  • Sole/Wasser-Wrmepumpe fr Innenaufstellung

    SI 5TESI 7TESI 9TESI 11TESI 14TESI 17 TESI 21TE

    Brine-to-Water Heat Pump for Indoor Installation

    Pompe chaleur eau glycole-eau pour installation intrieure

    Montage- und Gebrauchsanweisung De

    utsc

    hEn

    glis

    hFr

    ana

    isInstructions dinstallation et dutilisation

    Installation andOperating Instructions

    Bestell-Nr. / Order no. / No de commande : 452232.66.12 FD 8611

  • www.dimplex.de D-1

    Deu

    tsch

    Inhaltsverzeichnis1 Bitte sofort lesen .......................................................................................................................... D-2

    1.1 Wichtige Hinweise ..................................................................................................................................D-21.2 Gesetzliche Vorschriften und Richtlinien ................................................................................................D-21.3 Energiesparende Handhabung der Wrmepumpe .................................................................................D-2

    2 Verwendungszweck der Wrmepumpe...................................................................................... D-32.1 Anwendungsbereich ...............................................................................................................................D-32.2 Arbeitsweise ...........................................................................................................................................D-3

    3 Grundgert.................................................................................................................................... D-3

    4 Zubehr ......................................................................................................................................... D-44.1 Soleverteiler............................................................................................................................................D-4

    5 Transport....................................................................................................................................... D-4

    6 Aufstellung.................................................................................................................................... D-46.1 Allgemeine Hinweise ..............................................................................................................................D-46.2 Schallemissionen....................................................................................................................................D-4

    7 Montage......................................................................................................................................... D-57.1 Allgemein ................................................................................................................................................D-57.2 Heizungsseitiger Anschluss....................................................................................................................D-57.3 Wrmequellenseitiger Anschluss............................................................................................................D-57.4 Elektrischer Anschluss............................................................................................................................D-5

    8 Inbetriebnahme............................................................................................................................. D-68.1 Allgemeine Hinweise ..............................................................................................................................D-68.2 Vorbereitung ...........................................................................................................................................D-68.3 Vorgehensweise bei Inbetriebnahme .....................................................................................................D-6

    9 Pflege / Reinigung ........................................................................................................................ D-79.1 Pflege......................................................................................................................................................D-79.2 Reinigung Heizungsseite ........................................................................................................................D-79.3 Reinigung Wrmequellenseite................................................................................................................D-7

    10 Strungen / Fehlersuche ............................................................................................................. D-7

    11 Auerbetriebnahme / Entsorgung .............................................................................................. D-7

    12 Gerteinformation ........................................................................................................................ D-8

    13 Garantieurkunde......................................................................................................................... D-10

    Anhang / Appendix / Annexes ............................................................................................................ A-I

  • Deutsch

    11 Bitte sofort lesen

    1.1 Wichtige Hinweise

    ACHTUNG!Die Wrmepumpe ist nicht am Holzrost befestigt.

    ACHTUNG!Die Wrmepumpe darf nur bis zu einer Neigung von maximal 45 (in jederRichtung) gekippt werden.

    ACHTUNG!Gert nicht an den Bohrungen in den Verkleidungsblechen anheben!

    ACHTUNG!Vor Anschluss der Wrmepumpe Heizungsanlage splen.

    ACHTUNG!Im Wrmequelleneintritt der Wrmepumpe ist der beiliegendeSchmutzfnger zu montieren, um den Verdampfer gegenVerunreinigungen zu schtzen.

    ACHTUNG!Die Sole muss mindestens zu 25% aus einem Frostschutz aufMonoethylenglykol- oder Propylenglykolbasis bestehen und ist vor demBefllen zu mischen.

    ACHTUNG!Bei Anschluss der Lastleitung auf Rechtsdrehfeld achten (bei falschemDrehfeld bringt die Wrmepumpe keine Leistung und ist sehr laut).

    ACHTUNG!Die Inbetriebnahme der Wrmepumpe muss gem der Montage- undGebrauchsanweisung des Wrmepumpenreglers erfolgen.

    ACHTUNG!Zur Vermeidung von Ablagerungen (z.B. Rost) im Kondensator derWrmepumpe wird empfohlen, ein geeignetes Korrosionsschutzsystemeinzusetzen.

    ACHTUNG!Arbeiten an der Wrmepumpe drfen nur vom autorisierten undsachkundigen Kundendienst durchgefhrt werden.

    ACHTUNG!Vor ffnen des Gertes sind alle Stromkreise spannungsfrei zu schalten.

    1.2 Gesetzliche Vorschriften und Richtlinien

    Die Wrmepumpe entspricht allen relevanten DIN-/VDE-Vor-schriften und EG-Richtlinien. Diese knnen der CE-Erklrung imAnhang entnommen werden.Der elektrische Anschluss der Wrmepumpe muss nach den gl-tigen VDE-, EN- und IEC-Normen ausgefhrt werden. Zustzlichsind die Anschlussbedingungen der Versorgungsunternehmenzu beachten.Die Wrmepumpe ist entsprechend den einschlgigen Vorschrif-ten in die Wrmequellen- und Heizungsanlage einzubinden.Personen, insbesondere Kinder, die aufgrund ihrer physischen,sensorischen oder geistigen Fhigkeiten oder ihrer Unerfahren-heit oder Unkenntnis nicht in der Lage sind, das Gert sicher zubenutzen, sollten dieses Gert nicht ohne Aufsicht oder Anwei-sung durch eine verantwortliche Person benutzen.Kinder sollten beaufsichtigt werden, um sicher zu stellen, dasssie nicht mit dem Gert spielen.

    1.3 Energiesparende Handhabung der Wrmepumpe

    Durch das Betreiben dieser Wrmepumpe tragen Sie zur Scho-nung unserer Umwelt bei. Fr den effizienten Betrieb ist einesorgfltige Bemessung der Heizungsanlage und der Wrme-quelle sehr wichtig. Dabei ist besonderes Augenmerk auf mg-lichst niedrige Wasservorlauftemperaturen zu richten. Darumsollten alle angeschlossenen Energieverbraucher fr niedrigeVorlauftemperaturen geeignet sein. Eine um 1 K hhere Heiz-wassertemperatur steigert den Energieverbrauch um ca. 2,5%.Eine Niedertemperaturheizung mit Vorlauftemperaturen zwi-schen 30 C und 50 C ist fr einen energiesparenden Betriebgut geeignet.D-2

  • Deu

    tsch

    32 Verwendungszweck der Wrmepumpe

    2.1 AnwendungsbereichDie Sole-Wasser-Wrmepumpe kann in vorhandenen oder neuzu errichtenden Heizungsanlagen eingesetzt werden. Als Wr-metrger in der Wrmequellenanlage dient Sole. Als Wrme-quelle knnen Erdsonden, Erdkollektoren oder hnliche Anlagengenutzt werden.

    2.2 ArbeitsweiseDas Erdreich speichert Wrme die von Sonne, Wind und Regeneingebracht wird. Diese Erdwrme wird im Erdkollektor, der Erd-sonde oder hnlichem von der Sole bei niedriger Temperaturaufgenommen. Eine Umwlzpumpe frdert dann die "erwrmte"Sole in den Verdampfer der Wrmepumpe. Dort wird dieseWrme an das Kltemittel im Kltekreislauf abgegeben. Dabeikhlt sich die Sole wieder ab, so dass sie im Solekreis wiederWrmeenergie aufnehmen kann.Das Kltemittel wird vom elektrisch angetriebenen Verdichter an-gesaugt, verdichtet und auf ein hheres Temperaturniveau "ge-pumpt". Die bei diesem Vorgang zugefhrte elektrische Antriebs-leistung geht nicht verloren, sondern wird grtenteils demKltemittel zugefhrt.Daraufhin gelangt das Kltemittel in den Verflssiger und ber-trgt hier wiederum seine Wrmeenergie an das Heizwasser.Abhngig vom Betriebspunkt erwrmt sich so das Heizwasserauf bis zu 60 C.

    3 GrundgertDas Grundgert besteht aus einer anschlussfertigen Wrme-pumpe fr Innenaufstellung mit Blechgehuse, Schaltblech undintegriertem Regler. Im Kltekreis ist das Kltemittel R407C ein-gefllt. Das Kltemittel R407C ist FCKW-frei, baut kein Ozon abund ist nicht brennbar.Am Schaltblech sind alle fr den Betrieb der Wrmepumpe not-wendigen Bauteile angebracht. Ein Fhler fr die Auenwand-temperatur mit Befestigungsmaterial sowie ein Schmutzfngerliegen der Wrmepumpe bei. Die Spannungszufhrung fr Last-und Steuerstrom ist bauseits zu verlegen.Die Zuleitung der bauseits zu stellenden Solepumpe ist amSchaltblech anzuschlieen. Dabei ist - falls erforderlich - frdiese ein Motorschutz vorzusehen.Der Kollektor mit Soleverteiler ist bauseits zu erstellen.

    1) Verflssiger2) Schaltblech3) Verdampfer4) Verdichter

    www.dimplex.de D-3

  • Deutsch

    44 Zubehr

    4.1 SoleverteilerDer Soleverteiler vereinigt die Kollektorschleifen der Wrmequel-lenanlage zu einer Hauptleitung, welche an die Wrmepumpeangeschlossen wird. Mittels der integrierten Kugelhhne knnenzum Entlften einzelne Solekreise abgesperrt werden.

    5 TransportZum Transport auf ebenem Untergrund eignet sich ein Hubwa-gen. Muss die Wrmepumpe auf unebenem Untergrund oderber Treppen befrdert werden, kann dies mit Tragriemen ge-schehen. Diese knnen direkt unter dem Holzrost hindurchge-fhrt werden.

    ACHTUNG!Die Wrmepumpe ist nicht am Holzrost befestigt.

    ACHTUNG!Die Wrmepumpe darf nur bis zu einer Neigung von maximal 45 (in jederRichtung) gekippt werden.

    Zum Anheben des Gertes ohne Palette sind die seitlich im Rah-men vorgesehenen Bohrungen zu benutzen. Die seitlichen Ver-kleidungsbleche sind dabei abzunehmen. Als Tragehilfe kannein handelsbliches Rohr dienen.

    ACHTUNG!Gert nicht an den Bohrungen in den Verkleidungsblechen anheben!

    6 Aufstellung

    6.1 Allgemeine HinweiseDas Gert ist nur in nicht feuchten Innenrumen auf einer ebe-nen, glatten und waagrechten Flche aufzustellen. Dabei sollteder Rahmen rundum dicht am Boden anliegen, um eine geeig-nete Schallabdichtung zu gewhrleisten. Ist dies nicht der Fall,knnen zustzliche schalldmmende Manahmen notwendigwerden.Die Wrmepumpe muss so aufgestellt sein, dass ein Kunden-diensteinsatz problemlos durchgefhrt werden kann. Dies ist ge-whrleistet, wenn ein Abstand von ca. 1 m vor und neben derWrmepumpe eingehalten wird.

