre that is more insensitive to these types of effects. In the Subscriber cable PRO a single mode fibre according to ITU-T G.657.A2 is used

which meets these requirements.

The Subscriber cable is a white cable with 2 connectors in one end. The terminated end is

stripped with 20cm of “free fibre” (other lengths may be delivered on request). The PC-

connector is on the white fibre and the APC-connector is on the red fibre. In the 4-fibre cable

2 of the fibres have connectors and the other 2 are without, all 4 have 50 cm of “free fibre”.

The connectors are either connected to the wall outlet or directly to the home central. The

other end is typically spliced to the incoming cable (from the broadband supplier) in an

external subscriber box.

Subscriber cable PRO is meant for indoor use, but may also be used outdoors for a short

distance. Outdoor it should be put on the wall (not on/in the ground), also make sure that

water is prevented from coming into the cable-end. The cable is UV-resistant, but there may be some miscolouring over time.

Optical cable with bend insensitive fibre for use at private

subscribers.

4.5 mm white cable (2 or 4 fibres).

Using bend insensitive fibre according to ITU-T G.657.A2.

2 connectors (1 PC and 1 APC) in one end.

Delivered in customer specified lengths.

Subscriber cable, hybrid

Example usage for Subscriber cable PRO

Subscriber

box

Page 38: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4139-E Issue C Page 2 of 2

Specifications Connector type: SC IEC 61 754-4

Ferrule type: Zirconia 2.5 mm

Polishing: PC (0˚ convex) Colour code blue

APC (8˚ convex) Colour code green

Cable: Tight buffer, white Flame retardant, Zero halogen

Fibre type: ITU-T G.657.A2 compatible with G.652.D

OS-2 EN 50173-1

Insertion loss connectors: < 0.5 dB @ 1310/1550 nm < 0.15 dB typical

Return loss connectors: < -45 dB @ 1310/1550 nm for PC < -50 dB typical

< -60 dB @1310/1550 nm for APC < -65 dB typical

Classification, connectors: Class C2 (PC), class C1 (APC) IEC 61755-1

Operating temperature: -20°C to 60°C

Additional loss with sharp bends: <0,02 dB @/1550 nm 6 rounds w/radius of 15 mm

<0,1 dB @/1550 nm 1 round w/radius of 10 mm

<0,5 dB @/1550 nm 1 round w/radius of 7.5 mm

Article numbers

8-2CD2F-xxx 2-fibre Subscriber cable, SC/PC + SC/APC, x m, white 4.5 mm

8-2CD4F-xxx 4-fibre Subscriber cable, SC/PC + SC/APC, x m, white 4.5 mm

yyy = length code: 010 = 10 m, 015 = 15 m, 100 = 100 m etc. Other cable types may be delivered on request.

Gallery

Ordered length 20 cm

for 2 fibre

50 cm for 4 fibre

Subscriber cable, 2-fibre Subscriber cable, 4-fibre

Page 39: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4154-E Issue C Page 1 of 7

Description

We deliver cables with MTP in both ends and fan-out cables or modules for converting from MTP to LC or SC. The MTP connector has 12 or 24

fibres in each connector. It comes as female (without guide pins) or as male (with guide pins). Cables for cross connecting and fan-out cables

will normally be female, while modules will be male. If 2 MTP connectors are connected in an adapter one must be male and the other female.

Controlling polarity is always important, making sure that correct fibre end up where it should be. Especially with many fibres in each

connector as it is here, it is convenient with a standard system. Several ways of handling polarity when using MTP connectors are defined. The

most common way is called method A. This method gives you a “one-to-one” connection of the fibres through the system. The MTP cable

used is then called polarity A. Equipment delivered by Foss is using this method as standard, but other varieties may be ordered.

For direct connection between electronics cables with polarity B (12-pin/40G) or polarity X (24-pin/100G) is used.

This is described in more detail in Appendix: Polarity.

