402 COMFORT CONTROL LOGIC

28
402 COMFORT CONTROL LOGIC

description

402 COMFORT CONTROL LOGIC. Questions. SUB BASE. Up to 16 wires may be required. AUTO CHANGEOVER. IFIDT ≥ CSP (minus 1) then: COOLING MODE ( SP = 75, COOL MODE to 74) IF IDT < HSP then: HEATING MODE (Dead Band factory set to 3 degrees). LOAD VALUE. Control reacts to LOAD VALUE - PowerPoint PPT Presentation

Transcript of 402 COMFORT CONTROL LOGIC

Page 1: 402 COMFORT CONTROL LOGIC

402 COMFORT CONTROL LOGIC

Page 2: 402 COMFORT CONTROL LOGIC

Questions

SUB BASE

Up to 16 wires may be requiredUp to 16 wires may be required

Page 3: 402 COMFORT CONTROL LOGIC

AUTO CHANGEOVER

• IF IDT ≥ CSP (minus 1) then: – COOLING MODE – ( SP = 75, COOL MODE to 74)

• IF IDT < HSP then: – HEATING MODE – (Dead Band factory set to 3 degrees)

Page 4: 402 COMFORT CONTROL LOGIC

LOAD VALUE

• Control reacts to LOAD VALUE

• Traditional PI– Calculated every two seconds– P = Δt– I = ΣΔt Ti

• P + I = LOAD VALUE

Page 5: 402 COMFORT CONTROL LOGIC

LOAD VALUE & STAGING

• LV determines – TURN ON threshold for each stage– TURN OFF threshold for each stage

• LV of 5 to turn ON– 5 minute Min OFF time for CLG– 1 minute Min OFF time for HTG

• Max LV limits are set by HVAC config.

Page 6: 402 COMFORT CONTROL LOGIC

LOAD VALUE & STAGING

CLG 0-100 Single Stage Compressor 0-200 Two Stage Compressor

HTG 0-100 Single Stage HP or Furnace 0-200 Two Stage HP or Furnace 0-200 Single Stage HP + 1 Stage Indoor Heat 0-300 Single Stage HP + 2 Stage Indoor Heat 0-400 Single Stage HP + 3 Stage Indoor Heat 0-300 Two Stage HP + 1 Stage ID Heat 0-400 Two Stage HP + 2 Stage ID Heat 0-500 Two Stage HP + 3 Stage ID Heat

Page 7: 402 COMFORT CONTROL LOGIC

LOAD VALUE & STAGING

3002000 100 400+

LV = Load Value

Calculated Every Two Seconds

INCREASED DEMAND

INCREASED DEMAND

Stage 1 Stage 2 Stage 3 Stage 4

Maximum LV Limits

are set by

HVAC Configuration

Stage 5

Page 8: 402 COMFORT CONTROL LOGIC

MULTI STAGE THRESHOLD

• Dead Band @ LV Threshold – to avoid cycling around LV

Increased Demand LV 0-110 1st StageLV >111 2nd Stage

Decreased Demand LV >100 2nd StageLV 99-0 1st Stage

10 Minute INHIBIT once Threshold is Crossed

Page 9: 402 COMFORT CONTROL LOGIC

2000 110

Stage 1 Stage 2

Cross LV Dead Band & Initiate10 Minute INHIBIT

(Does not apply to W1 to W2)

Stage 3

115 125

LV = Load Value

Begin INHIBIT - Y1 to Y2

Begin INHIBIT - HP to W1

Begin INHIBIT - HP to Dual Fuel

MULTI STAGE INHIBIT

Page 10: 402 COMFORT CONTROL LOGIC

TWO STAGE COMPRESSOR

Y1 “ON”

Start INHIBIT

Y2 “ON”

10 Min

LV = Load Value

LV 110

Y1 “ON”

LV 100

Page 11: 402 COMFORT CONTROL LOGIC

Y1 “ON”

Start INHIBIT

10 Min

LV = Load Value

LV 115LV 100

SINGLE STAGE HEAT PUMP with AUX HEAT

W1 “ON” W1 “OFF”

Page 12: 402 COMFORT CONTROL LOGIC

Y1 “ON”

Start INHIBIT

10 Min

LV 125

Y1 “ON”

DUAL FUEL EQUIPMENT

W1 “ON” 45 seconds cool down

LV 100

LV = Load Value

Page 13: 402 COMFORT CONTROL LOGIC

MULTI STAGE INHIBIT

If IDT is ½° or less from Set Point, the next stage is always INHIBITED regardless of LV

