CPM-41 DIGITAL MICRO-PROCESS METER … DIGITAL MICRO-PROCESS METER Features Input: Universal input...

12
CPM-41 DIGITAL MICRO-PROCESS METER <<Operating Manual>> Features z Input: Universal input programmed by the front keys DC Voltage: 0 ~ 10V DC Current: 0 ~ 20mA Thermocouple: K J E T R B S N C Type RTD: Pt100Ω or JPt100Ω Strain Gauge: 0 ~ 100mV Sampling Time: 50mS Accuracy: DC Voltage: 0.04% F.S ± 1 digit DC Current: 0.04% F.S ± 1 digit Thermocouple: 0.2% F.S ± 1 digit RTD: 0.2% F.S ± 1 digit Strain Gauge: 0.04% F.S ± 1 digit z Display: Screens: Measuring Screen: 5 digits 0.56” high brightness 7 segment LED Index Screen: 5 digits 0.28” high brightness 7 segment LED Alarm Indicators: 4 high brightess red squares LED External Control Indicators: 3 high brightness green squares LED Communicating Indicators: 1 high brightness red square LED Display Range: -19999~19999 Red Settung Range: -19999~19999 Green MAX. / MIN. saving Reading may correspond with: PV MAX. HOLD MIN. HOLD Reading by COMM port of RS485 Easily programmed from the front panel z Control Functions: Control Output: Output Types: z Standard RELAY Contacts: SPDT; 3A / 115V, 2A / 230V z Optional Open Collector output: 4 alarm relays Start Delay, Run Delay, Off Delay Time& Hysteresis Used to be Differential Alarm Output with HI or LOW setpoint Used to be DO, output tripped by RS485 directly Analog Output: DC Voltage 0~10V & DC Current 0~20mA selection Programmable 15BIT D/A convertor (Response time: 100mS 0~90% step wave) Auto / Manual Output selection Setting Analog Output by Ccommunication Supply DC 24V Exciting Power for 2-wire sensors Communicating Output: Communication: RS 485 Protocol: Modbus RTU Mode Baud Rate: 2400 / 4800 / 9600 / 19200 / 38400 bps Communication Address: 1~255 Master-Slave function by communication External Control Input: CON1 / CON2 / CON3 programming: z BANK1~BANK3 selection z Tare Zero z Data Hold z MAX. HOLD / MIN. HOLD / RESET z Used to be DI, External Control Input may read by RS485 z Other Functions: Decimal Point selection Password Protection Memorize by EEPROM over 10 years z Optional Functions: Math functions: Square / Root / Absolutely / Reverse 16 segment for non-linearization Banks for preset: Bank functions: BANK1 ~ BANK3 Parameters for preset: DB,SDT,ALM-1~ALM-4,MD1~MD4,HY1~HY4,RD 1~RD4,FD1~FD4 ORDERING INFORMATION: CPM - Optional function Input Type 4 Analogue output RS 485 port Excitation supply Aux. Power CODE OPTIONAL FUNCTION CODE INPUT RANGE CODE INPUT RANGE CODE RELAY OUTPUT CODE CODE EXCITATION SUPPLY CODE AUX. POWER 41 Standard A2 0 ~ 10 mA S1 1.0 mV/V 4 HH/Hi/Lo/LL N N None N None A AC 115/230 V A3 0 ~ 20 mA S2 1.25 mV/V B 0 ~ 10 mA E1 DC 10 V A3 AC 380 V A4 4 ~ 20 mA S3 1.5 mV/V C 0 ~ 20 mA E2 DC 12 V A4 AC 415 V 42 Math functions: reverse/square/ square root/ absolutely V4 0 ~ 5 V S4 2.0 mV/V D 4 ~ 20 mA E3 DC 24 V A24 AC 24 V 43 3 Banks V5 0 ~ 10 V S5 3.0 mV/V 2 0 ~ 5 V EO Specify D24 DC 24 V V6 1 ~ 5 V S6 4.0 mV/V 3 0 ~ 10 V D48 DC 48 V 44 16 segments for non-linear V7 -10 ~ 0 ~ +10V S7 5.0 mV/V 4 1 ~ 5 V D11 DC 110 V TC Thermocouple S8 10.0 mV/V 5 -10 ~ 0 +10 V AO Specify AC 45 Full function above including Pt Pt100S9 20.0 mV/V 8 RS 485 DO Specify DC UI Universal input RP 50 ~ 50KCSEC -1- CPM41-2003/05

Transcript of CPM-41 DIGITAL MICRO-PROCESS METER … DIGITAL MICRO-PROCESS METER Features Input: Universal input...