MTP is a registered trademark of US Conec, Ltd

Specifications

Standards: IEC 61 754-7

Ferrule type: PPS thermoplastic

Polishing technic: PC (0˚ convex)

APC (8˚ convex)

Cable: Flame retardant, Zero halogen IEC 60332-3-24, 60332-1-2, 60754-1

Diameter cable: MTP: 3/3.6 mm 12/24 fibre

LC and SC: 2 mm

Operating temperature: -10˚C to 60˚C

Multimode:

Fibre type: OM-3 (50/125) EN 50173-1, turquoise

OM-4 (50/125) EN 50173-1, turquoise

Insertion loss: MTP: < 0.35 dB at 850/1300 nm < 0.1 dB typical

LC and SC: < 0.2 dB at 850/1300 nm

MTP is an improved, high performance MPO-connector.

MTP may be connected to all standard MPO-connectors.

Single– or multimode.

Modules and fan-outs converts from MTP to LC or SC.

Cables with MTP in both ends.

Single mode are delivered with bend insensitive fibre (G.657.A1).

Delivered in customer specified lengths.

MTP cables, fan-outs and modules

Page 40: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4154-E Issue C Page 2 of 7

Specifications cont.

Single mode:

Fibre type: ITU-T G.657.A1 Compatible with G.652.D

OS-2 EN 50173-1, yellow

Insertion loss: MTP/APC: < 0.35 dB at 1310/1550 nm < 0.1 dB typical

LC/PC and SC/PC: < 0.2 dB at 1310/1550 nm

LC/APC and SC/APC: < 0.3 dB at 1310/1550 nm

Return loss: MTP/APC: < -60 dB at 1310/1550 nm

LC/PC and SC/PC: < -50 dB at 1310/1550 nm

LC/APC and SC/APC: < -65 dB at 1310/1550 nm

Classification: MTP/APC Class C1 IEC 61755-1

LC/PC and SC/PC Class C2 IEC 61755-1

LC/APC and SC/APC Class C1 IEC 61755-1

Article number MTP cables

MTPF-FT-M4B12-yyy-MTPF-FT-A Cable, 12 fibre 50/OM4, MTP(F)-MTP(F), yyy m, pol A

MTPF-FT-M4B24-yyy-MTPF-FT-A Cable, 24 fibre 50/OM4, MTP(F)-MTP(F), yyy m, pol A

MTPF-FT-M3B12-yyy-MTPF-FT-A Cable, 12 fibre 50/OM3, MTP(F)-MTP(F), yyy m, pol A

MTPF-FT-M3B24-yyy-MTPF-FT-A Cable, 24 fibre 50/OM3, MTP(F)-MTP(F), yyy m, pol A

MTPF-AF-SMB12-yyy-MTPF-AF-A Cable, 12 fibre 9/OS2, MTP/A(F)-MTP/A(F), yyy m, pol A

MTPF-AF-SMB24-yyy-MTPF-AF-A Cable, 24 fibre 9/OS2, MTP/A(F)-MTP/A(F), yyy m, pol A

Module MTP-LC

FPM76/12LCOM4-MTP-A Module, 12 LC - MTP(M), 50/OM4, pol. A

FPM76/24LCOM4-MTP-A Module, 24 LC - MTP(M), 50/OM4, pol. A

FPM76/12LCOM3-MTP-A Module, 12 LC - MTP(M), 50/OM3, pol. A

FPM76/24LCOM3-MTP-A Module, 24 LC - MTP(M), 50/OM3, pol. A

FPM76/12SLC-MTPA-A Module, 12 LC/PC - MTP/A(M), 9/OS2, pol. A

FPM76/24SLC-MTPA-A Module, 24 LC/PC - MTP/A(M), 9/OS2, pol. A

FPM76/12SLCA-MTPA-A Module, 12 LC/APC - MTP/A(M), 9/OS2, pol. A

FPM76/24SLCA-MTPA-A Module, 24 LC/APC - MTP/A(M), 9/OS2, pol. A

xxx = length: 010 = 1.0 m, 015 = 1.5 m, 100 = 10 m etc. MTP/A(F) = APC/Female MTP(F) = PC/Female MTP/A(M) = APC/Male MTP(M) = PC/Male Other modules, cables, polarities and lengths may be delivered on request.

Page 41: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4154-E Issue C Page 3 of 7

Article number cont.