    6.2 SchallemissionenAufgrund der wirkungsvollen Schallisolation arbeitet die Wrme-pumpe sehr leise. Um eine Schwingungsbertragung auf dasFundament zu verhindern, sollte eine geeignete, dmpfendeGummimatte unter den Grundrahmen der Wrmepumpe gelegtwerden.Um die bertragung von Geruschen in das Heizsystem zu ver-meiden, empfiehlt es sich, die Wrmepumpe mit Schlauchst-cken an das Heizsystem zu koppeln.D-4

  • Deu

    tsch

    7.47 Montage

    7.1 AllgemeinAn der Wrmepumpe sind folgende Anschlsse herzustellen: Vor-/Rcklauf Soleanlage Vor-/Rcklauf Heizung Stromversorgung

    7.2 Heizungsseitiger Anschluss

    ACHTUNG!Vor Anschluss der Wrmepumpe Heizungsanlage splen.

    Bevor die heizwasserseitigen Anschlsse der Wrmepumpe er-folgen, muss die Heizungsanlage gesplt werden, um eventuellvorhandene Verunreinigungen, Reste von Dichtmaterial oderhnliches, zu entfernen. Ein Ansammeln von Rckstnden imVerflssiger kann zum Totalausfall der Wrmepumpe fhren.Nach erstellter heizungsseitiger Installation ist die Heizungsan-lage zu fllen, zu entlften und abzudrcken.Die im Schaltkasten angeschlossenen und lose eingelegten Fh-ler mssen, wie im Prinzipschema dargestellt, angebracht undisoliert werden.

    MindestheizwasserdurchsatzDer Mindestheizwasserdurchsatz der Wrmepumpe ist in jedemBetriebszustand der Heizungsanlage sicherzustellen. Dieseskann z.B. durch Installation eines differenzdrucklosen Verteilersoder eines berstrmventiles erreicht werden. Die Einstellungeines berstrmventiles ist in Kapitel Inbetriebnahme erklrt.

    Frostschutz bei frostgefhrdeter AufstellungSofern Regler und Heizungsumwlzpumpen betriebsbereit sind,arbeitet die Frostschutzfunktion des Reglers. Bei Auerbetrieb-nahme der Wrmepumpe oder Stromausfall ist die Anlage zuentleeren. Bei Wrmepumpenanlagen, an denen ein Stromaus-fall nicht erkannt werden kann (Ferienhaus), ist der Heizungs-kreis mit seinem geeigneten Frostschutz zu betreiben.

    7.3 Wrmequellenseitiger Anschluss

    Folgende Vorgehensweise ist beim Anschluss einzuhalten:Die Soleleitung am Vor- und Rcklauf der Wrmepumpe an-schlieen. Dabei ist das hydraulische Prinzipschema zu beach-ten.

    ACHTUNG!Im Wrmequelleneintritt der Wrmepumpe ist der beiliegendeSchmutzfnger zu montieren, um den Verdampfer gegenVerunreinigungen zu schtzen.

    Zustzlich muss ein Mikroluftblasenabscheider in der Wrme-quellenanlage eingebaut werden.Die Sole ist vor dem Befllen der Anlage herzustellen. Die Sole-konzentration muss mindestens 25% betragen. Das gewhrleis-tet Frostsicherheit bis -14 C.Es drfen nur Frostschutzmittel auf Monoethylenglykol- oderPropylenglykolbasis verwendet werden.Die Wrmequellenanlage ist zu entlften und auf Dichtheit zuprfen.

    ACHTUNG!Die Sole muss mindestens zu 25% aus einem Frostschutz aufMonoethylenglykol- oder Propylenglykolbasis bestehen und ist vor demBefllen zu mischen.

    7.4 Elektrischer AnschlussAn der Wrmepumpe mssen folgende elektrischen Anschlssehergestellt werden: Anschluss der Steuerleitung am Schaltblech der Wrme-

    pumpe ber Klemmen X1: L/N/PE. Anschluss der Lastleitung am Schaltblech der Wrme-

    pumpe ber Klemmen X5/X6: L1/L2/L3/PE. Anschluss der Solepumpe (bauseitig) am Schaltblech der

    Wrmepumpe ber Klemme X1: PE und Pumpenschtz K2:2/4/6 (SI 5TE - SI 17TE), bzw. Motorschutz F7: 2/4/6(SI 21TE). Optional kann bei SI 5TE - SI 14TE eine einpha-sige Solepumpe verwendet werden (siehe dazu Klemmen-anschlussplan).

    Alle fr den Betrieb der Wrmepumpe notwendigen elektrischenBauteile befinden sich am Schaltblech.Genaue Anweisungen ber Anschluss und Funktion des Wrme-pumpenreglers (z.B. beiliegender Auenwandfhler) entnehmenSie bitte der beigefgten Gebrauchsanweisung des Reglers.Eine allpolige Abschaltung mit mindestens 3 mm Kontaktff-nungsabstand (z.B. EVU-Sperrschtz oder Leistungsschtz),sowie ein 3-pol. Sicherungsautomat mit gemeinsamer Ausl-sung aller Auenleiter, sind vorzusehen. Der bentigte Leiter-querschnitt ist gem der Leistungsaufnahme der Wrme-pumpe, der technischen Anschlussbedingungen des jeweiligenEVU und nach den einschlgigen Vorschriften zu whlen. DieLeistungsaufnahme der Wrmepumpe entnehmen Sie der Pro-duktinformation oder dem Typschild. Die Anschlussklemmensind fr max. 10 mm Leiterquerschnitt ausgelegt.

    ACHTUNG!Bei Anschluss der Lastleitung auf Rechtsdrehfeld achten (bei falschemDrehfeld bringt die Wrmepumpe keine Leistung und ist sehr laut).www.dimplex.de D-5

  • Deutsch

    88 Inbetriebnahme

    8.1 Allgemeine HinweiseUm eine ordnungsgeme Inbetriebnahme zu gewhrleisten,sollte diese von einem vom Werk autorisierten Kundendienstdurchgefhrt werden. Unter bestimmten Bedingungen ist damiteine Verlngerung der Gewhrleistung verbunden (vgl. Garan-tieleistungen).

    8.2 VorbereitungVor der Inbetriebnahme mssen folgende Punkte geprft wer-den: Alle Anschlsse der Wrmepumpe mssen, wie in Kapitel 7

    beschrieben, montiert sein. Die Wrmequellenanlage und der Heizkreis mssen gefllt

    und geprft sein. Der Schmutzfnger muss im Soleeintritt der Wrmepumpe

    eingebaut sein. Im Sole- und Heizkreis mssen alle Schieber, die den kor-

    rekten Fluss behindern knnten, geffnet sein. Der Wrmepumpenregler muss gem seiner Gebrauchs-

    anweisung auf die Heizungsanlage abgestimmt sein.

    8.3 Vorgehensweise bei Inbetriebnahme

    Die Inbetriebnahme der Wrmepumpe erfolgt ber den Wrme-pumpenregler.

    ACHTUNG!Die Inbetriebnahme der Wrmepumpe muss gem der Montage- undGebrauchsanweisung des Wrmepumpenreglers erfolgen.

    Wird der Mindestheizwasserdurchsatz mittels berstrmventilsichergestellt, so ist dieses auf die Heizungsanlage abzustim-men. Eine falsche Einstellung kann zu verschiedenen Fehlerbil-dern und einem erhhten elektrischen Energiebedarf fhren. Umdas berstrmventil richtig einzustellen, empfehlen wir folgendeVorgehensweise:Schlieen Sie alle Heizkreise, die auch im Betrieb je nach Nut-zung geschlossen sein knnen, so dass der vom Wasserdurch-satz ungnstigste Betriebs-zustand vorliegt. Dies sind in derRegel die Heizkreise der Rume auf der Sd- und Westseite.Mindestens ein Heizkreis muss geffnet bleiben (z.B. Bad).Das berstrmventil ist so weit zu ffnen, dass sich bei der aktu-ellen Wrmequellentemperatur die in der unten stehenden Ta-belle angegebene maximale Temperaturspreizung zwischenHeizungsvor- und Rcklauf ergibt. Die Temperaturspreizung istmglichst nahe an der Wrmepumpe zu messen. Bei monoener-getischen Anlagen ist der Heizstab zu deaktivieren.

    Strungen whrend des Betriebes werden am Wrmepumpen-regler angezeigt und knnen, wie in der Gebrauchsanweisungdes Wrmepumpenreglers beschrieben ist, behoben werden.

    Wrmequellen-temperatur

    max. Temperaturspreizung zwischen Heizungsvor- und

    Rcklaufvon bis-5 C 0 C 10 K

    1 C 5 C 11 K

    6 C 9 C 12 K

    10 C 14 C 13 K

    15 C 20 C 14 K

    21 C 25 C 15 KD-6

  • Deu

    tsch

    119 Pflege / Reinigung

    9.1 PflegeDie Wrmepumpe arbeitet wartungsfrei. Um Betriebsstrungendurch Schmutzablagerungen in den Wrmeaustauschern zu ver-meiden, ist dafr Sorge zu tragen, dass keinerlei Verschmutzun-gen in die Wrmequellen- und Heizungsanlage gelangen kn-nen. Sollte es dennoch zu derartigen Betriebsstrungenkommen, ist die Anlage wie unten angegeben zu reinigen.

    9.2 Reinigung HeizungsseiteSauerstoff kann im Heizwasserkreis, insbesondere bei Verwen-dung von Stahlkomponenten, Oxidationsprodukte (Rost) bilden.Dieser gelangt ber Ventile, Umwlzpumpen oder Kunststoff-rohre in das Heizsystem. Deshalb sollte besonders bei denRohren der Fubodenheizung auf eine diffusionsdichte Instal-lation geachtet werden.

    ACHTUNG!Zur Vermeidung von Ablagerungen (z.B. Rost) im Kondensator derWrmepumpe wird empfohlen, ein geeignetes Korrosionsschutzsystemeinzusetzen.

    Auch Reste von Schmier- und Dichtmitteln knnen das Heizwas-ser verschmutzen.Sind die Verschmutzungen so stark, dass sich die Leistungsf-higkeit des Verflssigers in der Wrmepumpe verringert, mussein Installateur die Anlage reinigen.Nach heutigem Kenntnisstand schlagen wir vor, die Reinigungmit einer 5%-igen Phosphorsure oder, falls hufiger gereinigtwerden muss, mit einer 5%-igen Ameisensure durchzufhren.In beiden Fllen sollte die Reinigungsflssigkeit Raumtempera-tur haben. Es ist empfehlenswert, den Wrmeaustauscher ent-gegen der normalen Durchflussrichtung zu splen.Um zu verhindern, dass surehaltiges Reinigungsmittel in denHeizungsanlagenkreislauf gelangt, empfehlen wir, das Splgertdirekt an den Vor- und Rcklauf des Verflssigers anzuschlie-en. Danach muss mit geeigneten neutralisierenden Mittelngrndlich nachgesplt werden, um Beschdigungen durch even-tuell im System verbliebene Reinigungsmittelreste zu verhin-dern.Die Suren sind mit Vorsicht anzuwenden und es sind die Vor-schriften der Berufsgenossenschaften einzuhalten.Im Zweifelsfall ist mit dem Hersteller des ReinigungsmittelsRcksprache zu halten!