IDT

SP

1/2° INHIBIT 2nd stage Cooling

1/2°

SP

INHIBIT 2nd stage Heating

Page 14: 402 COMFORT CONTROL LOGIC

LV CLAMP

MAX OVERSHOOT = 2.5° F

Turns system “OFF” regardless of LV

System will turn back “ON” 3/4° from SP

•Provided Min OFF Time has elapsed

•Provided LV is still present

Max Overshoot not enforced during DROOP

Page 15: 402 COMFORT CONTROL LOGIC

COOLING DROOP

•Set Point is satisfied (No-load or light load condition)

•Time OFF satisfied

•IDT < Droop OVERSHOOT limit to start DROOP “ON” cycle

•Standard DROOP = 1 degree OVERSHOOT

•Enhanced DROOP = 2 degree OVERSHOOT

•Fan delay-to-OFF is cancelled

•Var Sp: Blower speed set to 80% (BK= 70% PWM)

•Minimum ON = 8 minutes

•Minimum OFF = 20 minutes

Page 16: 402 COMFORT CONTROL LOGIC

SET POINT CHANGES

• Temperature Display Rounds to Nearest Whole Number

• Room Sensor can Discern 10ths of a Degree – – Used to Calculate Temp Difference from SP

• Large Changes in SP will Freeze LV until New SP is Reached to Avoid Overshoot– “Snap Shot & Roll Back”

Page 17: 402 COMFORT CONTROL LOGIC

$

10 Min

Set PointIDT

New Set Point

4°= AUX HT 3°= No AUX HT

Recovering IDT

ENERGY SAVINGS MODE

Rate of Recovery can increase INHIBIT

Only applies to Y1 to Y2 or HP to W1

Recovery Delta must be 1.25° to INHIBIT

Distance to New SP divided by 4 is the Recovery Delta

Y2 or W1Y

Page 18: 402 COMFORT CONTROL LOGIC

$

10 Min

Set PointIDT

10°

New Set Point

8°= AUX HT 7°= No AUX HT

Recovering IDT

ENERGY SAVINGS MODE

Rate of Recovery can increase INHIBIT

Only applies to Y1 to Y2 or HP to W1

Recovery Delta must be 2.5° to INHIBIT

Distance to New SP divided by 4 is the Recovery Delta

Y Y2 or W1

Page 19: 402 COMFORT CONTROL LOGIC

$

Set PointIDT

>2°

New Set Point

Recovering IDT

ENERGY SAVINGS MODE

Aggressive Recovery will cancel INHIBIT

Only applies to Y1 to Y2 or HP to W1

NO INHIBIT

ISU # 35 EnabledY Y2 or W1

Page 20: 402 COMFORT CONTROL LOGIC

HUMIDISTAT OPERATION

RH control with external Humidistat connected to input terminals H1 and H2

In COOLING MODE

Open signal triggers:

•Compressor “ON” cycle time is extended by 2 minutes•Fan “OFF” delay is cancelled •PSC motors “ON” delay calculated by previous “OFF” time •Fan CFM reduced by 20% -Variable Speed – if Room Temp is within 2º of SP

Page 21: 402 COMFORT CONTROL LOGIC

BALANCE POINTS

Outdoor Sensor Must be Installed

Page 22: 402 COMFORT CONTROL LOGIC

BALANCE POINTS

Outdoor Sensor Must be Installed

Page 23: 402 COMFORT CONTROL LOGIC

BLOWER PROFILES

Page 24: 402 COMFORT CONTROL LOGIC

BLOWER PROFILES

PSC Motors

Page 25: 402 COMFORT CONTROL LOGIC

BLOWER PROFILES

When ODT is below 87° F, Variable Speed Airflow is Reduced to 80%

WET HEAT

VAR SP

0-90sec at 35% Airflow

PSC and VAR SP Motors

Page 26: 402 COMFORT CONTROL LOGIC

WET HEAT

Single Stage Wet Heat

PSC Motor VAR SP MotorLV ≤ 100 W1 cycled based on LV W1 on, Airflow adjusted based on LV

Two Stage Wet Heat

PSC Motor VAR SP MotorLV < 100 W1 cycled based on LV W1 on, Airflow adjusted based on LV

LV > 100 W1 On, W2 cycle based on LV W1 On, Airflow set to 100%, W2 cycled based on LV

PSC

BK Disabled - ISU # 11VARIABLE SPEED

BK Enabled - ISU # 11

Page 27: 402 COMFORT CONTROL LOGIC

TWO STAGE COMPRESSORS

WARM AIR HEAT PUMP

Page 28: 402 COMFORT CONTROL LOGIC

402 Comfort Control

Heat Pump Connection Diagram