CPM-41 DIGITAL MICRO-PROCESS METER <<Operating Manual>> Features Input: Universal input programmed by the front keys

DC Voltage: 0 ~ 10V DC Current: 0 ~ 20mA Thermocouple: K J E T R B S N C Type RTD: Pt100Ω or JPt100Ω Strain Gauge: 0 ~ 100mV

Sampling Time: 50mS Accuracy:

DC Voltage: 0.04% F.S ±1 digit DC Current: 0.04% F.S ±1 digit Thermocouple: 0.2% F.S ±1 digit RTD: 0.2% F.S ±1 digit Strain Gauge: 0.04% F.S ±1 digit

Display: Screens:

Measuring Screen: 5 digits 0.56” high brightness 7 segment LED

Index Screen: 5 digits 0.28” high brightness 7 segment LED

Alarm Indicators: 4 high brightess red squares LED

External Control Indicators: 3 high brightness green squares LED

Communicating Indicators: 1 high brightness red square LED

Display Range: -19999~19999 Red Settung Range: -19999~19999 Green MAX. / MIN. saving Reading may correspond with:

PV MAX. HOLD MIN. HOLD Reading by COMM port of RS485

Easily programmed from the front panel Control Functions: Control Output:

Output Types: Standard RELAY Contacts: SPDT; 3A /

115V, 2A / 230V Optional Open Collector output:

4 alarm relays Start Delay, Run Delay, Off Delay Time&

Hysteresis Used to be Differential Alarm Output with HI or

LOW setpoint Used to be DO, output tripped by RS485 directly

Analog Output: DC Voltage 0~10V & DC Current 0~20mA

selection Programmable 15BIT D/A convertor (Response

time: 100mS 0~90% step wave) Auto / Manual Output selection Setting Analog Output by Ccommunication Supply DC 24V Exciting Power for 2-wire sensors

Communicating Output: Communication: RS 485 Protocol: Modbus RTU Mode Baud Rate: 2400 / 4800 / 9600 / 19200 / 38400

bps Communication Address: 1~255 Master-Slave function by communication

External Control Input: CON1 / CON2 / CON3 programming:

BANK1~BANK3 selection Tare Zero Data Hold MAX. HOLD / MIN. HOLD / RESET Used to be DI, External Control Input may

read by RS485 Other Functions: Decimal Point selection Password Protection Memorize by EEPROM over 10 years

Optional Functions: Math functions: Square / Root / Absolutely / Reverse 16 segment for non-linearization Banks for preset:

Bank functions: BANK1 ~ BANK3 Parameters for preset:

DB,SDT,ALM-1~ALM-4,MD1~MD4,HY1~HY4,RD1~RD4,FD1~FD4

ORDERING INFORMATION:

CPM - Optional function — Input Type — 4 — Analogue

output RS 485

port — Excitation supply — Aux. Power

CODE OPTIONAL FUNCTION CODE INPUT

RANGE CODE INPUT RANGE CODE RELAY

OUTPUT CODE CODE EXCITATION SUPPLY CODE AUX. POWER

41 Standard A2 0 ~ 10 mA S1 1.0 mV/V 4 HH/Hi/Lo/LL N N None N None A AC 115/230 V A3 0 ~ 20 mA S2 1.25 mV/V B 0 ~ 10 mA E1 DC 10 V A3 AC 380 V A4 4 ~ 20 mA S3 1.5 mV/V C 0 ~ 20 mA E2 DC 12 V A4 AC 415 V

42 Math functions: reverse/square/ square root/ absolutely V4 0 ~ 5 V S4 2.0 mV/V D 4 ~ 20 mA E3 DC 24 V A24 AC 24 V

43 3 Banks V5 0 ~ 10 V S5 3.0 mV/V 2 0 ~ 5 V EO Specify D24 DC 24 V V6 1 ~ 5 V S6 4.0 mV/V 3 0 ~ 10 V D48 DC 48 V 44 16 segments for

non-linear V7 -10 ~ 0 ~ +10V S7 5.0 mV/V 4 1 ~ 5 V D11 DC 110 V TC Thermocouple S8 10.0 mV/V 5 -10 ~ 0 +10 V AO Specify AC 45 Full function above

including Pt Pt100Ω S9 20.0 mV/V 8 RS 485 DO Specify DC UI Universal input RP 50 ~ 50KΩ

CSEC -1- CPM41-2003/05

EXTERROR DESCRIPTION: INSTALLATION

96.0

48.0

92.0+0.8

44.0+0.8PANEL CUTOUT

FRONT VIEW

Unit: mm

7.0 20 98.0

DIMENSIONS

PANEL CUTOUT: 92+0.8(W) x 44+0.8(H) mm 1.0~8.0 mm

FIXED HOLDER: 120 mm (L) / W M4

Kg/cm2

FUN ENT

CON1CON2CON3

COM HHHILOLL

FRONT PANEL Kg/cm2

FUNENT

CON1 CON2 CON3

COM HH H I

LOL L

Measuring Screen

Control StatusIndications

Operating Keys

Index Screen

Engineer Unit

WIRING DIAGRAM

Analogue O utput

21 22 24 25 23 27 28 26 29 30 31 33 32 34

R 2(HI) R S-485

R x Tx

a c b a c b

R 3(LO )

A+ B - a c a c

R 1(HH ) R 4(LL)

13 11 12 CJ 2 4 5 3 7 8 6 9 1

C O N 3 C O N 1 C O M C O N 2

Excit. Supply External C ontrol

AC 230VAC 115V D C Power

AUX. PO W ER S IG NAL IN PUT

m A

V / TC P t100Ω A B b

RELAY FUNCTIONS

Start Delay: Run Delay / Off Delay Time & Hysteresis:

Start Delay (SD)

Deadband (DB)

HI Setpoint

Alarm Relay ON

Inhibit Inhibit

HI Setpoint

Alarm Relay ON

Hystereis

OFF D

ELAY

RUN

DELA

Y

Differential output with Hi or Low setpoint

HH Relay Mode: Differential mode HH Setpoint = -X HH Relay trip level = Hi setpoint - X