    9.3 Reinigung Wrmequellenseite

    ACHTUNG!Im Wrmequelleneintritt der Wrmepumpe ist der beiliegendeSchmutzfnger zu montieren, um den Verdampfer gegenVerunreinigungen zu schtzen.

    Einen Tag nach der Inbetriebnahme sollte das Filtersieb desSchmutzfngers gereinigt werden, danach wchentlich reinigen.Sind keine Verunreinigungen mehr erkennbar, kann das Siebdes Schmutzfngers ausgebaut werden, um die Druckverlustezu reduzieren.

    10 Strungen / FehlersucheDiese Wrmepumpe ist ein Qualittsprodukt und sollte strungs-frei arbeiten. Tritt dennoch eine Strung auf, wird dies im Displaydes Wrmepumpenamanagers angezeigt. Schlagen Sie dazuauf der Seite Strungen und Fehlersuche in der Gebrauchsan-weisung des Wrmepumpenreglers nach.Wenn die Strung nicht selbst behoben werden kann, verstndi-gen Sie bitte den zustndigen Kundendienst.

    ACHTUNG!Arbeiten an der Wrmepumpe drfen nur vom autorisierten undsachkundigen Kundendienst durchgefhrt werden.

    ACHTUNG!Vor ffnen des Gertes sind alle Stromkreise spannungsfrei zu schalten.

    11 Auerbetriebnahme / Entsorgung

    Bevor die Wrmepumpe ausgebaut wird, ist die Maschine span-nungsfrei zu schalten und abzuschiebern. Umweltrelevante An-forderungen, in Bezug auf Rckgewinnung, Wiederverwendungund Entsorgung von Betriebsstoffen und Bauteilen gem dengngigen Normen, sind einzuhalten. Dabei ist besonders Wertauf eine fachgerechte Entsorgung des Kltemittels und Klteleszu legen.www.dimplex.de D-7

  • Deutsch

    1212 GerteinformationGerteinformation fr Sole/Wasser-Heiz-Wrmepumpen SI 5TE - SI 11TE

    1 Typ- und Verkaufsbezeichnung SI 5TE SI 7TE SI 9TE SI 11TE2 Bauform2.1 Schutzart nach EN 60 529 IP 20 IP 20 IP 20 IP 20

    2.2 Aufstellungsort Innen Innen Innen Innen

    3 Leistungsangaben3.1 Temperatur-Betriebseinsatzgrenzen:

    Heizwasser-Vorlauf C bis 58 bis 58 bis 58 bis 58

    Sole (Wrmequelle) C -5 bis +25 -5 bis +25 -5 bis +25 -5 bis +25

    Frostschutzmittel Monoethylengly-kol Monoethylengly-

    kol Monoethylengly-

    kol Monoethylengly-

    kol

    Minimale Solekonzentration (-13C Einfriertemperatur) 25% 25% 25% 25%

    3.2 Heizwasser-Temperaturspreizung bei B0 / W35 K 10,1 5,0 9,9 5,0 10,5 5,0 10,1 5,0

    3.3 Wrmeleistung / Leistungszahl bei B-5 / W55 1 kW / ---

    1. Diese Angaben charakterisieren die Gre und die Leistungsfhigkeit der Anlage. Fr wirtschaftliche und energetische Betrachtungen sind Bivalenzpunkt und Regelung zu be-rcksichtigen. Dabei bedeuten z.B. B10 / W55: Wrmequellentemperatur 10 C und Heizwasser-Vorlauftemperatur 55 C.

    3,8 / 2,0 5,6 / 2,2 7,7 / 2,3 9,4 / 2,4

    bei B0 / W45 1 kW / --- 5,0 / 2,9 6,6 / 3,0 8,7 / 3,211,2 /

    3,2

    bei B0 / W50 1 kW / --- 4,8 / 2,8 6,7 / 2,9 9,0 / 3,111,3 /

    3,0

    bei B0 / W35 1 kW / --- 5,3 / 4,3 5,2 / 4,1 6,9 / 4,3 6,8 / 4,1 9,2 / 4,4 9,0 / 4,211,8 /

    4,411,7 /

    4,2

    3.4 Schall-Leistungspegel dB(A) 54 55 56 56

    3.5 Heizwasserdurchfluss bei interner Druckdifferenz m/h / Pa 0,45 / 19000,9 / 7400

    0,6 /3300

    1,2 / 13000

    0,75 / 2300

    1,6 / 10300

    1,0 /4100

    2,0 / 16100

    3.6 Soledurchsatz bei interner Druckdifferenz (Wrmequelle) m/h / Pa 1,2 /160001,2 /

    160001,7 /

    295001,6 /

    265002,3 /

    250002,2 /

    230003,0 /

    240002,7 /

    20000

    3.7 Kltemittel; Gesamt-Fllgewicht Typ / kg R407C / 1,2 R407C / 1,1 R407C / 1,6 R407C / 1,7

    4 Abmessungen, Anschlsse und Gewicht4.1 Gerteabmessungen ohne Anschlsse 2 H x B x L mm

    2. Beachten Sie, dass der Platzbedarf fr Rohranschluss, Bedienung und Wartung grer ist.

    805 650 462 805 650 462 805 650 462 805 650 4624.2 Gerteanschlsse fr Heizung Zoll G 1" a G 1" a G 1" a G 1" a

    4.3 Gerteanschlsse fr Wrmequelle Zoll G 1" a G 1" a G 1" a G 1" a

    4.4 Gewicht der Transporteinheit(en) incl. Verpackung kg 109 111 118 122

    5 Elektrischer Anschluss5.1 Nennspannung; Absicherung V / A 400 / 16 400 / 16 400 / 16 400 / 16

    5.2 Nennaufnahme 1 B0 W35 kW 1,23 1,27 1,6 1,66 2,07 2,14 2,66 2,79

    5.3 Anlaufstrom m. Sanftanlasser A 22 (ohne SA) 30 (ohne SA) 15 26

    5.4 Nennstrom B0 W35 / cos A / --- 2,22 / 0,82,29 /

    0,82,89 / 0,8 3 / 0,8

    3,77 / 0,8

    3,86 / 0,8

    4,84 / 0,8

    5,03 / 0,8

    6 Entspricht den europischen Sicherheitsbestimmungen 3

    3. siehe CE-Konformittserklrung

    3 3 3

    7 Sonstige Ausfhrungsmerkmale7.1 Wasser im Gert gegen Einfrieren geschtzt 4

    4. Die Heizungs-Umwlzpumpe und der Regler der Wrmepumpe mssen immer betriebsbereit sein.

    ja ja ja ja

    7.2 Leistungsstufen 1 1 1 1

    7.3 Regler intern / extern intern intern intern internD-8

  • Deu

    tsch

    12Gerteinformation fr Sole/Wasser-Heiz-Wrmepumpen SI 14TE - SI 21TE

    1 Typ- und Verkaufsbezeichnung SI 14TE SI 17TE SI 21TE2 Bauform2.1 Schutzart nach EN 60 529 IP 20 IP 20 IP 20

    2.2 Aufstellungsort Innen Innen Innen

    3 Leistungsangaben3.1 Temperatur-Betriebseinsatzgrenzen:

    Heizwasser-Vorlauf C bis 58 bis 58 bis 58

    Sole (Wrmequelle) C -5 bis +25 -5 bis +25 -5 bis +25

    Frostschutzmittel Monoethylenglykol Monoethylenglykol Monoethylenglykol

    Minimale Solekonzentration (-13C Einfriertemperatur) 25% 25% 25%

    3.2 Heizwasser-Temperaturspreizung bei B0 / W35 K 9,6 5,0 9,3 5,0 11,3 5,0

    3.3 Wrmeleistung / Leistungszahl bei B-5 / W55 1 kW / --- 12,5 / 2,6 14,4 / 2,6 17,9 / 2,5

    bei B0 / W45 1 kW / --- 14,1 / 3,5 16,2 / 3,4 19,8 / 3,2

    bei B0 / W50 1 kW / --- 14,2 / 3,4 16,7 / 3,2 20,4 / 3,1

    bei B0 / W35 1 kW / --- 14,5 / 4,5 14,4 / 4,3 17,1 / 4,6 16,9 / 4,4 21,1 / 4,3 20,8 / 4,1

    3.4 Schall-Leistungspegel dB(A) 56 58 59

    3.5 Heizwasserdurchfluss bei interner Druckdifferenz m/h / Pa 1,3 / 4800 2,5 / 17600 1,5 / 4000 2,9 / 15000 1,6 / 4600 3,6 / 23000

    3.6 Soledurchsatz bei interner Druckdifferenz (Wrmequelle) m/h / Pa 3,5 / 20000 3,3 / 18000 3,8 / 18000 3,8 / 18000 5,5 / 10000 5,4 / 9800

    3.7 Kltemittel; Gesamt-Fllgewicht Typ / kg R407C / 2,1 R407C / 2,3 R407C / 4,5

    4 Abmessungen, Anschlsse und Gewicht4.1 Gerteabmessungen ohne Anschlsse 2 H x B x L mm 805 650 462 805 650 462 1445 650 5754.2 Gerteanschlsse fr Heizung Zoll G 1" a G 1" a G 1" a

    4.3 Gerteanschlsse fr Wrmequelle Zoll G 1" a G 1" a G 1" a

    4.4 Gewicht der Transporteinheit(en) incl. Verpackung kg 130 133 225

    5 Elektrischer Anschluss5.1 Nennspannung; Absicherung V / A 400 / 16 400 / 16 400 / 20

    5.2 Nennaufnahme 1 B0 W35 kW 3,22 3,37 3,72 3,86 4,91 5,10

    5.3 Anlaufstrom m. Sanftanlasser A 26 27 29

    5.4 Nennstrom B0 W35 / cos A / --- 5,81 / 0,8 6,08 / 0,8 6,35 / 0,8 6,64 / 0,8 8,86 / 0,8 9,2 / 0,86 Entspricht den europischen Sicherheitsbestimmungen 3 3 3

    7 Sonstige Ausfhrungsmerkmale7.1 Wasser im Gert gegen Einfrieren geschtzt 4 ja ja ja

    7.2 Leistungsstufen 1 1 1

    7.3 Regler intern / extern intern intern intern

    1. Diese Angaben charakterisieren die Gre und die Leistungsfhigkeit der Anlage. Fr wirtschaftliche und energetische Betrachtungen sind Bivalenzpunkt und Regelung zu be-rcksichtigen. Dabei bedeuten z.B. B10 / W55: Wrmequellentemperatur 10 C und Heizwasser-Vorlauftemperatur 55 C.