Fan-out

MTPF-FT-M4B12F1.5-20-2.5-LC-PC Fan-Out, 12-fibre 50/OM4, MTP(F)-LC, 2.5 m

MTPF-FT-M3B12F1.5-20-2.5-LC-PC Fan-Out, 12-fibre 50/OM3, MTP(F)-LC, 2.5 m

MTPF-AF-SMB12F1.5-20-2.5-LC-PC Fan-Out, 12-fibre 9/OS2, MTP/A(F)-LC/PC, 2.5 m

Direct cables 40G

MTPF-FT-M4B12-yyy-MTPF-FT-B Cable, 12 fibre 50/OM4, MTP(F)-MTP(F), yyy m, pol B

MTPF-FT-M3B12-yyy-MTPF-FT-B Cable, 12 fibre 50/OM3, MTP(F)-MTP(F), yyy m, pol B

MTPF-AF-SMB12-yyy-MTPF-AF-B Cable, 12 fibre 9/OS2, MTP/A(F)-MTP/A(F), yyy m, pol B

Direct cables 100G

MTPF-FT-M4B24-yyy-MTPF-FT-X Cable, 24 fibre 50/OM4, MTP(F)-MTP(F), yyy m, pol X

MTPF-FT-M3B24-yyy-MTPF-FT-X Cable, 24 fibre 50/OM3, MTP(F)-MTP(F), yyy m, pol X

MTPF-AF-SMB24-yyy-MTPF-AF-X Cable, 24 fibre 9/OS2, MTP/A(F)-MTP/A(F), yyy m, pol X xxx = length: 010 = 1.0 m, 015 = 1.5 m, 100 = 10 m etc. MTP/A(F) = APC/Female MTP(F) = PC/Female MTP/A(M) = APC/Male MTP(M) = PC/Male Other modules, cables, polarities and lengths may be delivered on request.

Accessories

FPM76100 Panel, modular, 12-slot, 3U

FPM76105 Panel, modular, 3-slot, 1U

FPM76106 Lid, 1U panel

FPM76190 Blanking plate, 1-slot

Total length: 2.5 m

1.5 m

Fan-out

Page 42: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4154-E Issue C Page 4 of 7

Interferometric geometrical control

The geometry of the connectors (the ferrule) are tested at type approval and by sample tests,

using an interferometer. Geometry deviations from standard can cause bit errors. For critical

systems, we are now capable of delivering entire orders or part of orders with interferometric

certificate. Please contact us for details.

Gallery

MTP-fan-out SM MTP fan-out OM3/4 MTP module

MTP-connector male MTP-connector female MTP-cable OM3/4

MTP-module w/cable MTP-cable SM - APC

Page 43: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4154-E Issue C Page 5 of 7

Appendix: Polarity Method A gives you a “one-to-one” connection of the fibres through the system. It is easy to implement, but requires 2 different patch cords

in each end.

MTP connectors/adapters The connectors comes in two versions:

Also the adapter comes in 2 versions:

For method A only adapters with "key-up to key-down" are used.

Patch cords 2 types of double patch cords are defined:

Double patch cords - straight:

Double patch cords - crossed:

For method A one of each type patch cord are needed - one in each end. When using LC– or SC-connectors you will normally order crossed

patch cords for all connections. Then you will open the clip on one side and switch the connectors at installation. In that way you avoid

keeping track of storing the correct type before installing. Straight patch cords may also be delivered.

Male (with guide pins) Female (without guide pins)

Key-up to key-down Key-up to key-up

The grey colour shows placing in the duplex adapter – not real colours

Page 44: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4154-E Issue C Page 6 of 7

Method A

Method A means using cables and path cords in a “one-to-one” configuration as shown in the figure. You only have to make sure to use a

crossed patch cords in one end and a straight patch cords in the other end.

Because the decision of using crossed patch cord is done at installation the method is flexible with regards to type of equipment connected

and number of fibres used (e.g. 3 fibres for video). The method also means using the same modules/MTP-cables (fan-out) in both ends.