Hi Setpoint

Hi Relay ON

Lo Setpoint

HH Relay ON

- X

Lo Relay

LL Relay Mode: Differential mode LL Setpoint = Y LL Relay trip level = Lo setpoint + Y

Hi Setpoint

Lo Relay ON

Lo Setpoint

LL Relay

Y

Hi Relay ON

ON

KEY FUNCTIONS:

KEY NAME DESCRIPTION ENT ENTER 1. In the MEASURING PAGE, it allows users to switch the ALARM REMINDING (ALM-1, ALM-2…rESEt )

2. In the setting parameters, it allows users to save the data and enter to next parameter

UP 1. In the MEASURING PAGE, it allows usersto return the last ALARM REMINDING (ALM-1, ALM-2…rESEt ) 2. In the setting parameters, it allows users to increase the digits or switch the parameters

DOWN 1. In the setting parameters, it allows users to decrease the digits or switch the parameters 2. In the LEVEL PAGES, it allows users to return the last LEVEL PAGE 3. In the PARAMETER PAGES, it allowsusers to return the last PARAMETER PAGE

SHIFT 1. In the programming parameters, it allows users to move the cursor 2. In the LEVEL PAGES, it allows you to enter this page to select the level functions for setting

ENT + COMPOUND-1 In the LEVEL PAGES & PARAMETER PAGES, press ENT + can return to the MEASURING PAGE, and thedata will not be saved if users do not press ENT to save the revised data

+ COMPOUND-2 In the setting parameters, press + can return to the LEVEL page

NO KEYS In the LEVEL PAGES & PARAMETER PAGES, it will return to MEASURING PAGE automatically when users donot press any keys about 2 minutes

CSEC -2- CPM-41- 2003/05

POWER ON

“INPUT TYPE REMINDING"

“HI & LOW SCALE REMINDING"

"ALM-1 REMINDING"

"ALM-1 SETPOINT"

"ALM-2 REMINDING"

"ALM-2 SETPOINT"

"ALM-3 REMIND"

"ALM-3 SETPOINT"

"ALM-4 REMINDING"

"ALM-4 SETPOINT"

“SELF-DIAGNOSIS”

“MEASURING PAGE"

"ALARM-1 SETPOINT SETTING"

"ALARM-2 SETPOINT SETTING"

"ALARM-3 SETPOINT SETTING"

"ALARM-4 SETPOINT SETTING"

“MIN. SAVING"

“RESET SETTING"

“PASSWORD SETTING"

ENT ENT ENT ENT ENT

ENT ENT ENT

“USER LEVER PAGE"

“INPUT LEVER SETTING"

“OUTPUT LEVER SETTING"

“INPUT TYPE SETTING"

“INPUT SIGNAL SETTING"

“DECIMAL POINT SETTING"

“UNIT SETTING"

“DISPLAY HI SCALE PAGE"

“DISPLAY LOW SCALE PAGE"

“INPUT SIGNAL SPAN SETTING"

“INPUT SIGNAL ZERO SETTING"

“DISPLAY FUNCTION SETTING"

“MOVING AVG. SETTING"

“DISPLAY AVG. SETTING"

“ALARM LEVER SETTING"

“ALARM START DELAY SETTING"

“A/D CONVERTER ERROR ALARM

SETTING"

“ALM_1 MODE SETTING"

“ALM_1 HYSETERESIS

SETTING"

“ALM_1 RUN DELAY SETTING"

“ALM_1 OFF DELAY SETTING"

“ALM_2 MODE SETTING"

“ALM_2 HYSETERESIS

SETTING"

“ALM_2 RUN DELAY SETTING"

“ALM_2 OFF DELAY SETTING"

“ALM_3 MODE SETTING"

" ALM_3 OFF DELAY SETTING "

" ALM_4 MODE SETTING "

" ALM_4 HYSETERESIS

SETTING "

" ALM_4 RUN DELAY SETTING "

" ALM_4 OFF DELAY SETTING "

" ALM_3 HYSETERESIS

SETTING "

" ALM_3 RUN DELAY SETTING "

“ALARM DEAD BAND SETTING"

"CON-1 SETTING"

"CON-2 SETTING"

"CON-3 SETTING"

“ANALOG OUTPUT TYPE

SETTING"

“ANALOG OUTPUT SIGNAL

SETTING"

“ANALOG OUTPUT HI

SCALE SETTING"

“ANALOG OUTPUT LOW

SCALE SETTING"

“ANALOG OUTPUT SPAN ADJUSTMENT"

“ANALOG OUTPUT ZERO ADJUSTMENT"

“ADDRESS SETTING"

“BAUD RATE

SETTING"

“PARITY SETTING"

“CODE SETTING

ENT ENT ENT ENT ENT ENT ENT

ENT ENT ENT ENT

ENT ENT ENT ENT ENT ENT ENT ENT

ENTENTENTENTENT

ENT

“Password Correction" “Default=1000"

“No"

“Yes"

ENT ENT ENT ENT ENT ENT ENT

ENT ENT ENT ENT

ENT ENT ENT ENT ENT

ENT

ENT

ENT

ENT

ENT ENT

ENT

“Pres s + to a llow you re turn the USER LEVEL PAGE“

“MAX. SAVING"

“Press to select the LEVEL”

“Pres s + to a llow you re turn the USER LEVEL PAGE“

“Pres s + to a llow you re turn the USER LEVEL PAGE“

OPERATING DIAGRAM:

CSEC -3- CPM-41- 2003/05

OPERATING SETPS: ALARM REMINDING PAGES: STEP DISPLAY DESCRIPTION OTHER

1 POWER ON

Confrim the wiring and specification, turn on the power. The decription of ERROR CODE, please refer to the Appendant.