    2. Beachten Sie, dass der Platzbedarf fr Rohranschluss, Bedienung und Wartung grer ist.

    3. siehe CE-Konformittserklrung4. Die Heizungs-Umwlzpumpe und der Regler der Wrmepumpe mssen immer betriebsbereit sein.www.dimplex.de D-9

  • D-10

    Deutsch

    13

    13 GarantieurkundeDie nachstehenden Bedingungen, die Voraussetzungen undUmfang unserer Garantieleistung umschreiben, lassen die Ge-whrleistungsverpflichtungen des Verkufers aus dem Kaufver-trag mit dem Endabnehmer unberhrt. Fr die Gerte leisten wirGarantie gem nachstehenden Bedingungen:Wir beheben unentgeltlich nach Magabe der folgenden Bedin-gungen Mngel am Gert, die nachweislich auf einem Material-und/oder Herstellungsfehler beruhen, wenn sie uns unverzglichnach Feststellung und innerhalb von 24 Monaten nach Lieferungan den Erstendabnehmer gemeldet werden. Bei gewerblichemGebrauch innerhalb von 12 Monaten. Zeigt sich der Mangel in-nerhalb von 6 Monaten ab Lieferung und liegt eine erfolgreicheInbetriebnahme (Heizungs-Wrmepumpe und zentrale Woh-nungslftungsgerte) durch den autorisierten Systemtechnik-Kundendienst vor, wird vermutet, dass es sich um einen Mate-rial- oder Herstellungsfehler handelt.Dieses Gert fllt nur dann unter diese Garantie, wenn es voneinem Unternehmer in einem der Mitgliedstaaten der Eur-opischen Union gekauft wurde, es bei Auftreten des Mangels inDeutschland betrieben wird und Garantieleistungen auch inDeutschland erbracht werden knnen.Die Behebung der von uns als garantiepflichtig anerkannterMngel geschieht dadurch, dass die mangelhaften Teile unent-geltlich nach unserer Wahl instandgesetzt oder durch einwand-freie Teile ersetzt werden. Durch Art oder Ort des Einsatzes desGertes oder schlechte Zugnglichkeit des Gertes bedingte au-ergewhnliche Kosten der Mngelbeseitigung werden nichtbernommen. Der freie Gertezugang muss durch den Endab-nehmer gestellt werden. Ausgebaute Teile, die wir zurckneh-men, gehen in unser Eigentum ber. Die Garantiezeit fr Nach-besserungen und Ersatzteile endet mit dem Ablauf derursprnglichen Garantiezeit fr das Gert. Die Garantie erstrecktsich nicht auf leicht zerbrechliche Teile, die den Wert oder dieGebrauchstauglichkeit des Gertes nur unwesentlich beein-trchtigen. Es ist jeweils der Original-Kaufbeleg mit Kauf- und/oder Lieferdatum vorzulegen.Eine Garantieleistung entfllt, wenn vom Endabnehmer odereinem Dritten die entsprechenden VDE-Vorschriften, die Bestim-mungen der rtlichen Versorgungsunternehmen oder unsereMontage- und Gebrauchsanweisung sowie die in den Projektie-rungsunterlagen enthaltenen Hinweise oder Einbindungssche-men nicht beachtet worden sind oder wenn unser funktionsnot-wendiges Zubehr nicht eingesetzt wurde. Durch etwa seitensdes Endabnehmers oder Dritter unsachgem vorgenommenennderungen und Arbeiten, wird die Haftung fr die daraus ent-stehenden Folgen aufgehoben. Die Garantie erstreckt sich aufdas Gert und vom Lieferer bezogene Teile. Nicht vom Liefererbezogene Teile und Gerte-/Anlagenmngel die auf nicht vomLieferer bezogene Teile zurckzufhren sind fallen nicht unterden Garantieanspruch.Sofern der Mangel nicht beseitigt werden kann, oder die Nach-besserung von uns abgelehnt oder unzumutbar verzgert wird,wird der Hersteller entweder kostenfreien Ersatz liefern oder denMinderwert vergten. Im Falle einer Ersatzlieferung, behalten wiruns die Geltendmachung einer angemessenen Nutzungsanrech-nung, fr die bisherige Nutzungszeit, vor. Weitergehende oderandere Ansprche, insbesondere solche auf Ersatz auerhalbdes Gertes entstandener Schden sind soweit eine Haftungnicht zwingend gesetzlich angeordnet ist ausgeschlossen. Beieiner Haftung nach 478 BGB wird die Haftung des Lieferers aufdie Servicepauschalen des Lieferers als Hchstbetrag be-schrnkt.

    Eine Verlngerung der Garantie auf 36 Monate fr Heizungs-Wrmepumpen und zentrale Wohnungslftungsgerte ab Inbe-triebnahmedatum, jedoch maximal 38 Monate ab AuslieferungWerk, wird gem den nachfolgenden Bedingungen gewhrt:Voraussetzung fr die bernahme der verlngerten Garantie isteine kostenpflichtige Inbetriebnahme durch den autorisiertenSystemtechnik-Kundendienst mit Inbetriebnahmeprotokoll inner-halb einer Betriebszeit (Verdichterlaufzeit) von weniger als 150Stunden. Im Inbetriebnahmeprotokoll vermerkte Mngel sind un-verzglich zu beseitigen. Dies ist Grundlage fr die Garantie.Das Inbetriebnahmeprotokoll ist, innerhalb von einem Monatnach erfolgter Inbetriebnahme, an die unten angegebeneAdresse einzureichen, von welcher auch die Garantiezeitver-lngerung besttigt wird.Die Inbetriebnahmepauschale beinhaltet die eigentliche Inbe-triebnahme und die Fahrtkosten. Es wird keine Haftung fr dieordnungsgeme Planung, Dimensionierung und Ausfhrungder Gesamtanlage bernommen. Die Behebung von Anlagen-mngel und Wartezeiten sind Sonderleistungen.Die Inbetriebnahmepauschale fr alle Heizungs-Wrmepumpenvon derzeit netto Euro 340,-- und fr zentrale Lftungsanlagenvon netto Euro 400,--, jeweils je Gert, wird durch den autorisier-ten Systemtechnik-Kundendienst dem Auftraggeber in Rech-nung gestellt. Eine Preisanpassung ist vorbehalten.Im Kundendienstfalle wird der autorisierte Systemtechnik-Kun-dendienst vor Ort informiert, der fr eine schnelle Abhilfe desProblems sorgt. Den fr Ihre Region zustndigen autorisiertenSystemtechnik-Kundendienst erfahren Sie ber die zentrale Ser-vicehotline der Glen Dimplex Deutschland GmbH.Glen Dimplex Deutschland GmbHGeschftsbereich DimplexKundendienst SystemtechnikAm Goldenen Feld 1895326 Kulmbach

    Fr die Auftragsbearbeitung werden die Erzeugnisnummer E-Nr.und das Fertigungsdatum FD des Gertes bentigt. Diese Anga-ben befinden sich auf dem Typschild in dem stark umrandetenFeld.

    Kundendienstadresse:

    Tel.-Nr.:Fax.-Nr.:E-Mail-Adresse:

    Internet:

    +49 (0) 9221 709 562+49 (0) 9221 709 [email protected]@dimplex.dewww.dimplex.de

  • www.dimplex.de E-1

    Engl

    ish

    Table of contents1 Please Read Immediately .............................................................................................................E-2

    1.1 Important Information..............................................................................................................................E-21.2 Legal Regulations and Directives ...........................................................................................................E-21.3 Energy-Efficient Use of the Heat Pump ..................................................................................................E-2

    2 Purpose of the Heat Pump ...........................................................................................................E-32.1 Application ..............................................................................................................................................E-32.2 Operating Principle .................................................................................................................................E-3

    3 Basic Device ..................................................................................................................................E-3

    4 Accessories ...................................................................................................................................E-44.1 Brine Circuit Manifold..............................................................................................................................E-4

    5 Transport........................................................................................................................................E-4

    6 Set-up .............................................................................................................................................E-46.1 General Information ................................................................................................................................E-46.2 Acoustic Emissions.................................................................................................................................E-4

    7 Installation .....................................................................................................................................E-57.1 General Information ................................................................................................................................E-57.2 Heating System Connection ...................................................................................................................E-57.3 Heat Source Connection.........................................................................................................................E-57.4 Electrical Connection ..............................................................................................................................E-5

    8 Commissioning .............................................................................................................................E-68.1 General Information ................................................................................................................................E-68.2 Preparation .............................................................................................................................................E-68.3 Start-up Procedure .................................................................................................................................E-6

    9 Maintenance and Cleaning ...........................................................................................................E-79.1 Maintenance ...........................................................................................................................................E-79.2 Cleaning the Heating System .................................................................................................................E-79.3 Cleaning the Heat Source System..........................................................................................................E-7

    10 Faults / Trouble-Shooting.............................................................................................................E-7

    11 Decommissioning / Disposal .......................................................................................................E-7

    12 Device Information ........................................................................................................................E-8

    Anhang / Appendix / Annexes ............................................................................................................ A-I

  • English

    11 Please Read Immediately

    1.1 Important Information

    ATTENTION!The heat pump is not secured to the wooden pallet.

    ATTENTION!The heat pump must not be tilted more than 45 (in any direction).

    ATTENTION!Do not use the holes in the panel assemblies for lifting the device!

    ATTENTION!Flush the heating system prior to connecting the heat pump.

    ATTENTION!The supplied dirt trap must be inserted in the heat source inlet of the heatpump to protect the evaporator against the ingress of impurities.

    ATTENTION!The brine solution must contain at least a 25 % concentration of amonoethylene glycol or propylene glycol-based antifreeze, which mustbe mixed before filling.

    ATTENTION!Observe the clockwise rotating field when connecting the mains cable (ifrotating field is not clockwise, the heat pump will not work properly andwill be very noisy).

    ATTENTION!The heat pump must be started up in accordance with the installation andoperating instructions of the heat pump controller.

    ATTENTION!We recommend the installation of a suitable corrosion protection systemto prevent the formation of deposits (e.g. rust) in the condenser of theheat pump.

    ATTENTION!Any work on the heat pump may only be performed by authorised andqualified after-sales service technicians.

    ATTENTION!Disconnect all electrical circuits from the power source prior to openingthe device.

    1.2 Legal Regulations and Directives

    This heat pump conforms to all relevant DIN/VDE regulationsand EU directives. Refer to the EC Declaration of Conformity inthe appendix for details.The heat pump must be connected to the power supply in com-pliance with all relevant VDE, EN and IEC standards. Any furtherconnection requirements stipulated by local utility companiesmust also be observed.The heat pump is to be connected to the heat source system andthe heating system in accordance with all applicable regulations.Persons, especially children, who are not capable of operatingthe device safely due to their physical, sensory or mental abilitiesor their inexperience or lack of knowledge, must not operate thisdevice without supervision or instruction by the person in charge. Children must be supervised to ensure that they do not play withthe device.

    1.3 Energy-Efficient Use of the Heat Pump

    By operating this heat pump you are helping to protect our envi-ronment. Both the heating system and the heat source must beproperly designed and dimensioned to ensure efficient operation.It is particularly important to keep water flow temperatures as lowas possible. All connected energy consumers should thereforebe suitable for low flow temperatures. Raising the heating watertemperature by 1 K corresponds to an increase in energy con-sumption of approx. 2.5 %. Low-temperature heating systems with flow temperaturesbetween 30 C and 50 C are particularly well-suited for energy-efficient operation.E-2

  • Engl

    ish

    32 Purpose of the Heat Pump

    2.1 ApplicationThe brine-to-water heat pump is designed for use in existing ornewly built heating systems. Brine is used as the heat carrier inthe heat source system. Borehole heat exchangers, ground heatcollectors or similar systems can be used as the heat source.