Double patch cord - crossed

B

A

B

A

key up

/down

Key up

/down

M

M

F

F Optical signal path

M = Male

F = Female

Module

Module

MTP-cable with

polarity A

Rx

Tx

Rx

Tx

MTP-connector 1 MTP-connector 2

1 BLUE 2 ORANGE 3 BROWN 4 GREEN 5 GREY 6 WHITE 7 RED 8 BLACK 9 YELLOW 10 PURPLE 11 PINK 12 AQUA

BLUE 1 ORANGE 2 GREEN 3 BROWN 4 GREY 5 WHITE 6 RED 7 BLACK 8 YELLOW 9 PURPLE 10 PINK 11 AQUA 12

BLUE/ 13 ORANGE/ 14 GREEN/ 15 BROWN/ 16 GREY/ 17 WHITE/ 18 RED/ 19 BLACK/ 20 YELLOW/ 21 PURPLE/ 22 PINK/ 23 AQUA/ 24

13 BLUE/ 14 ORANGE/ 15 BROWN/ 16 GREEN/ 17 GREY/ 18 WHITE/ 19 RED/ 20 BLACK/ 21 YELLOW/ 22 PURPLE/ 23 PINK/ 24 AQUA/

Double patch cord - straight

Page 45: DATA SHEET D4121 Ordering information optical patch cords52ebad10ee97eea25d5e-d7d40819259e7d3022d9ad53e3694148.r84.cf… · Ordering information optical patch cords. 8 - ... Patch

DATA SHEET DB4154-E Issue C Page 7 of 7

Direct connection

There are mainly 2 cases where you will need other MTP-cables than polarity A.

Direct connection between electronics (Tx to Rx):

For 24-pin/100G you will need an MTP cable with polarity X as shown below.

For 12-pin/40G you will need an MTP cable with polarity B also shown below.

Extending the cable:

To extend a cable - or a connection in a panel - without changing the polarity of the system around you may use a "key up to key down"

adapter with:

MTP cable with polarity X for 24-pin (as shown below)

MTP cable with polarity A for 12-pin (as shown on the former page).

MTP-cable with polarity X used directly between electronics.

MTP-connector 1 MTP-connector 2

MTP-cable with polarity B used directly between electronics.

MTP-connector 1 MTP-connector 2

Polarity X

Polarity B

MTP-cable with polarity X used as cable extension.

1 BLUE 2 ORANGE 3 BROWN 4 GREEN 5 GREY 6 WHITE 7 RED 8 BLACK 9 YELLOW 10 PURPLE 11 PINK 12 AQUA

BLUE 1 ORANGE 2 GREEN 3 BROWN 4 GREY 5 WHITE 6 RED 7 BLACK 8 YELLOW 9 PURPLE 10 PINK 11 AQUA 12

BLUE/ 13 ORANGE/ 14 GREEN/ 15 BROWN/ 16 GREY/ 17 WHITE/ 18 RED/ 19 BLACK/ 20 YELLOW/ 21 PURPLE/ 22 PINK/ 23 AQUA/ 24

13 BLUE/ 14 ORANGE/ 15 BROWN/ 16 GREEN/ 17 GREY/ 18 WHITE/ 19 RED/ 20 BLACK/ 21 YELLOW/ 22 PURPLE/ 23 PINK/ 24 AQUA/

1 BLUE 2 ORANGE 3 BROWN 4 GREEN 5 GREY 6 WHITE 7 RED 8 BLACK 9 YELLOW 10 PURPLE 11 PINK 12 AQUA

BLUE 1 ORANGE 2 GREEN 3 BROWN 4 GREY 5 WHITE 6 RED 7 BLACK 8 YELLOW 9 PURPLE 10 PINK 11 AQUA 12

BLUE/ 13 ORANGE/ 14 GREEN/ 15 BROWN/ 16 GREY/ 17 WHITE/ 18 RED/ 19 BLACK/ 20 YELLOW/ 21 PURPLE/ 22 PINK/ 23 AQUA/ 24

13 BLUE/ 14 ORANGE/ 15 BROWN/ 16 GREEN/ 17 GREY/ 18 WHITE/ 19 RED/ 20 BLACK/ 21 YELLOW/ 22 PURPLE/ 23 PINK/ 24 AQUA/