2

"SELF-DIAGNOSIS”

Enter to SELF-DIAGNOSIS

3

"INPUT TYPE REMINDING"

Enter to INPUT TYPE REMINDING

4

"HI & LOW SCALE

REMINDING"

Enter to HI & LOW SCALE REMINDING The upper screen is HI SCALE The lower screen is LOW SCALE

5

"ALM-1 REMINDING"

If the SELF-DIAGNOSIS is OK, it will enter to MEASURING PAGE Roll to ALM-1 REMINDING

6

"ALM-1 SETPOINT"

Roll to ALM-1 SETPOINT

7

"ALM-2 REMINDING"

Roll to ALM-2 REMINDING

8

"ALM-2 SETPOINT "

Roll to ALM-2 SETPOINT

9

"ALM-3 REMINDING "

Roll to ALM-3 REMINDING

10

"ALM-3 SETPOINT"

Roll to ALM-3 SETPOINT

11

"ALM-4 REMINDING"

Roll to ALM-4 REMINDING

12

"ALM-4 SETPOIN"

Roll to ALM-4 SETPOINT

1

"ALM-1 REMINDING "

Reture to ALM-1 REMINDING

CSEC -4- CPM-41- 2003/05

ALARM SETTING OPERATING: Press ENT + to allow you return the MEASURING PAGE *STEP U-0* In the parameter setting status, press to allow you return the last page

STEP DISPLAY DESCRIPTION SWITCH OTHERS In the MEASURING PAGE, press ENT to enter the ALARM SETTING

1. Press ENT to enter the ALARM-1 SETPOINT SETTING U-0

"MEASURING PAGE"

ENT

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the value 3. Press ENT to confirm and save the parameter

U-1

"ALARM-1 SETPOINT

SETTING" ENT 4. Press ENT to enter the ALARM-2 SETPOINT SETTING

Default: 0 Range: 0 ~ HI.SC

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the value 3. Press ENT to confirm and save the parameter

U-2

"ALARM-2 SETPOINT

SETTING" ENT 4. Press ENT to enter the ALARM-3 SETPOINT SETTING

Default: 0 Range: 0 ~ HI.SC

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the value 3. Press ENT to confirm and save the parameter

U-3

"ALARM-3 SETPOINT

SETTING" ENT 4. Press ENT to enter the ALARM-4 SETPOINT SETTING

Default: 0 Range: 0 ~ HI.SC

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the value 3. Press ENT to confirm and save the parameter

U-4

"ALARM-4 SETPOINT

SETTING" ENT 4. Press ENT to enter the MAX. SAVING PAGE

Default: 0 Range: 0 ~ HI.SC

1. Press ENT to enter the MIN. SAVING PAGE

U-5

"MAX. SAVING PAGE"

ENT

1. Press ENT to enter the RESET SETTING

U-6

"MIN. SAVING PAGE"

ENT

1. Press and the LED will be flashed and can be set

2. Press to move the cursor, press or to change the

parameters

3. Press ENT to confirm and save the parameter U-7

"RESET SETTING"

ENT 4. Press ENT to enter the PASSWORD SETTING

Default: NONE Range: NONE / RESET / A.SAVE NONE: Max & Min don’t reset RESET: Reset Max. & Min. to 0 A.SAVE: Save the values per 10 minutes; when users return to the power on, the records will not dispear

1. Press , and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the value 3. Press ENT to confirm and save the parameter (Password error will

return the MEASUREMENT PAGE. Password correct will enter to the USER LEVEL PAGE)

U-8

"PASSWORD

SETTING" ENT

Default: 1000 Range: 00000 ~ 20000 Change the password please refer to STEP B-13, and don’t forget the new password

L-0

"USER LEVEL PAGE"

Please refer to USER LEVEL OPERATING

CSEC -5- CPM-41- 2003/05

USER LEVEL OPERATING: 【*Please enter to the USER LEVEL when you use the new machine*】 Press ENT + to allow you return the MEASURING PAGE *STEP U-0* Press + to allow you return the USER LEVEL PAGE *STEP L-0* In the parameter setting status, press to allow you return the last page

STEP DISPLAY DESCRIPTION SWITCH OTHERS 1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the value 3. Press ENT to confirm and save the parameter and enter to the USER

LEVEL PAGE

U-8

" PASSWORD

SETTING " ENT

Default: 1000 Range: 00000 ~ 20000 Change the password please refer to STEP B-13, and don’t forget the new password

1. Press and the LED will be flashed and can be set

2. Press to select the LEVEL PAGES【LEVEL Input / Output / Alarm】

L-0

“USER LEVEL PAGE”