    2.2 Operating PrincipleThe heat generated by the sun, wind and rain is stored in theground. This heat stored in the ground is collected at a low tem-perature by the brine circulating in the ground collector, groundcoil or similar device. A circulating pump then conveys theheated brine to the evaporator of the heat pump. There the heatis given off to the refrigerant in the refrigerating cycle. This coolsthe brine so that it can once again absorb thermal energy in thebrine circuit.The refrigerant is drawn in by the electrically driven compressor,compressed and pumped to a higher temperature level. Theelectrical power needed to run the compressor is not lost in thisprocess. Most of it is absorbed by the refrigerant.Subsequently, the refrigerant is passed through the condenserwhere it transfers its heat energy to the heating water. Depend-ing on the set operating point (thermostat setting), the heatingwater is thus heated up to a max. of 60 C.

    3 Basic DeviceThe basic device consists of a ready-to-use heat pump for indoorinstallation, complete with sheet metal casing, control panel andintegrated controller. The refrigerating cycle contains the refriger-ant R407C. R407C refrigerant is CFC-free, non-ozone depletingand non-combustible.All components required for the operation of the heat pump arelocated on the control panel. An external wall temperature sensorincluding fixing accessories and a dirt trap are supplied with theheat pump. The power feed for the load current and the controlcurrent must be installed by the customer.The supply lead of the brine circulating pump (to be provided bythe customer) must be connected to the control panel. If re-quired, the supply lead of the brine pump is be equipped with amotor protection device.The customer must provide both the collector and the brine cir-cuit manifold.

    1) Liquifier2) Control panel3) Evaporator4) Compressor

    www.dimplex.de E-3

  • English

    44 Accessories

    4.1 Brine Circuit ManifoldThe brine circuit manifold merges the individual collector loops ofthe heat source system into a single main pipe which is con-nected to the heat pump. Integrated ball valves allow the individ-ual brine circuits to be shut off for de-aeration purposes.

    5 TransportA lift truck is suited for transporting the unit on a level surface.Carrying straps may be used if the heat pump needs to be trans-ported on an uneven surface or carried up or down stairs. Thesestraps can be passed directly underneath the wooden pallet.

    ATTENTION!The heat pump is not secured to the wooden pallet.

    ATTENTION!The heat pump must not be tilted more than 45 (in any direction).

    Use the holes provided in the sides of the frame to lift the unitwithout the pallet. The side panel assemblies must be removedfor this purpose. Any commercially available length of pipe canbe used as a carrying aid.

    ATTENTION!Do not use the holes in the panel assemblies for lifting the device!

    6 Set-up

    6.1 General InformationThe unit may only be installed indoors in rooms with low humidityon a level, smooth and horizontal surface. The entire base of theframe should lie directly on the floor to ensure a good soundproofseal. If this is not the case, additional sound insulation measuresmay be necessary.The heat pump must be installed so that maintenance work canbe carried out without hindrance. This can be ensured by main-taining a clearance of approx. 1 m in front of and on each side ofthe heat pump.

    6.2 Acoustic EmissionsThe heat pump operates silently due to efficient sound insulation.To prevent noise transmission to the foundation, a suitable,sound dampening rubber mat should be placed underneath thebase frame of the heat pump.To prevent any sound from being transmitted to the heating sys-tem, we recommend connecting the heat pump to the heatingsystem by means of hose sections.E-4

  • Engl

    ish

    7.47 Installation

    7.1 General InformationThe following connections need to be established on the heatpump: Flow and return flow of the brine system Flow and return flow of the heating system Power supply

    7.2 Heating System Connection

    ATTENTION!Flush the heating system prior to connecting the heat pump.

    Before connecting the heating water system to the heat pump,the heating system must be flushed to remove any impurities,residue from sealants, etc. Any accumulation of deposits in theliquifier could cause the heat pump to completely break down.Once the heating system has been installed, it must be filled, de-aerated and pressure-tested.The sensors which are delivered already connected and looselyplaced in the switch box must be mounted and insulated accord-ing to the block diagram.

    Minimum heating water flow rateThe minimum heating water flow rate through the heat pumpmust be assured in all operating states of the heating system.This can be accomplished, for example, by installing either amanifold without differential pressure or an overflow valve. Theprocedure for adjusting an overflow valve is described in theChapter Start-Up.

    Antifreeze protection for installation locations prone to frostThe antifreeze function of the heat pump controller is activewhenever the controller and the heat circulating pumps are readyfor operation. If the heat pump is taken out of service or in theevent of a power failure, the system has to be drained. The heat-ing circuit should be operated with a suitable antifreeze if heatpump systems are implemented in buildings where a power fail-ure can not be detected (holiday home).

    7.3 Heat Source ConnectionThe following procedure must be observed when connecting theheat source:Connect the brine pipe to the heat pump flow and return. The hy-draulic plumbing diagram must be adhered to.

    ATTENTION!The supplied dirt trap must be inserted in the heat source inlet of the heatpump to protect the evaporator against the ingress of impurities.

    In addition, a micro bubble air separator must be installed in theheat source system.The brine liquid must be produced prior to charging the system.The liquid must have an antifreeze concentration of at least 25 %to ensure frost protection down to -14 C.Only monoethylene glycol or propylene glycol-based antifreezemay be used.The heat source system must be de-aerated and checked forleaks.

    ATTENTION!The brine solution must contain at least a 25 % concentration of amonoethylene glycol or propylene glycol-based antifreeze, which mustbe mixed before filling.

    7.4 Electrical ConnectionThe following electrical connections must be established on theheat pump: Connection of the control line to the control panel of the heat

    pump via terminal X1: L/N/PE. Connection of the mains cable to the control panel of the

    heat pump via terminal X5/X6: L1/L2/L3/PE. Connection of the brine circulating pump (to be provided by

    the customer) to the control panel of the heat pump via ter-minal X1: PE and pump contactor K2: 2/4/6 (SI 5TE -SI 17TE), or motor protection F7: 2/4/6 (SI 21TE). Option-ally, a single-phase brine pump can be used for the SI 5TEto SI 14TE series (see terminal connection plan).

    All electrical components required for the operation of the heatpump are located on the control panel.For detailed instructions concerning the connection and function-ing of the heat pump controller (e.g. external wall sensor includedin the scope of supply) refer to the operating manual suppliedwith the controller.An all-pole disconnecting device with a contact gap of at least 3mm (e.g. utility blocking contactor or power contactor) as well asa 3-pole circuit breaker with common tripping for all external con-ductors have to be provided by the customer. The required con-ductor cross section is to be selected according to the powerconsumption of the heat pump, the technical connection require-ments of the respective utility company as well as all applicableregulations. Details on the power consumption of the heat pumpare listed on both the product information sheet and the typeplate. The connection terminals are designed for a max. conduc-tor cross section of 10 mm.

    ATTENTION!Observe the clockwise rotating field when connecting the mains cable (ifrotating field is not clockwise, the heat pump will not work properly andwill be very noisy).www.dimplex.de E-5

  • English

    88 Commissioning

    8.1 General InformationTo ensure that start-up is performed correctly, it should only becarried out by an after-sales service technician authorised by themanufacturer. This may be a condition for extending the guaran-tee (see Warranty).

    8.2 PreparationThe following items need to be checked prior to start-up: The heat pump must be fully connected, as described in

    Chapter 7. The heat source system and the heating circuit must have

    been filled and checked. The dirt trap must be inserted in the brine inlet of the heat

    pump. All valves that could impair proper flow in the brine and heat-

    ing circuits must be open. The heat pump controller must be adapted to the heating

    system in accordance with the controllers operating instruc-tions.

    8.3 Start-up ProcedureThe heat pump is started up via the heat pump controller.

    ATTENTION!The heat pump must be started up in accordance with the installation andoperating instructions of the heat pump controller.

    If an overflow valve is fitted to assure the minimum heating waterflow rate, the valve must be set in accordance with the require-ments of the respective heating system. Incorrect adjustmentcan lead to faulty operation and increased energy consumption.We recommend carrying out the following procedure to correctlyadjust the overflow valve:Close all of the heating circuits that may also be closed duringoperation (depending on the type of heat pump usage) so thatthe most unfavourable operating state - with respect to the waterflow rate - is achieved. This normally means the heating circuitsof the rooms on the south and west sides of the building. At leastone heating circuit must remain open (e.g. bathroom).The overflow valve should be opened far enough to produce themaximum temperature spread between the heating flow and re-turn flow listed in the table below for the current heat source tem-perature. The temperature spread should be measured as closeas possible to the heat pump. The heating element of mono en-ergy systems should be disconnected.

    Any faults occurring during operation are displayed on the heatpump controller and can be corrected as described in the operat-ing manual of the heat pump controller.

    Heat sourcetemperature

    Max. temperature spreadbetween heating flow and return

    flowFrom To-5 C 0 C 10 K

    1 C 5 C 11 K

    6 C 9 C 12 K

    10 C 14 C 13 K

    15 C 20 C 14 K

    21 C 25 C 15 KE-6

  • Engl

    ish

    119 Maintenance and Cleaning

    9.1 MaintenanceThe heat pump is maintenance-free. To prevent faults due tosediment in the heat exchangers, care must be taken to ensurethat no impurities can enter either the heat source system or theheating system. In the event that operating malfunctions due tocontamination occur nevertheless, the system should be cleanedas described below.

    9.2 Cleaning the Heating SystemThe ingress of oxygen into the heating water circuit may result inthe formation of oxidation products (rust), particularly if steelcomponents are used. This oxygen enters the heating system viathe valves, the circulating pumps and/or plastic pipes. It is there-fore essential - in particular with respect to the piping of under-floor heating systems - that only diffusion-proof materials areused.

    ATTENTION!We recommend the installation of a suitable corrosion protection systemto prevent the formation of deposits (e.g. rust) in the condenser of theheat pump.

    Residue from lubricants and sealants may also contaminate theheating water.In the case of severe contamination leading to a reduction in theperformance of the liquifier in the heat pump, the system must becleaned by a heating technician.According to todays state of knowledge, we recommend using a5 % phosphoric acid solution for cleaning purposes. However, ifcleaning needs to be performed more frequently, a 5 % formicacid solution should be used.In either case, the cleaning fluid should be at room temperature.We recommend flushing the heat exchanger in the direction op-posite to the normal flow direction.To prevent acidic cleaning agents from entering the heating sys-tem circuit, we recommend connecting the flushing device di-rectly to the flow and return flow of the liquifier. It is important thatthe system be thoroughly flushed using appropriate neutralisingagents to prevent any damage from being caused by cleaningagent residue remaining in the system.Acids must be used with great care and all relevant regulations ofthe employers liability insurance associations must be adheredto.If in doubt, contact the manufacturer of the chemicals!

    9.3 Cleaning the Heat Source System

    ATTENTION!The supplied dirt trap must be inserted in the heat source inlet of the heatpump to protect the evaporator against the ingress of impurities.