Range: LEvEL input:【INPUT LEVEL SETTING】 LEvEL oUPUt:【OUTPUT LEVEL SETTING】 LEvEL ALArM:【ALARM LEVEL SETTING】

1. Press to select the【INPUT LEVEL SETTING】

2. Press ENT to enter the INPUT LEVEL SETTING *STEP A-0*

L-1

【INPUT LEVEL

SETTING】

1. Press or to select the【OUTPUT LEVEL SETTING】

2. Press ENT to enter the OUTPUT LEVEL SETTING *STEP B-0*

L-2

【OUTPUT LEVEL

SETTING】

1. Press or to select the【ALARM LEVEL SETTING】

2. Press ENT to enter the ALARM LEVEL SETTING *STEP C-0*

L-3

【ALARM LEVEL

SETTING】

INPUT LEVEL OPERATING: Press ENT + to allow you return the MEASURING PAGE *STEP U-0* Press + to allow you return the USER LEVEL PAGE *STEP L-0* In the parameter setting status, press to allow you return the last page

STEP DISPLAY DESCRIPTION SWITCH OTHERS 1. In the LEvEL USEr, press the screen will be flashed and can be set

2. Press to select theLEvEL inPUT【INPUT LEVEL SETTING】

A-0

【INPUT LEVEL

SETTING】 ENT

3. Press ENT to enter the INPUT TYPE SETTING

1. Press + then press the screen will be flashed and can be set

2. Press or to select the INPUT TYPE 3. Press ENT to confirm and save the parameter

A-1

"INPUT TYPE

SETTING" ENT 4. Press ENT to enter the INPUT SIGNAL SETTING

Default: LINER Selecting Types: Liner / RTD / Thermocouple LinEr: Analog input rtd: RTD input tC: Thermocouple input

1. Press + then press the screen will be flashed and can be set

2. Press or to select the INPUT SIGNAL 3. Press ENT to confirm and save the parameter

A-2

"INPUT SIGNAL

SETTING" ENT 4. Press ENT to enter the DECIMAL POINT SETTING

Default: Liner: 20mA Range: Liner: 20mA /10V / 100mV /

1Kohm RTD: DIN Pt100 / JIS Pt100 TC: K / J / E / T / R / S / B / N / C

1. Press and the screen will be flashed and can be set

2. Press or to select the position of DECIMAL POINT 3. Press ENT to confirm and save the parameter

A-3

"DECIMAL POINT

SETTING" ENT 4. Press ENT to enter the UNIT SETTING

Default: 000.00 Range: 00000 / 0000.0 /

000.00 / 00.000 / 0.0000

CSEC -6- CPM-41- 2003/05

STEP DISPLAY DESCRIPTION SWITCH OTHERS

1. In the RTD or TC INPUT, press the screen will be flashed and can be set

2. Press or to select the °C or °F 3. Press ENT to confirm and save the parameter

A-4

"UNIT SETTING"

ENT 4. Press ENT to enter the DISPLAY HI SCALE PAGE

Default: Liner: mA RTD & TC: °C (or °F) Selection

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

A-5

"DISPLAY HI SCALE

PAGE" ENT 4. Press ENT to enter the DISPLAY LOW SCALE PAGE

Default: 20.00 Range: 0 ~ 19999

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

A-6

"DISPLAY LOW SCALE

PAGE" ENT 4. Press ENT to enter the INPUT SIGNAL SPAN SETTING

Default: 0.00 Range: -19999 ~ HI.SC

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

A-7

“INPUT SIGNAL SPAN

SETTING" ENT 4. Press ENT to enter the INPUT SIGNAL ZERO SETTING

Default: 20.00 Range: mA input: -20.00 ~ +20.00 V input: -10.00 ~ +10.00 EX: Input is set by 4~20mA, Span is 20.00

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

A-8

"INPUT SIGNAL ZERO

SETTING" ENT 4. Press ENT to enter the DISPLAY FUNCTION SETTING

Default: 0.00 Range: mA input: -20.00 ~ +20.00 V input: -10.00 ~ +10.00 EX: Input is set by 4~20mA, Zero is 4.00

1. Press and the right side LED will be flashed and can be set

2. Press or to select the DISPLAY FUNCTION 3. Press ENT to confirm and save the parameter

A-9

" DISPLAY FUNCTION

SETTING " ENT 4. Press ENT to enter the MOVING AVG. SETTING

Default: PV Range:PV / MAX / MIN / COMM When the setting is MAX( or Min), it means the display is MaxHold( or Min. Hold); if the setting is COMM, it means the display is reading by RS485 PORT

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

A-10

" MOVING AVG.

SETTING " ENT 4. Press ENT to enter the DISPLAY AVG. SETTING

Default: 50 Range: 0 ~ 1000

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

A-11

" DISPLAY AVG.

SETTING " ENT 4. Press ENT to return the INPUT type SETTING

Default: 10 Range: 0 ~ 1000 When the DISPLAY AVG. is higher, the display is more stable; but the response time will be slow

A-1

" INPUT TYPE

SETTING "

OUTPUT LEVEL OPERATING: Press ENT + to allow you return the MEASURING PAGE *STEP U-0* Press + to allow you return the USER LEVEL PAGE *STEP L-0* In the parameter setting status, press to allow you return the last page

STEP DISPLAY DESCRIPTION SWITCH OTHERS 1. In the LEvEL USEr, press the screen will be flashed and can be set

2. Press to select the LEvEL oUPUT【OUTPUT LEVEL SETTING】

B-0

【OUTPUT LEVEL

SETTING】 ENT

3. Press ENT to enter the CON-1 SETTING

CSEC -7- CPM-41- 2003/05

STEP DISPLAY DESCRIPTION SWITCH OTHERS

1. Press and the screen will be flashed and can be set

2. Press or to select the parameters 3. Press ENT to confirm and save the parameter

B-1

" CON-1 SETTING "