    Clean the dirt traps filter screen one day after start-up and sub-sequently in weekly intervals. If no more signs of contaminationare evident, the filter can be removed to reduce pressure drops.

    10 Faults / Trouble-Shooting

    This heat pump is a quality product and is designed for trouble-free operation. In the event that a fault should occur, it will be in-dicated on the heat pump manager display. Simply consult theFaults and Trouble-Shooting page in the operating instructions ofthe heat pump controller.If you cannot correct the fault yourself, please contact your after-sales service technician.

    ATTENTION!Any work on the heat pump may only be performed by authorised andqualified after-sales service technicians.

    ATTENTION!Disconnect all electrical circuits from the power source prior to openingthe device.

    11 Decommissioning / Disposal

    Before removing the heat pump, disconnect it from the powersource and close all valves. Observe all environmentally-relevantrequirements regarding the recovery, recycling and disposal ofmaterials and components in accordance with all applicablestandards. Particular attention should be paid to the proper dis-posal of refrigerants and refrigeration oils.www.dimplex.de E-7

  • English

    1212 Device InformationDevice information for brine-to-water heat pumps for heating purposes SI 5TE - SI 11TE

    1 Type and order code SI 5TE SI 7TE SI 9TE SI 11TE2 Design2.1 Degree of protection according to EN 60 529 IP 20 IP 20 IP 20 IP 20

    2.2 Installation Location Indoors Indoors Indoors Indoors

    3 Performance data3.1 Operating temperature limits:

    Heating water flow C Up to 58 Up to 58 Up to 58 Up to 58

    Brine (heat source) C -5 to +25 -5 to +25 -5 to +25 -5 to +25

    Antifreeze Mono-ethylene glycolMono-ethylene

    glycolMono-ethylene

    glycolMono-ethylene

    glycol

    Minimum brine concentration (-13 C freezing temperature) 25% 25% 25% 25%

    3.2 Temperature spread of heating water (flow/return flow)at B0 / W35 K 10.1 5.0 9.9 5.0 10.5 5.0 10.1 5.0

    3.3 Heat output / COP at B-5 / W55 1 kW / ---

    1. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, both the bivalence point and the regulation shouldalso be taken into consideration. The specified values, e.g. B10 / W55, have the following meaning: Heat source temperature 10 C and heating water flow temperature 55 C.

    3.8 / 2.0 5.6 / 2.2 7.7 / 2.3 9.4 / 2.4

    at B0 / W45 1 kW / --- 5.0 / 2.9 6.6 / 3.0 8.7 / 3.211.2 /

    3.2

    at B0 / W50 1 kW / --- 4.8 / 2.8 6.7 / 2.9 9.0 / 3.111.3 /

    3.0

    at B0 / W35 1 kW / --- 5.3 / 4.3 5.2 / 4.1 6.9 / 4.3 6.8 / 4.1 9.2 / 4.4 9.0 / 4.211.8 /

    4.411.7 /

    4.2

    3.4 Sound power level dB(A) 54 55 56 56

    3.5 Heating water flow with an internal pressure differential of m/h / Pa 0.45 / 19000.9 / 7400

    0.6 /3300

    1.2 / 13000

    0.75 / 2300

    1.6 / 10300

    1.0 /4100

    2.0 / 16100

    3.6 Brine throughput with an internal pressuredifferential (heat source) of m/h / Pa

    1.2 /16000

    1.2 / 16000

    1.7 / 29500

    1.6 / 26500

    2.3 / 25000

    2.2 / 23000

    3.0 / 24000

    2.7 / 20000

    3.7 Refrigerant; total filling weight type / kg R407C / 1.2 R407C / 1.1 R407C / 1.6 R407C / 1.7

    4 Dimensions, connections and weight4.1 Device dimensions without connections 2 H x W x L mm

    2. Note that additional space is required for pipe connections, operation and maintenance.

    805 650 462 805 650 462 805 650 462 805 650 4624.2 Device connections to heating system Inch G 1" external G 1" external G 1" external G 1" external

    4.3 Device connections to heat source Inch G 1" external G 1" external G 1" external G 1" external

    4.4 Weight of the transportable unit(s) incl. packing kg 109 111 118 122

    5 Electrical Connection5.1 Nominal voltage; fuse protection V / A 400 / 16 400 / 16 400 / 16 400 / 16

    5.2 Nominal power consumption 1 B0 W35 kW 1.23 1.27 1.6 1.66 2.07 2.14 2.66 2.79

    5.3 Starting current with soft starter A 22 (without SS) 30 (without SS) 15 26

    5.4 Nominal current B0 W35 / cos A / --- 2.22 / 0.82.29 /

    0.82.89 / 0.8 3 / 0.8

    3.77 / 0.8

    3.86 / 0.8

    4.84 / 0.8

    5.03 / 0.8

    6 Complies with the European safety regulations 3

    3. See CE declaration of conformity

    3 3 3

    7 Additional model features7.1 Water in device protected against freezing 4

    4. The heat circulating pump and the heat pump controller must always be ready for operation.

    Yes Yes Yes Yes

    7.2 Performance levels 1 1 1 1

    7.3 Controller internal/external Internal Internal Internal InternalE-8

  • Engl

    ish

    12Device information for brine-to-water heat pumps for heating purposes SI 14TE - SI 21TE

    1 Type and order code SI 14TE SI 17TE SI 21TE2 Design2.1 Degree of protection according to EN 60 529 IP 20 IP 20 IP 20

    2.2 Installation Location Indoors Indoors Indoors

    3 Performance data3.1 Operating temperature limits:

    Heating water flow C Up to 58 Up to 58 Up to 58

    Brine (heat source) C -5 to +25 -5 to +25 -5 to +25

    Antifreeze Mono-ethylene glycol Mono-ethylene glycol Mono-ethylene glycol

    Minimum brine concentration (-13 C freezing temperature) 25% 25% 25%

    3.2 Temperature spread of heating water (flow/return flow)at B0 / W35 K 9.6 5.0 9.3 5.0 11.3 5.0

    3.3 Heat output / COP at B-5 / W55 1 kW / --- 12.5 / 2.6 14.4 / 2.6 17.9 / 2.5

    at B0 / W45 1 kW / --- 14.1 / 3.5 16.2 / 3.4 19.8 / 3.2

    at B0 / W50 1 kW / --- 14.2 / 3.4 16.7 / 3.2 20.4 / 3.1

    at B0 / W35 1 kW / --- 14.5 / 4.5 14.4 / 4.3 17.1 / 4.6 16.9 / 4.4 21.1 / 4.3 20.8 / 4.1

    3.4 Sound power level dB(A) 56 58 59

    3.5 Heating water flow with an internal pressure differential of m/h / Pa 1.3 / 4800 2.5 / 17600 1.5 / 4000 2.9 / 15000 1.6 / 4600 3.6 / 23000

    3.6 Brine throughput with an internal pressuredifferential (heat source) of m/h / Pa 3.5 / 20000 3.3 / 18000 3.8 / 18000 3.8 / 18000 5.5 / 10000 5.4 / 9800

    3.7 Refrigerant; total filling weight type / kg R407C / 2.1 R407C / 2.3 R407C / 4.5

    4 Dimensions, connections and weight4.1 Device dimensions without connections 2 H x W x L mm 805 650 462 805 650 462 1445 650 5754.2 Device connections to heating system Inch G 1" external G 1" external G 1" external

    4.3 Device connections to heat source Inch G 1" external G 1" external G 1" external

    4.4 Weight of the transportable unit(s) incl. packing kg 130 133 225

    5 Electrical Connection5.1 Nominal voltage; fuse protection V / A 400 / 16 400 / 16 400 / 20

    5.2 Nominal power consumption 1 B0 W35 kW 3.22 3.37 3.72 3.86 4.91 5.10

    5.3 Starting current with soft starter A 26 27 29

    5.4 Nominal current B0 W35 / cos A / --- 5.81 / 0.8 6.08 / 0.8 6.35 / 0.8 6.64 / 0.8 8.86 / 0.8 9.2 / 0.86 Complies with the European safety regulations 3 3 3

    7 Additional model features7.1 Water in device protected against freezing 4 Yes Yes Yes

    7.2 Performance levels 1 1 1

    7.3 Controller internal/external Internal Internal Internal

    1. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, both the bivalence point and the regulation shouldalso be taken into consideration. The specified values, e.g. B10 / W55, have the following meaning: Heat source temperature 10 C and heating water flow temperature 55 C.

    2. Note that additional space is required for pipe connections, operation and maintenance.3. See CE declaration of conformity

    4. The heat circulating pump and the heat pump controller must always be ready for operation.www.dimplex.de E-9

  • F-1

    Franais

    Table des matires1 A lire immdiatement ! ................................................................................................................. F-2

    1.1 Remarques importantes..........................................................................................................................F-21.2 Dispositions lgales et directives ............................................................................................................F-21.3 Utilisation de la pompe chaleur pour conomiser de l'nergie.............................................................F-2

    2 Utilisation de la pompe chaleur................................................................................................ F-32.1 Domaine dutilisation...............................................................................................................................F-32.2 Fonctionnement ......................................................................................................................................F-3

    3 Appareil de base ........................................................................................................................... F-3

    4 Accessoires................................................................................................................................... F-44.1 Distributeur d'eau glycole......................................................................................................................F-4

    5 Transport ....................................................................................................................................... F-4

    6 Installation..................................................................................................................................... F-46.1 Gnralits..............................................................................................................................................F-46.2 Emissions sonores..................................................................................................................................F-4

    7 Montage ......................................................................................................................................... F-47.1 Remarques dordre gnral ....................................................................................................................F-47.2 Branchement ct installation de chauffage ...........................................................................................F-47.3 Raccordement ct source de chaleur ...................................................................................................F-57.4 Branchements lectriques ......................................................................................................................F-5

    8 Mise en service ............................................................................................................................. F-58.1 Gnralits..............................................................................................................................................F-58.2 Prparation .............................................................................................................................................F-68.3 Procdures suivre lors de la mise en service ......................................................................................F-6

    9 Entretien / nettoyage .................................................................................................................... F-69.1 Entretien..................................................................................................................................................F-69.2 Nettoyage ct chauffage .......................................................................................................................F-69.3 Nettoyage ct source de chaleur ..........................................................................................................F-7

    10 Dfaillances / recherche de pannes............................................................................................ F-7

    11 Mise hors service / mise au rebut ............................................................................................... F-7

    12 Informations sur les appareils..................................................................................................... F-8

    Anhang / Appendix / Annexes............................................................................................................. A-I

  • Fran

    ais

    1.31 A lire immdiatement !

    1.1 Remarques importantes

    ATTENTION !La pompe chaleur nest pas fixe la palette en bois.

    ATTENTION !Lors du transport, langle dinclinaison de la pompe chaleur ne doit pasdpasser 45 (dans tous les sens).

    ATTENTION !Ne pas soulever lappareil en utilisant les orifices de lhabillage !

    ATTENTION !Rincer l'installation de chauffage avant de brancher la pompe chaleur.

    ATTENTION !Monter, sur la pompe chaleur, le collecteur dimpurets qui vous estlivr dans louverture dadmission de la source de chaleur, afin deprotger lvaporateur des salissures.