ENT 4. Press ENT to enter the CON-2 SETTING 1. Press and the screen will be flashed and can be set

2. Press or to select the parameters 3. Press ENT to confirm and save the parameter

B-2

" CON-2 SETTING "

ENT 4. Press ENT to enter the CON-3 SETTING 1. Press and the screen will be flashed and can be set

2. Press or to select the parameters 3. Press ENT to confirm and save the parameter

B-3

" CON-3 SETTING "

ENT 4. Press ENT to enter the ANALOG OUTPUT TYPE SETTING

Default: NONE Range: NONE / A-M / TARE /

Data HOLD / RESET / DI NONE: No functions A-M: Auto or Manual Analog output selection TARE: Compel to reset to 0 D.HOLD: Data Hold function RESET: MAX. & MIN. reset to 0 DI: External Control Input may read by RS485

1. Press and the screen will be flashed and can be set

2. Press or to select the ANALOG OUTPUT TYPE 3. Press ENT to confirm and save the parameter

B-4

" ANALOG OUTPUT

TYPE SETTING" ENT 4. Press ENT to enter the ANALOG OUTPUT SIGNAL SETTING

Default: AUTO Range: AUTO / MENU AUTO: Correspond with Full Scale Ratio for output MANU: According to Manual Output Setting Ratio for output

1. Press + then press , the screen will be flashed and can be set

2. Press or to select the ANALOG OUTPUT SIGNAL 3. Press ENT to confirm and save the parameter

B-5

"ANALOG OUTPUT SIGNAL SETTING"

ENT 4. Press ENT to enter the ANALOG OUTPUT HI SCALE SETTING

Default: 4-20mA Range: 4-20mA / 0-20mA/ 0-10V /

0-5V / 1-5V

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

B-6

"ANALOG OUTPUT HI

SCALE SETTING" ENT 4. Press ENT to enter the ANALOG OUTPUT LOW SCALE SETTING

Default: 0.00% Range: 0 ~ 100.00% EX: The Output is set by4~20mA, and the display is set by 0~1000.0; if Ao.Hi.C is set by 50.00%, then the display is 500.0, the Output is 20mA

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

B-7

"ANALOG OUTPUT

LOW SCALE SETTING"

ENT 4. Press ENT to enter the ANALOG OUTPUT SPAN SETTING

Default: 0.00% Range: 0 ~ 100.00% EX: The Output is set by4~20mA, and the display is set by 0~1000.0; if Ao.Lo.C is set by 0.00%, then the display is 0.0, the Output is 4mA

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

B-8

"ANALOG OUTPUT SPAN

FINE ADJUSTMENT" ENT 4. Press ENT to enter the ANALOG OUTPUT ZERO SETTING

Default: 0 Range: -4000 ~ 4000 ANALOG OUTPUT HI SCALE has errors, it allows user to get fine adjustment the SPAN

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

B-9

"ANALOG OUTPUT ZERO

FINE ADJUSTMENT" ENT 4. Press ENT to enter the ADDRESS SETTING

Default: 0 Range: -4000 ~ 4000 ANALOG OUTPUT LOW SCALE has errors, it allows user to get fine adjustment adjust the ZERO

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

B-10

"ADDRESS SETTING"

ENT 4. Press ENT to enter the BAUD RATE SETTING

Default: 1 Range: 1 ~ 255

CSEC -8- CPM-41- 2003/05

STEP DISPLAY DESCRIPTION SWITCH OTHERS

1. Press and the screen will be flashed and can be set

2. Press or to select the BAUD RATE 3. Press ENT to confirm and save the parameter

B-11

"BAUD RATE

SETTING" ENT 4. Press ENT to enter the PARITY SETTING

Default: 9600 Range: 2400 / 4800 / 9600 / 19200

/ 38400

1. Press and the screen will be flashed and can be set

2. Press or to select the PARITY 3. Press ENT to confirm and save the parameter

B-12

"PARITY SETTING"

ENT 4. Press ENT to enter the CODE SETTING

Default: NONE Range: NONE / EVEN / ODD

1. Press and the screen will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

B-13

"CODE SETTING"

ENT 4. Press ENT to return the CON-1 SETTING

Default: 1000 Range: 0 ~ 20000 Please remember the new CODE in case for next time to using

B-1

"CON-1 SETTING"

ENT

ALARM LEVEL OPERATING: Press ENT + to allow you return the MEASURING PAGE *STEP U-0* Press + to allow you return the USER LEVEL PAGE *STEP L-0* In the parameter setting status, press to allow you return the last page

STEP DISPLAY DESCRIPTION SWITCH OTHERS 1. In the LEvEL USEr, press , the screen will be flashed and can be set

2. Press to select the LEvEL ALArM【ALARM LEVEL SETTING】

C-0

【ALARM LEVEL

SETTING】 ENT

3. Press ENT to enter the ALARM DEAD BAND SETTING

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

C-1

"ALARM DEAD BAND

SETTING" ENT 4. Press ENT to enter the ALARM START DELAY SETTING

Default: 0.00% Range: -50.00 ~ +50.00

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter C-2

"ALARM START

DELAY SETTING" ENT

4. Press ENT to enter the A/D SYSTEM ERROR ALARM SETTING

Default: 0.00.0 Range: 99’59”,9 (min.sec.0)