    ATTENTION !La teneur de leau glycole en produit antigel base de monothylne-glycol ou propylne-glycol, doit tre dau moins 25% et celle-ci doit tremlange avant le remplissage.

    ATTENTION !Lors du raccordement, faire attention la rotation droite du champmagntique de lalimentation de charge (la pompe chaleur napporteaucune puissance si le champ magntique est incorrect et devient trsbruyante).

    ATTENTION !La mise en service de la pompe chaleur doit seffectuer conformmentaux instructions de montage et dutilisation du rgulateur de pompe chaleur.

    ATTENTION !Il est recommand de faire appel un systme appropri de protectioncontre la corrosion pour viter les dpts (rouille par ex.) dans lecondensateur de la pompe chaleur.

    ATTENTION !Les travaux sur la pompe chaleur doivent tre effectus uniquement pardes techniciens qualifis et agrs.

    ATTENTION !Avant douvrir lappareil, assurez-vous que tous les circuits lectriquessont bien hors tension.

    1.2 Dispositions lgales et directives

    La pompe chaleur est conforme toutes les prescriptions DIN/VDE et toutes les directives CE affrentes. Celles-ci sont non-ces dans la dclaration de conformit CE en annexe.Le branchement lectrique de la pompe chaleur doit tre ra-lis selon les normes VDE, EN et CEI en vigueur. En outre, ilconvient de respecter les conditions techniques de branchementdes fournisseurs dnergie. La pompe chaleur doit tre intgre l'installation de chauf-fage et de source de chaleur, en conformit avec les prescrip-tions affrentes.Les personnes, en particulier les enfants, qui, compte tenu deleurs capacits physiques, sensorielles ou intellectuelles, ou deleur manque d'exprience ou de connaissances, ne sont pas enmesure d'utiliser l'appareil en toute sret, ne devraient pas lefaire en l'absence ou sans instructions d'une personne responsa-ble.Les enfants doivent tre surveills pour viter qu'ils ne jouentavec l'appareil.

    1.3 Utilisation de la pompe chaleur pour conomiser de l'nergie

    En utilisant cette pompe chaleur, vous contribuez prserverlenvironnement. Pour obtenir un fonctionnement efficace, il esttrs important de dimensionner prcisment linstallation dechauffage et la source de chaleur. Dans cette optique, une atten-tion toute particulire doit tre prte aux tempratures de dpartde leau, qui doivent tre les plus basses possible. Cest pour-quoi tous les consommateurs dnergie relis linstallation doi-vent tre dimensionns pour des tempratures de dpart bas-ses. Une temprature deau de chauffage qui augmente de 1 Ksignifie une augmentation de la consommation dnergie de2,5% environ. Un chauffage basse temprature avec des temp-ratures dpart entre 30 et 50 C saccorde bien avec un fonction-nement conomique en nergie. www.dimplex.de F-2

  • Franais

    22 Utilisation de la pompe chaleur

    2.1 Domaine dutilisationLa pompe chaleur eau glycole-eau peut tre utilise dans lesinstallations de chauffage dj en place ou nouvelles. Leau gly-cole sert de fluide caloporteur dans la pompe chaleur.Comme source de chaleur, des sondes gothermiques, des col-lecteurs enterrs ou dautres installations similiaires peuvent treutiliss.

    2.2 FonctionnementLe sol emmagasine la chaleur apporte par le soleil, le vent et lapluie. Cette chaleur gothermique est capte par leau glycole temprature basse dans le collecteur enterr, la sonde go-thermique ou autre. Un circulateur refoule ensuite leau glycoleainsi chauffe vers lvaporateur de la pompe chaleur danslequel la chaleur est dlivre au fluide frigorigne du circuit frigo-rifique. Par cette opration, leau glycole se refroidit nouveaude manire pouvoir une nouvelle fois, dans le circuit deau gly-cole, absorber de lnergie thermique.Cependant, le fluide frigorigne est aspir par le compresseur commande lectrique, compress et pomp un niveau detemprature plus lev. Lnergie lectrique mise dispositiontout au long de ce procd nest pas perdue, elle est transfreau contraire galement en grande partie au fluide frigorigne.Le fluide frigorigne arrive alors dans le condenseur o sontour, il transmet lnergie thermique leau de chauffage. Ainsi,leau de chauffage chauffe et atteint des tempratures pouvantaller, en fonction du point de fonctionnement, jusqu 60 C.

    3 Appareil de baseIl s'agit d'une pompe chaleur pour installation intrieure, prte brancher, avec jaquette en tle, panneau de commande et r-gulateur intgr. Le fluide frigorigne R407C est utilis dans lecircuit rfrigrant, il est sans HCFC, non combustible et ne dtruitpas la couche d'ozone.Sur le panneau de commande figurent toutes les pices nces-saires lutilisation de la pompe chaleur. Une sonde pour me-surer la temprature du mur extrieur et son petit matriel defixation ainsi qu'un collecteur d'impurets sont livrs avec l'appa-reil. Les raccordements pour la tension destine au courant decharge et de commande doivent tre effectus par le client.La ligne d'alimentation de la pompe eau glycole, installe parle client, doit tre raccorde au panneau de commande. A cetteoccasion, prvoir une protection moteur, si ncessaire.La connexion du collecteur au distributeur deau glycole doittre ralise par le client.

    1) Condenseur2) Panneau de commande3) Evaporateur4) Compresseur

    F-3

  • Fran

    ais

    7.24 Accessoires

    4.1 Distributeur d'eau glycoleLe distributeur deau glycole runit les boucles du collecteur delinstallation de source de chaleur pour former une conduite prin-cipale qui, elle, est raccorde la pompe chaleur. Les robinets boisseau sphrique intgrs permettent de couper chaque cir-cuit deau glycole pour permettre une purge.

    5 TransportLe transport par chariot lvateur convient bien un dplace-ment sur surface plane. Si la pompe chaleur doit tre convoyesur une surface non plane ou dans des escaliers, il est possiblede le faire l'aide de sangles, que l'on peut glisser directementsous la palette en bois.

    ATTENTION !La pompe chaleur nest pas fixe la palette en bois.

    ATTENTION !Lors du transport, langle dinclinaison de la pompe chaleur ne doit pasdpasser 45 (dans tous les sens).

    Pour soulever lappareil sans palette, veuillez utiliser les orificesprvus dans le chssis, sur les cts. Retirer cet effet les pan-neaux latraux de lhabillage. Pour vous aider porter lappareil,un tube quelconque fera laffaire.

    ATTENTION !Ne pas soulever lappareil en utilisant les orifices de lhabillage !

    6 Installation

    6.1 GnralitsN'installer l'appareil qu' l'intrieur, dans des pices non humi-des sur une surface plane, lisse et horizontale. Ici, le chssis dela pompe chaleur doit adhrer au sol sur toute sa circonfrenceafin de garantir une isolation acoustique approprie. Si tel n'estpas le cas, des mesures d'absorption acoustique complmentai-res seront ventuellement ncessaires.La pompe chaleur doit tre mise en place de telle manire quele service aprs-vente puisse y accder sans problmes, ce quine fait aucun doute, si on laisse un espace denv. 1 m devant etsur les cts de la pompe chaleur.

    6.2 Emissions sonoresEn raison de son isolation sonore efficace, la pompe chaleurest trs silencieuse. Pour viter la transmission de vibrations surles fondations, un tapis amortissant caoutchout appropri de-vrait tre pos sous le chssis de base de la pompe chaleur.Pour viter la transmission de bruits au systme de chauffage, ilest recommand de raccorder la pompe chaleur au systme dechauffage l'aide de tuyaux souples.

    7 Montage

    7.1 Remarques dordre gnralLes raccordements suivants doivent tre raliss sur la pompe chaleur : Circuits dpart et retour de linstallation eau glycole Circuits dpart et retour du chauffage Alimentation lectrique

    7.2 Branchement ct installation de chauffage

    ATTENTION !Rincer l'installation de chauffage avant de brancher la pompe chaleur.

    Avant de procder au raccordement de la pompe chaleur cteau de chauffage, linstallation de chauffage doit tre rince pourliminer dventuelles impurets et les restes ventuels des ma-triaux dtanchit ou autres. Une accumulation de dpts di-vers dans le condenseur est susceptible d'entraner une d-faillance totale de la pompe chaleur.www.dimplex.de F-4

  • Franais

    7.3Une fois le montage ct chauffage termin, linstallation dechauffage devra tre remplie, purge et prouve la pression.Les sondes livres dans le botier de commande doivent trefixes et isoles selon le schma de principe en annexe.

    Dbit d'eau de chauffage minimumQuel que soit l'tat de fonctionnement de l'installation de chauf-fage, un dbit d'eau de chauffage minimum doit tre garanti dansla pompe chaleur. C'est tout fait ralisable en montant un dis-tributeur exempt de pression diffrentielle ou une vanne de trop-plein. Vous trouverez des explications quant au rglage d'unevanne de trop-plein dans le chapitre Mise en service .

    Protection antigel dans le cas dune installation expose au gelLa fonction de protection antigel du rgulateur est active dsque le rgulateur et les circulateurs de chauffage sont prts fonctionner. Linstallation doit tre vidange dans le cas dunemise hors service de la pompe chaleur ou en cas de panne decourant. Pour les installations de pompe chaleur qui pourraienttre victimes de pannes de courant non dcelables (maison devacances), le circuit de chauffage doit fonctionner avec une pro-tection anti-gel approprie.

    7.3 Raccordement ct source de chaleur

    Pour le raccordement, il faut procder exactement comme indi-qu ci-aprs :raccorder la conduite deau glycole aux circuits dpart et retourde la pompe chaleur. Suivre pour cela les indications duschma hydraulique.

    ATTENTION !Monter, sur la pompe chaleur, le collecteur dimpurets qui vous estlivr dans louverture dadmission de la source de chaleur, afin deprotger lvaporateur des salissures.

    Un sparateur dair doit en plus tre mont dans l'installation desource de chaleur.Prparer leau glycole avant de remplir linstallation. La concen-tration de leau glycole doit se monter au moins 25 %, ce quigarantit une protection contre le gel jusqu' -14 C.Seul, les produits antigel base de monothylne-glycol ou pro-pylneglycol peuvent tre utiliss.Linstallation de source de chaleur doit tre purge et soumise des contrles dtanchit.

    ATTENTION !La teneur de leau glycole en produit antigel base de monothylne-glycol ou propylne-glycol, doit tre dau moins 25% et celle-ci doit tremlange avant le remplissage.

    7.4 Branchements lectriquesBranchements lectriques effectuer sur la pompe chaleur. Branchement de la ligne de commande sur le panneau de

    commande de la pompe chaleur par la borne X1 : L/N/PE. Branchement de la ligne de charge sur le panneau de com-

    mande de la pompe chaleur par la borne X5/X6 : L1/L2/L3/PE.

    Branchement de la pompe eau glycole (par le client) surle panneau de commande de la pompe chaleur par laborne X1 : PE et contacteur de pompe K2 : 2/4/6 (SI 5TE -SI 17TE), ou protection moteur F7 : 2/4/6 (SI 21TE). Dans lecas de SI 5TE - SI 14TE, une pompe eau glycole ali-mentation monophase peut galement tre utilise en op-tion (voir ce sujet le schma de connexion des bornes).