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, different places mean different relays for

output (Refer to the diagram of right side) , press to change the values to 1

3. Press ENT to confirm and save the parameter

C-3

"A/D CONVERTER

ERROR ALARM SETTING"

ENT 4. Press ENT to enter the ALM_1 MODE SETTING

Default: 00000 Range: 01111(BINARY)

1. Press and the screen will be flashed and can be set

2. Press or to select the ALM_1 MODE 3. Press ENT to confirm and save the parameter C-4

"ALM_1 MODE

SETTING" ENT

4. Press ENT to enter the ALM_1 HYSTERESIS SETTING

Default: HI Range: HI/LO/DIF.HI/DIF.LO/DO/NONE HI: Over the setpoint, the relay trips LO: Under the setpoint, the relay trips DIF.HI: Compare with ALM_2, if it over the setpoint, the relay trips DIF.LO: Compare with ALM_2, if it under the setpoint, the relay trips DO: Output tripped by communication

Alarm Dead Band

Start Delay Time

Dead Band(db)

Hi Setting

Alarm Relay ON

Inhibit Inhibit

Start Delay Time

Start Delay Time

Dead Band(db)

Hi Setting

Alarm Relay ON

Inhibit Inhibit

AL-1: AL-2: AL-3: AL-4:

The setting is 00001, the ALM-1 (Relay1) output The setting is 00010, the ALM-2 (Relay2) output The setting is 00100, the ALM-3 (Relay3) output The setting is 01000, the ALM-4 (Relay4) output

CSEC -9- CPM-41- 2003/05

CSEC -10- CPM-41- 2003/05

STEP DISPLAY DESCRIPTION SWITCH OTHERS1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

C-5

" ALM_1 HYSTERESIS

SETTING" ENT 4. Press ENT to enter the ALM_1 RUN DELAY SETTING

Default: 0.00% Range: -50.00 ~ +50.00 Run / Off Delay & Hysteresis

Hi Setting

Run D

elay T

ime

Alarm Relay ON

Hysteresis

Off D

elay T

ime

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

C-6

"ALM_1 RUN DELAY

SETTING" ENT 4. Press ENT to enter the ALM_1 OFF DELAY SETTING

Default: 0.00.0 Range: 99’59”,9 (min.sec.0) Run / Off Delay & Hysteresis

Hi Setting

Run D

elay T

ime

Alarm Relay ON

Hysteresis

Off D

elay T

ime

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

C-7

"ALM_1 OFF DELAY

SETTING" ENT 4. Press ENT enter to the ALM_2 MODE SETTING

Default: 0.00.0 Range: 99’59”,9 (min.sec.0) Run / Off Delay & Hysteresis

Hi Setting

Run D

elay T

ime

Alarm Relay ON

Hysteresis

Off D

elay T

ime

1. Press and the screen will be flashed and can be set

2. Press or to select the ALM_2 MODE 3. Press ENT to confirm and save the parameter

C-8

"ALM_2 MODE

SETTING" ENT 4. Press ENT to enter the ALM_2 HYSTERESIS SETTING

Default: HI Range: HI/LO/DO/NONE HI: Over the setpoint, the relay trips LO: Under the setpoint, the relay trips DO: Output tripped by communication

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

C-9

"ALM_2 HYSTERESIS

SETTING" ENT 4. Press ENT to enter the ALM_2 RUN DELAY SETTING

Default: 0.00% Range: -50.00~+50.00 Please refer to STEP C-5 (ALM_1 HYSTERESIS SETTING) the diagram of right side

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

C-10

"ALM_2 RUN DELAY

SETTING" ENT 4. Press ENT to enter the ALM_2 OFF DELAY SETTING

Default: 0.00.0 Range: 99’59”,9( . .0) Please refer to STEP C-6 (ALM_1 RUN DELAY SETTING) the diagram of right side

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

C-11

"ALM_2 OFF DELAY

SETTING" ENT 4. Press ENT enter to the ALM_3 MODE SETTING

Default: 0.00.0 Range: 99’59”,9(min.sec.0) Please refer to STEP C-7 (ALM_1 OFF DELAY SETTING) the diagram of right side

1. Press and the screen will be flashed and can be set

2. Press or to select the ALM_3 MODE 3. Press ENT to confirm and save the parameter

C-12

"ALM_3 MODE

SETTING" ENT 4. Press ENT to enter the ALM_3 HYSTERESIS SETTING

Default: LO Range: HI / LO / DO / NONE HI: Over the setpoint, the relay trips LO: Under the setpoint, the relay trips DO: Output tripped by communication

1. Press , and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

C-13

" ALM_3 HYSTERESIS

SETTING" ENT 4. Press ENT to enter the ALM_3 RUN DELAY SETTING

Default: 0.00% Range: -50.00 ~ +50.00 Please refer to STEP C-5 (ALM_1 HYSTERESIS SETTING) the diagram of right side

1. Press , and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values

3. Press ENT to confirm and save the parameter

C-14

"ALM_3 RUN DELAY

SETTING" ENT 4. Press ENT to enter the ALM_3 OFF DELAY SETTING

Default: 0.00.0 Range: 99’59”,9(min.sec.0) Please refer to STEP C-6 (ALM_1 RUN DELAY SETTING) the diagram of right side

CSEC -11- CPM-41- 2003/05

STEP DISPLAY DESCRIPTION SWITCH OTHERS

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and the parameter

C-15

"ALM_3 OFF DELAY

SETTING" ENT 4. Press ENT enter to the ALM_4 MODE SETTING

Default: 0.00.0 Range: 99’59”,9 (min.sec.0) Please refer to STEP C-7 (ALM_1 OFF DELAY SETTING) the diagram of right side

1. Press and the screen will be flashed and can be set

2. Press or to select the ALM_4 MODULE 3. Press ENT to confirm and the parameter

C-16

"ALM_4 MODE

SETTING" ENT 4. Press ENT to enter the ALM_4 HYSTERESIS SETTING

Default: HI Range: HI/LO/DIF.HI /DIF.LO/DO/NONE HI: Over the setpoint, the relay trips LO: Under the setpoint, the relay trips DIF.HI: Compare with ALM_3, if it over the setpoint, the relay trips DIF.LO: Compare with ALM_3, if it under the setpoint, the relay trips DO: Output tripped by communication

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

C-17

" ALM_4 HYSTERESIS

SETTING" ENT 4. Press ENT to enter the ALM_4 RUN DELAY SETTING

Default: 0.00% Range: -50.00~+50.00 Please refer to STEP C-5 (ALM_1 HYSTERESIS SETTING) the diagram of right side

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

C-18

"ALM_4 RUN DELAY

SETTING" ENT 4. Press ENT to enter the ALM_4 OFF DELAY SETTING

Default: 0.00.0 Range: 99’59”,9(min.sec.0) Please refer to STEP C-6 (ALM_1 RUN DELAY SETTING) the diagram of right side

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

C-19

"ALM_4 OFF DELAY

SETTING" ENT 4. Press ENT to return the ALARM DEAD BAND SETTING

Default: 0.00.0 Range: 99’59”,9(min.sec.0) Please refer to STEP C-7 (ALM_1 OFF DELAY SETTING) the diagram of right side

C-1

"ALARM DEAD BAND

SETTING" ENT

MEASURING COMPENSATION OPERATING STEPS: STEP DISPLAY DESCRIPTION SWITCH OTHERS

In the MEASURING PAGE, press ENT over 5 sec, it will enter the DISPLAY LOW SCALE COMPENSATION SETTING

P-0

"MEASURING PAGE"

ENT

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

P-1

"DISPLAY LOW SCALE

COMPENSATION SETTING"

ENT 4. Press ENT to enter the DISPLAY HI SCALE OFFSET SETTING

Default: 0.00% Range: - 50 ~ +50% F.S Display Low Scale Offset

Hi Scaling

Low Scaling

Low Offset

Standard

Input Low Input Hi

Hi Offse

1. Press and the right side LED will be flashed and can be set

2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter

P-2

"DISPLAY HI SCALE

COMPENSATION SETTING"

ENT 4. Press ENT to enter the DISPLAY SOFTWARE VERSION

Default: 0.00% Range: - 50 ~ +50% F.S Display Hi Scale Offset

Hi Scaling

Low Scaling

Low Offset

Standard

Input Low Input Hi

Hi Offse

Press ENT to enter the FUNCTIONS LOCK SETTING

P-3

"DISPLAY SOFTWARE

VERSION" ENT

STEP DISPLAY DESCRIPTION SWITCH OTHERS

Press ENT to enter the FUNCTIONS LOCK SETTING P-3

"DISPLAY SOFTWARE

VERSION" ENT

1. Press , and the right side LED will be flashed and can be set 2. Press to move the cursor, different places mean different functions

for skip (Refer to the diagram of right side) , press to change the values to 1(Lock) or 0(Unlock)

3. Press ENT to confirm and save the parameter

P-4

"FUNCTIONS LOCK

SETTING" ENT 4. Press ENT to return the MEASURING PAGE

Default: 01111 Range: 01111(BINARY)

P-0

"MEASURING PAGE"

ENT

Alarm Setting 1:Skip 0:Unskip Input Setting 1:Skip 0:Unskip Output Setting 1:Skip 0:Unskip Alarm Setting 1:Skip 0:Unskip None

ERROR CODE OF SELF-DIAGNOSIS: STEP DESCRIPTION DISPLAY SWITCH OTHERS

ERROR CODE OF SELF-DIAGNOSIS: : A/D circuits error (Please return to the Factory)

: Display postive overflow (Signals over the range) (Please check the Input Signals)

: Display negative overflow (Signals under the range) (Please check the Input Signals)

SOFTWARE OPTIONAL FUNCTIONS: (NEEDS TO EXTRA CHARGES) ITEM MODEL NO. DESCRIPTION OTHERS

Option 1 CPM-42 Math functions NON: None(Default), SQU: Square, ROOT: Root ABS: Absolutely, INVT: Reverse

Option 2 CPM-43 3 Banks for preset BANK1 ~ BANK3 Option 3 CPM-44 Non-Lineariztion 16 segment for non-linearization

Option 4 CPM-45 All functions included Option 1 + Option 2 + Option 3

HARDWARE OPTIONAL FUNCTIONS: (NEEDS TO EXTRA CHARGES) ITEM DESCRIPTION OTHERS

Option A Analogue Output 0~10Vdc / 0~20mAdc selection, 15 BIT DAC can be programmed

Option B Communication Output RS-485 / RS-232C, MODBUS RTU Mode

CSEC -12- CPM-41- 2003/05