    Tous les composants lectriques ncessaires lutilisation de lapompe chaleur se trouvent sur le panneau de commande.Des instructions prcises sur le raccordement et la fonction durgulateur de pompe chaleur (par exemple sonde mur ext-rieur) vous sont fournies dans les instructions d'utilisation du r-gulateur jointes la machine.Il faut prvoir une coupure avec au moins 3 mm d'cartementd'ouverture de contact (p. ex. disjoncteur de blocage du fournis-seur dnergie ou contacteur de puissance) ainsi qu'un coupe-circuit automatique tripolaire, avec dclenchement simultan detous les conducteurs extrieurs. La section du conducteur n-cessaire doit tre dtermine en fonction de la puissance absor-be de la pompe chaleur, des conditions techniques de bran-chement de chaque fournisseur dnergie et selon lesprescriptions affrentes. Vous trouverez les donnes sur la puis-sance absorbe par la pompe chaleur dans les informationsproduits ou sur la plaque signaltique. Les bornes de connexionsont dimensionnes pour une section du conducteur de 10 mmmaximum.

    ATTENTION !Lors du raccordement, faire attention la rotation droite du champmagntique de lalimentation de charge (la pompe chaleur napporteaucune puissance si le champ magntique est incorrect et devient trsbruyante).

    8 Mise en service

    8.1 GnralitsPour garantir une mise en service en rgle, cette dernire doittre effectue par un service aprs-vente agr par le construc-teur. Ceci permet de prolonger la garantie sous certaines condi-tions.F-5

  • Fran

    ais

    9.28.2 PrparationAvant la mise en service, il est impratif de procder aux vrifica-tions suivantes : tous les raccordements de la pompe chaleur doivent tre

    raliss comme dcrit au chapitre 7. l'installation de source de chaleur et le circuit de chauffage

    doivent tre remplis et tests. le collecteur d'impurets doit se trouver dans l'ouverture

    d'admission d'eau glycole de la pompe chaleur. dans les circuits de chauffage et d'eau glycole, toutes les

    vannes susceptibles de perturber l'coulement doivent treouvertes.

    le rgulateur de la pompe chaleur doit tre accord l'ins-tallation de chauffage conformment ses instructions deservice.

    8.3 Procdures suivre lors de la mise en service

    La mise en service de la pompe chaleur seffectue via le rgu-lateur de pompe chaleur.

    ATTENTION !La mise en service de la pompe chaleur doit seffectuer conformmentaux instructions de montage et dutilisation du rgulateur de pompe chaleur.

    Si le dbit minimal en eau de chauffage est assur par unevanne de trop-plein, il faut l'adapter l'installation de chauffage.Un mauvais rglage pourrait conduire divers messages der-reur et une augmentation du besoin en nergie lectrique. Pourrgler la soupape de trop-plein correctement, nous vous con-seillons de procder de la manire suivante.Fermez tous les circuits de chauffage pouvant l'tre en phase defonctionnement, selon l'utilisation qu'il en est faite ; ceci ayantpour but d'obtenir le dbit d'eau le plus dfavorable. En rgle g-nrale, ce sont les circuits de chauffage des locaux donnant surle ct sud et ouest. Au moins un des circuits de chauffage doitrester ouvert (par ex. salle de bains).La vanne de trop-plein est ouvrir au maximum de telle sorteque, pour la temprature actuelle des sources dnergie, l'tale-ment maximal de temprature, indiqu dans le tableau, entre cir-cuit dpart et retour du chauffage, soit obtenu. Il faut mesurerl'talement de temprature le plus proche possible de la pompe chaleur. La cartouche chauffante doit tre dsactive pour desinstallations mono-nergtiques.

    Les anomalies qui se produisent lors du fonctionnement sontgalement affiches au rgulateur PAC et peuvent tre limi-nes suivant les indications du manuel de service du rgulateur.

    9 Entretien / nettoyage

    9.1 EntretienLa pompe chaleur travaille sans interventions en maintenance.Pour viter des dysfonctionnements dus des dpts dans leschangeurs thermiques de la pompe chaleur, il faut veiller cequ'aucune sorte de dpt ne puisse s'introduire dans les installa-tions de chauffage et de source de chaleur. Si des dysfonction-nements dus des impurets devaient quand mme se produire,linstallation devra tre nettoye comme indiqu ci-aprs.

    9.2 Nettoyage ct chauffageLoxygne est susceptible dentraner la formation de produitsdoxydation (rouille) dans leau de chauffage, notamment lorsquedes composants en acier sont utiliss. Celui-ci gagne le systmede chauffage par les vannes, les circulateurs ou les tuyaux enmatire plastique. Cest pourquoi il faut veiller ce que linstalla-tion reste tanche la diffusion, notamment en ce qui concerneles tuyaux du chauffage au sol.

    ATTENTION !Il est recommand de faire appel un systme appropri de protectioncontre la corrosion pour viter les dpts (rouille par ex.) dans lecondensateur de la pompe chaleur.

    Il est galement possible que leau de chauffage soit souille pardes restes de graisse et dagents dtanchification.Si en raison dimpurets la puissance du condenseur de lapompe chaleur se trouve rduite, linstallation devra tre net-toye par linstallateur.Dans l'tat actuel des connaissances, nous conseillons de pro-cder au nettoyage avec de lacide phosphorique 5 % ou, si lenettoyage est plus frquent, avec de lacide formique 5 %.Dans les deux cas, le liquide de nettoyage doit tre la tempra-ture ambiante. Il est recommand de nettoyer l'changeur dechaleur dans le sens contraire au sens normal du dbit.Pour viter linfiltration de nettoyant contenant de lacide dans lecircuit de linstallation de chauffage, nous vous recommandonsde raccorder lappareil de nettoyage directement sur le dpart etle retour du condenseur. Il faut ensuite soigneusement rincer laide de produits neutralisants adquats, afin dviter tous dom-mages provoqus par dventuels restes de produits de net-toyage dans le systme.Les acides doivent tre utiliss avec prcaution et les prescrip-tions des caisses de prvoyance des accidents doivent tre res-pectes.En cas de doute, prendre contact avec les fabricants des pro-duits chimiques !

    Tempraturesource de chaleur

    Diffrence de temprature max.entre circuits dpart et retour du

    chauffagede -5 C 0 C 10 K

    1 C 5 C 11 K

    6 C 9 C 12 K

    10 C 14 C 13 K

    15 C 20 C 14 K

    21 C 25 C 15 Kwww.dimplex.de F-6

  • Franais

    9.39.3 Nettoyage ct source de chaleur

    ATTENTION !Monter, sur la pompe chaleur, le collecteur dimpurets qui vous estlivr dans louverture dadmission de la source de chaleur, afin deprotger lvaporateur des salissures.

    Le tamis du filtre du collecteur dimpurets doit tre nettoy lelendemain de la mise en service, puis toutes les semaines. Siaucune souillure nest plus signaler, on pourra dmonter letamis du filtre et rduire ainsi les pertes de pression.

    10 Dfaillances / recherche de pannes

    Cette pompe chaleur est un produit de qualit et elle devraitfonctionner sans dysfonctionnements. Si un dysfonctionnementdevait quand mme survenir, celui-ci sera affich sur lcran durgulateur de pompe chaleur. Rfrez-vous pour cela la pagedes dysfonctionnements et de recherche de panne dans les ins-tructions du rgulateur de pompe chaleur.Si vous n'tes pas en mesure de remdier vous-mme au dys-fonctionnement, veuillez vous adresser au service aprs-ventecomptent.

    ATTENTION !Les travaux sur la pompe chaleur doivent tre effectus uniquement pardes techniciens qualifis et agrs.

    ATTENTION !Avant douvrir lappareil, assurez-vous que tous les circuits lectriquessont bien hors tension.

    11 Mise hors service / mise au rebut

    Avant de dmonter la pompe chaleur, il faut mettre la machinehors tension et fermer toutes les vannes. Il faut se conformer auxexigences relatives l'environnement quant la rcupration, larutilisation et llimination de consommables et de composantsen accord avec les normes en vigueur. Une attention toute parti-culire doit tre prte lvacuation du rfrigrant et de lhuilede la machine frigorifique, qui doit seffectuer selon les rgles delart.F-7

  • Fran

    ais

    1212 Informations sur les appareils

    Informations sur les pompes chaleur eau glycole/eau pour chauffage SI 5TE - SI 11TE

    1 Dsignation technique et commerciale SI 5TE SI 7TE SI 9TE SI 11TE2 Forme2.1 Degr de protection selon EN 60 529 IP 20 IP 20 IP 20 IP 20

    2.2 Emplacement intrieur intrieur intrieur intrieur

    3 Indications de puissance3.1 Temprature - limites dexploitation :

    Dpart eau de chauffage C moins de 58 moins de 58 moins de 58 moins de 58

    Eau glycole (source de chaleur) C entre -5 et +25 entre -5 et +25 entre -5 et +25 entre -5 et +25

    Antigel monothylne-glycol monothylne-

    glycol monothylne-

    glycol monothylne-

    glycol

    Concentration minimale en eau glycole (temprature de gel -13C) 25% 25% 25% 25%

    3.2 Plage de tempratures eau de chauffage pour B0 / W35 K 10,1 5,0 9,9 5,0 10,5 5,0 10,1 5,0

    3.3 Capacit therm. / coef. puissance pour B-5 / W55 1 kW / ---

    1. Ces indications caractrisent la taille et le rendement de linstallation. Le point de bivalence et la rgulation sont prendre en compte pour des considrations conomiques etnergtiques. Ici, B10 / W55 signifie par ex. : temprature extrieure 10 C et temprature dpart eau de chauffage 55 C.

    3,8 / 2,0 5,6 / 2,2 7,7 / 2,3 9,4 / 2,4

    pour B0 / W45 1 kW / --- 5,0 / 2,9 6,6 / 3,0 8,7 / 3,211,2 /

    3,2

    pour B0 / W50 1 kW / --- 4,8 / 2,8 6,7 / 2,9 9,0 / 3,111,3 /

    3,0

    pour B0 / W35 1 kW / --- 5,3 / 4,3 5,2 / 4,1 6,9 / 4,3 6,8 / 4,1 9,2 / 4,4 9,0 / 4,211,8 /

    4,411,7 /

    4,2

    3.4 Niveau de puissance sonore dB(A) 54 55 56 56

    3.5 Dbit deau de chauffage avec pression diff. int. m/h / Pa 0,45 / 19000,9 / 7400

    0,6 /3300

    1,2 / 13000

    0,75 / 2300

    1,6 / 10300

    1,0 /4100

    2,0 / 16100

    3.6 Dbit eau glycole avec pression diff. int. (source chaleur) m/h / Pa

    1,2 /16000

    1,2 / 16000

    1,7 / 29500

    1,6 / 26500

    2,3 / 25000

    2,2 / 23000

    3,0 / 24000

    2,7 / 20000

    3.7 Fluide frigor